80 | SAMLEX AMErICA INC.
6.4 oPtionAL reMote ControL eVo-rC (see Appendix A) For
ProgrAMMing oF MoDeS oF oPerAtion AnD PArAMeterS
Optional remote Control Model EVO-rC (fig 2.4) will be required for more advanced control
and monitoring. Please see separate Owner’s Manual for EVO-rC at Appendix A. The remote
Control comes with 10M / 33 ft., rJ-45 Data Cable. The remote plugs into rJ-45 Jack on
the front panel of the unit (7, fig 2.1). It has provision for Data Logging using SD Card of up
to 16 Gb (fAT16 / fAT32). It also has its own real Time Clock and Super Capacitor Type of
battery.
Detailed messaging is available through its LCD display and LEDs. This remote will also
be required for programming of various parameters to suit specific requirements. Each
programmable parameter has a Default Value. This unit has been shipped with the various
parameters set at the Default Values. Programmable and Default values are shown in Tables
6.2 to 6.6:
tAbLe 6.2 ProgrAMMAbLe AnD DeFAuLt PArAMeterS: grouP ChArging CurVe
Parameter
Programming range
(Programming requires optional
remote Control Model eVo-rC)
Default
eVo-
2212e
eVo-
3012e
eVo-
2224e
eVo-
4024e
eVo-
2212e
eVo-
3012e
eVo-
2224e
eVo-
4024e
“buLk Current”
(bulk Charge Current “Io”)
0-100A
0-130A
0-70A
0-110A
40A
“AbSorP VoLtAge”
(Absorption Voltage)
13.5V - 16.0V
27.0V - 32.0V
14.4V
28.8V
“eQuALiZe VoLtAge”
(Equalization Voltage)
14.0V - 16.0V
28.0V - 32.0V
14.4V
28.8V
“FLoAting VoLtAge"
(float Voltage)
13.0V - 15.0V
26.0V - 30.0V
13.5V
27.0V
“CoMPenSAte”
(Temperature Compensation)
-3mV to -5mV /°C/Cell
-4mV /°C/Cell
“Low VoLt ALArM”
(battery Low Voltage Alarm)
9.5V - 12.5V
19.0V - 25.0V
11.0V
22.0V
“bAtt Low VoLtAge”
(battery Low Voltage Shut
Down)
9.1V - 12.0V
18.1V - 24.0V
10.5V
21.0V
“LV DeteCt tiMe”
(Low Voltage Detect Time)
0-600 sec
10 sec
“LV Cut oFF tiMe”
(Low Voltage Cut Off Time)
0-7200 sec
1200 sec
“reSet VoLtAge”
(battery Low Voltage reset)
12.0V - 17.0V
24.0V - 35.0V
14.0V
28.0V
“bAtt oVer VoLt”
(battery Over Voltage Shut
Down)
14.0V - 17.0V
28.0V - 35.0V
16.0V
32.0V
“ChArge MoDe”
( 3 or 4 Stage Charging)
Normal (3-Stage) / Equalization (4-Stage)
Normal (3-Stage)
"onLine MoDe" or
"oFFLine MoDe"
0 = Off 1 = On
0 = Off
SECTIOn 6 |
Operation, Protections and Troubleshooting