30 | SAMLEX AMERICA INC.
APPENDIX A
4.7 GRoUP 4 PARAMeteR Set UP: inPUt HiGH LiMit
Please refer to Parameters under Group 4 at Fig 4.1. Details of Parameter set up are given below:
tABLe 4.7. GRoUP 4 PARAMeteR Set UP: inPUt HiGH LiMit
Screen
no. for
Group 4
(Fig 4.1)
Parameter
Setting range
Default value
eVo-
2212e
eVo-
3012e
eVo-
222e
eVo-
4024e
eVo-
2212e
eVo-
3012e
eVo-
2224e
eVo-
4024e
1
ReSet VoLtAGe
200.0 – 280.0V
260.0V
2
CUt oFF VoLt 1
200.0 – 280.0V
265.0V
3
DeteCt tiMe 1
0 – 2000 cycles
60 cycles
4
CUt oFF VoLt 2
200.0 – 280.0V
270.0V
5
DeteCt tiMe 2
0 – 2000 cycles
15 cycles
6
CUt oFF VoLt 3
200.0 – 280.0V
275.0V
7
DeteCt tiMe 3
0 – 2000 cycles
1 cycle
ReSet VoLtAGe:
This is the reset voltage at which the unit will revert to "Charging Mode" after it has switched
over to "Inverting Mode" due to input AC voltage rising to "CUT-OFF VOLT 1/CUT-OFF VOLT 2/
CUT-OFF VOLT 3.
SELECT GROUP
CHARGE CURVE
SELECT GROUP
INPUT HIGH LIMIT
RESET VOLTAGE
260.0 V
Up Key x 3
ò
Enter Key
ò
RESET VOLTAGE
260.0 V
ò
KEY IN PASSWORD
0000
Enter Key
ò
Password 8052
See Section 4.3.1
CUt oFF VoLt 1:
If during "Charging Mode", the AC input voltage rises above "CUT-OFF VOLT 1" for period >
"DETECT TIME 1", the EVO
TM
Inverter/Charger will transfer to "Inverting Mode".
SELECT GROUP
CHARGE CURVE
SELECT GROUP
INPUT HIGH LIMIT
CUT OFF VOLT 1
265.0 V
RESET VOLTAGE
260.0 V
Up Key x 3
ò
Enter Key
ò
Up Key x 1
ò
CUT OFF VOLT 1
275.0 V
ò
KEY IN PASSWORD
0000
Enter Key
ò
Password 8052
See Section 4.3.1
DeteCt tiMe 1:
This is the time limit in cycles up to which high AC input voltage "CUT-OFF VOLT 1" is allowed.
SELECT GROUP
CHARGE CURVE
SELECT GROUP
INPUT HIGH LIMIT
DETECT TIME 1
60 cycle
RESET VOLTAGE
260.0 V
Up Key x 3
ò
Enter Key
ò
Up Key x 2
ò
DETECT TIME 1
0060 cycle
ò
KEY IN PASSWORD
0000
Enter Key
ò
Password 8052
See Section 4.3.1
CUt oFF VoLt 2:
If during "Charging Mode", the AC input voltage rises above "CUT-OFF VOLT 2" for period >
"DETECT TIME 2", the EVO
TM
Inverter/Charger will transfer to "Inverting Mode".
SELECT GROUP
CHARGE CURVE
SELECT GROUP
INPUT HIGH LIMIT
CUT OFF VOLT 2
270.0 V
RESET VOLTAGE
260.0 V
Up Key x 3
ò
Enter Key
ò
Up Key x 3
ò
CUT OFF VOLT 2
270.0 V
ò
KEY IN PASSWORD
0000
Enter Key
ò
Password 8052
See Section 4.3.1
SECtION 4 |