7-24
EB 6493 EN
Start-up and configuration at the device
1. In manual mode, set the manipulated variable
Y
to the operating point so that the con-
trolled variable
X
has the same value as the set point
W
.
2.
Raise the manipulated variable
Y
, for example by 10 % (with step change value of the
manipulated variable
Y.JMP
= 20 %) and wait until the controlled variable
X
does not
change anymore.
3. Check whether the controlled variable is within the permissible range.
4.
Reduce the manipulated variable
Y
, for example by 20 % (with step change value of the
manipulated variable
Y.JMP
= 20 %) and wait until the controlled variable
X
does not
change anymore.
5. Check whether the controlled variable is within the permissible range.
6. In the TUNE menu, select
-CO- ADAP
function and set the step change value Y.JMP.
7. In the TUNE menu, select
-CO- ADAP
function. Select 'run ADP.S' to start the adaptation.
How long the adaptation takes is determined by the time behavior of the controlled sys
-
tem. If the controlled variable does not reach an end value within five hours, the adapta
-
tion is automatically canceled.
After starting the adaptation, status messages on the start-up adaptation are displayed in the
top row.
Messages
10
Adaptation started
20
Noise measurement (approx. 10 seconds)
40
Step-change value output (Y = YPID + Y.JMP)
Wait for controlled system to react (step response)
41
Step-change value output (Y = YPID + Y.JMP)
Wait for controlled system to settle
50
Returned to output value before starting adaptation
Determining parameters
70, 71, 72, End
Adaptation finished
Press key to cancel the adaptation.
If an error occurs during adaptation, the error appears on the display and the binary output
for fault alarms is activated (see the 'Malfunctions' section).
Note
Summary of Contents for Trovis 6493
Page 6: ...Contents EB 6493 EN...
Page 22: ...3 10 EB 6493 EN...
Page 30: ...5 6 EB 6493 EN...
Page 36: ...6 6 EB 6493 EN...
Page 72: ...8 12 EB 6493 EN...
Page 84: ...11 2 EB 6493 EN...
Page 86: ...12 2 EB 6493 EN...
Page 88: ...13 2 EB 6493 EN...
Page 90: ...14 2 EB 6493 EN...
Page 92: ...15 2 EB 6493 EN...
Page 95: ...EB 6493 EN 16 3 Certificates TR CU certificate...
Page 96: ...16 4 EB 6493 EN Certificates...
Page 97: ...EB 6493 EN 16 5 Certificates...
Page 98: ...16 6 EB 6493 EN...
Page 125: ......
Page 126: ......
Page 127: ......