background image

 

   

SAMLEX AMERICA INC.  |  89

SECTION 5  |

 

 Battery Charging in Evolution™ Series

5.8.2.1 Stage 1 – Bulk Charge Stage under 4-Stage Adaptive Charging Profile - Equalization

Refer to Section 1.4.3.1 for general information on Bulk Charge Stage and to Fig 5.2 for voltage and current curves 
during this stage.

5.8.2.1.1 

During the 1st “Bulk Charge Stage”, the batteries will be charged at constant current (CC) = the 

programmed value of parameter “BULK CURRENT” (“Io”) 

[Default value of Parameter “BULK CURRENT” is 20A.

 

See 

programming range at Table 6.2 and programming procedure at Section 4.4.2.1 in the EVO-RC-PLUS Remote Control 
Manual]

. The value of programmed parameter “BULK CURRENT” (“Io”) should normally be limited to 10% to 20% 

of the Ah capacity of the battery [Ah capacity at C-rate of discharge = C/20 (or, 0.05C)]. Higher current may be used 
if permitted by the battery manufacturer. The Bulk Charge Stage is displayed as “E-Bulk Stage” in the 2

nd

 line of 

Charging Mode Screens of EVO-RC-PLUS Remote Control. 

[Please refer to (i) Display Screen Nos. 1 to 5 in Fig 3.3(c) 

under Section 3.6.4.3 of EVO-RC-PLUS Remote Control Manual and, (ii) codes / abbreviations in Table 3.2 under 
Section 3.6.4.4 of EVO-RC-PLUS Remote Control Manual].

5.8.2.1.2  

A Software Timer is used to measure the time taken from the time the unit enters Bulk Stage to the time 

the battery voltage reaches 0.3V below the programmed value of parameter “ABSORP VOLTAGE” 

[Default value 

of parameter “ABSORP VOLTAGE” is 57.6V for EVO-4248SP. See programming range at Table 6.2, Section 6 and 
programming procedure at Section 4.4.2.2 in the EVO-RC-PLUS Remote Control Manual]

. This time is registered as 

Bulk Stage Time “To”. 

As part of Adaptive Algorithm, the following times are computed based on the Bulk 

Stage Time “To”:

a)  Absorption Stage Time T1' = 

To x 0.5

b)  Equalization Stage Time T2:

i.  T2 = T1' + 1 Hr = (To x 0.5) +1 Hr ; if  T1' is <2 Hrs
ii.  T2 = T1' + 2 Hrs = (To x 0.5) +2 Hr ; if  T1' is > 2 Hrs but  <4 Hrs
iii. T2 = T1' + 4 Hrs = (To x 0.5) +4 Hr ; if  T1' is > 4 Hrs 

5.8.2.1.3 

When the battery voltage rises to the programmed value of parameter “ABSORP VOLTAGE”, the charging 

stage transitions to the next Stage 2 – Absorption Stage described at Section 5.8.2.2

 [Default value of parameter 

“ABSORP VOLTAGE” is 57.6V for EVO-4248SP. See programming range at Table 6.2, Section 6 and programming 
procedure at Section 4.4.2.2 in the EVO-RC-PLUS Remote Control Manual]

.  

5.8.2.1.4 Automatic Adjustment of Internal AC Charger Current when External Solar Charge Controller  
is also Charging in Parallel

Please note that if an external solar charge controller is also used to charge the batteries at the same time in parallel 
with the internal AC charger of the unit, the charging current of the internal AC charger will be controlled so that the 
total charging current of the external charger and the internal charger is = the programmed "BULK CURRENT (

“Io”

[See Section 4.4.2.1 of EVO-RC-PLUS Remote Control Manual].

For example, if the programmed value of parameter “BULK CURRENT” (

“Io”

) is say 40A and the charging current 

from the external Solar Charge Controller is say 30A at any given instant, the internal AC charger will output only 
10A (

Programmed value of 40A minus external charging current of 30A = 10A

). Now, if the charging current from 

the External Charge Controller rises to say 50A, the internal AC charger will be reduced to 0A. 

Please refer to Section 5.4 for more details.

Summary of Contents for Evolution EVO-4248SP

Page 1: ...EvolutionTM Series Inverter Charger Pure Sine Wave Model EVO 4248SP Please read this manual BEFORE operating Firmware Rev 0 77 Owner s Manual...

Page 2: ...UFFICIENCY OR SUITABILITY OF ANY TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION 2 ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSSES DAMAGES COSTS OR EXPENSES WHETHER SPE...

Page 3: ...ce risk of explosion do not install in machinery space or in area in which ignition protected equipment is required to be used 2 CAUTION a To prevent damage due to excessive vibration shock use on mar...

Page 4: ...g connections and DC cable connections to the required torque values 11 This unit has been provided with integral protections against overloads 12 WARNING To reduce risk of electric shock and fire Ins...

Page 5: ...de machines ou dans la zone o l quipement prot g contre les incendies doit tre utilis 2 ATTENTION Cet appareil est con u pour une installation PAS M t o pont Pour r duire les risques de choc lectriqu...

Page 6: ...de charge AC Circuit de panneau de disjoncteurs ayant Direction Multi fil circuits reli s L es deux sources de tension AC et DC sont termin es l int rieur de cet quipement Chaque circuit doit tre d co...

Page 7: ...e pas provoquer une tincelle Les batteries au lithium ion S assurer que la batterie comprend Battery Management System BMS avec protocole de s curit int gr S assurer que la tension le courant et les p...

Page 8: ...d on NEC Ampacity at Column 3 Column 9 Cable Running Distance between the Unit and the Battery Cable Routing In Free Air Cable Running Distance between the Unit and the Battery Cable Routing In Racewa...

Page 9: ...e 90 In a purely resistive load the current vector is in phase with the voltage vector and hence the Phase Angle 0 In a load consisting of a combination of resistances inductances and capacitances the...

Page 10: ...ly specified in Active Power P in Watts for Resistive type of loads that have Power Factor 1 Reactive types of loads will draw higher value of Apparent Power that is the sum of Active and Reactive Pow...

Page 11: ...actically the loads will be a combination of resistive inductive and capacitive elements and hence its value will be 0 1 Normally it ranges from 0 5 to 0 8 Load Electrical appliance or device to which...

Page 12: ...angle also changes abruptly and it sits at 0V for some time before changing its polarity Thus devices that use control circuitry to sense the phase for voltage speed control or instantaneous zero volt...

Page 13: ...not function Sewing machines with speed microprocessor control Transformer less capacitive input powered devices like i Razors flashlights night lights smoke detectors etc ii Some re chargers for bat...

Page 14: ...ve where rated output power is the Cooking Power 2 Furnace Fan 3 Industrial Motor 3 Portable Kerosene Diesel Fuel Heater 3 Circular Saw Bench Grinder 3 Incandescent Halogen Quartz Lamps 3 Ceramic Posi...

Page 15: ...ed RMS input current and lasts for a few milliseconds An example of the input voltage versus input current waveforms is given in Fig 1 3 2 It will be seen that the initial input current pulse just aft...

Page 16: ...ation Battery Related i INFO For complete information on Lead Acid Batteries and Charging Process please visit www samlexamerica com Support White Papers White Paper Batteries Chargers and Alternators...

Page 17: ...ter and to measure the specific gravity of the electrolyte using a hydrometer When fully charged each individual cell has a voltage of approximately 2 105 V and electrolyte specific gravity of 1 265 A...

Page 18: ...tage at which the electrolyte in the battery begins to break down into Hydrogen and Oxygen gases Under normal circumstances a battery should not be charged at a voltage above its Gassing Voltage excep...

Page 19: ...t Section 1 4 4 1 1 4 3 4 Stage 4 Constant Voltage Equalization Stage This stage is normally initiated manually because it is not required every time the battery is recharged In EVOTM it is carried ou...

Page 20: ...cation can be minimized by the Equalization Stage by raising the charging voltage so that the increased gassing and bubbling agitates stirs the electrolyte and ensures that the electrolyte has uniform...

Page 21: ...Ampere Hour Ah capacity that is lost when the battery is not being charged and there is no load connected to it i e it sits idle in storage Self discharge is caused by electro chemical processes withi...

Page 22: ...n the two units is Capacity C in Ah Reserve Capacity in RC minutes x 0 6 1 4 9 TYPICAL BATTERY SIZES Table 1 4 1 shows details of some popular battery sizes TABLE 1 4 1 POPULAR BATTERY SIZES BCI Group...

Page 23: ...ry Bank at 80 F 26 7 C These curves are used to determine the State of Charge Discharge of the Battery Pack Bank based on its terminal voltage The Y Axis shows the terminal voltage of the battery The...

Page 24: ...pical 12V 24V 48V Flooded Lead Acid Battery 1 4 12 REDUCTION IN USABLE CAPACITY AT HIGHER DISCHARGE RATES TYPICAL IN INVERTER APPLICATION As stated earlier the Ah capacity of automotive battery is nor...

Page 25: ...for a typical 12V 24V battery system at 80 F 26 7 C TABLE 1 4 4 SOC VERSUS STANDING VOLTAGE TYPICAL FLOODED BATTERY Percentage of Full Charge Standing Voltage of Individual Cells Standing Voltage of 1...

Page 26: ...of the curves shows the of State of Charge The of State of Discharge will be 100 State of Charge 1 4 14 1 Low DC Input Voltage Alarm in Inverters As stated earlier at Section 1 4 14 the buzzer alarm i...

Page 27: ...ischarged condition that is harmful for the battery and for the inverter Inverters are normally provided with a protection to shut down the output of the inverter if the DC voltage at the input termin...

Page 28: ...ing the size of the battery system and the load on the inverter Usually this question is turned around to ask How long do you want your load to run and then specific calculation can be done to determi...

Page 29: ...load in Ah Thus as a Rule of Thumb the Ah capacity of the batteries should be twice the energy required by the load in Ah 1 14 18 CHARGING BATTERIES Batteries can be charged by using good quality AC...

Page 30: ...l free contact switching signal from Lithium Ion Battery Management System BMS to stop charging inverting See Sections 3 16 and 5 11 2 7 RJ 45 Jack for Remote Control Model EVO RC PLUS 8 Air inlet ven...

Page 31: ...te 1A removed 1A Cover Plate 2 Input Terminal L1 3 Input Terminal L2 4 Input Terminal N 5 Output Terminal N 6 Output Terminal L2 7 Output Terminal L1 8A Input Ground Terminal 8B Output Ground Terminal...

Page 32: ...te characters 2 ON OFF Key 3 Blue LED Status 4 Red LED Fault 5 Navigation Key Back 6 Navigation Key Up 7 Navigation Key Down 8 Navigation Key Enter 9 SD Card Slot FAT16 32 format up to 32 GB 10 RJ 45...

Page 33: ...rminal Mounting hole 10mm 0 39 suitable for 3 8 or 5 16 battery studs 2 RJ 45 Plug Plug this into the RJ 45 Jack marked Battery Temp Sensor 6 Fig 2 1 3 5 meter 16 5 ft cable 2 6 CONTENTS HARDWARE PACK...

Page 34: ...urit fournies la section 1 sont strictement suivies 3 2 OVERALL DIMENSIONS The overall dimensions and the location of the mounting holes are shown in Fig 3 1 380 415 35 303 5 324 40 7 123 90 50 80 298...

Page 35: ...rs Cooling The unit has openings on the front bottom and back for cooling and ventilation Ensure that these openings are not blocked or restricted Install in cool dry and well ventilated area CAUTION...

Page 36: ...t No 3 Mount vertically on a vertical surface Protect against possibility of small objects or water entering the ventila tion openings on the top If necessary install a suitable sloping guard at least...

Page 37: ...ery Pack 3 The Negative terminal of Battery Pack 3 is connected to the Positive terminal of Battery Pack 2 The Negative terminal of Battery Pack 2 is connected to the Positive terminal of Battery Pack...

Page 38: ...ery Bank 1 in Fig 3 6 or to the Positive battery post of the first battery string Battery Bank 1 of String 1 in Fig 3 7 then the Negative output cable of the inverter charger Cable B should be connect...

Page 39: ...l 2 et la banque de batterie 4 dans la Fig 3 7 Cette connexion assure la suivante Les r sistances des c bles interconnect s seront quilibr es Tous les batteries fils de batterie dans la s rie auront l...

Page 40: ...Negative Input Connector marked BATTERY NEGATIVE Stud and Nut M8 Pitch 1 25 mm Black Protection Cover 2 a is removed 2a Black Protection Cover for Battery Negative Input Connector 3 External Charger I...

Page 41: ...arging current capacity of the external charger does not exceed 100A Battery Temperature Sensor EVO BCTS is connected to the RJ 45 Jack 6 in Figs 3 8 a 3 8 b See Section 2 5 for installation details D...

Page 42: ...the resistance of the conductor The resistance of the conductor is directly proportional to the length of the conductor and inversely proportional to its cross section thickness The resistance in the...

Page 43: ...y arc with accompanying high pressure wave that may cause fire damage nearby objects and cause injury To prevent occurrence of hazardous conditions under short circuit conditions the fuse used in the...

Page 44: ...FOR TABLE 3 1 SIZING OF BATTERY SIDE CABLES AND EXTERNAL BATTERY SIDE FUSES 1 Column 2 indicates the Rated Continuous DC Input Current drawn from the battery in Inverter Mode or 1 25 times the Short...

Page 45: ...put Connectors 70 kgf cm 5 0 lbf ft 35 kgf cm 2 5 lbf ft 7 to 12 kgf cm 0 5 to 0 9 lbf ft 3 5 8 Reducing RF Interference To reduce the effect of radiated interference shield the wires with sheathing c...

Page 46: ...ng the 4 screws holding the plate LEGEND for Fig 3 9 1 Compartment for AC Input Output Connections shown with Cover Plate removed See Fig 2 3 under Section 2 3 2 Input Terminal L1 3 Input Terminal L2...

Page 47: ...la charge du groupe de batteries et du fonctionnement travers les charges des deux pattes L1 et L2 de la tension de sortie 120 240VAC Split Phase 2 NE connectez PAS 120 VCA m me phase aux bornes d ent...

Page 48: ...t travers la interne Neutre ch ssis relais de commutation RY 5 Relais de la figure 4 1 Dans Mode de chargement l interne Neutre ch ssis relais de commutation RY 5 d connecte le neutre de la connexion...

Page 49: ...e est aliment e partir de cette unit et ce panneau est galement n cessaire pour tre aliment partir de suppl ant suppl mentaire source de courant alternatif l alimentation de la source de courant alter...

Page 50: ...ed by a removable front plate Two 27 8 mm 13 32 diameter holes have been provided on the front panel of the unit 10b 10b in Fig 2 1 for cable conduit entry Remove the caps covering the holes and insta...

Page 51: ...ng the GRID MAX CURRENT feature available with the EVO RC PLUS Optional Remote Control EVO RC PLUS is required to change this limit The GRID MAX CURRENT is set at 30A Default Setting For details on GR...

Page 52: ...me Support White Papers Grounded Electrical Power Distribution Grounding System and Lightning Ground Fault Protection Grounding means connecting bonding to Earth Ground or to the other designated Grou...

Page 53: ...ed This recommendation on sizing of the DC Side Grounding Wire will be superseded by the National Local Electrical Codes i INFO As described at Section 3 14 the metal frame chassis of the EVO Fig 3 13...

Page 54: ...rth Ground If such a portable generator is used to feed the AC input of EVO 4248SP ensure the following i The Neutral is bonded to the metal frame either internally or externally ii The metal frame is...

Page 55: ...ral and Chassis Ground Bond Switching Relay RY 5 in Fig 4 1 Switching is carried as follows When operating as an inverter the current carrying conductor of the Inverter Section that is connected to th...

Page 56: ...Battery Temperature Sensor Pinout of this RJ 45 Jack marked Battery Temp Sensor on the front panel of EVOTM 6 in Fig 2 1 is shown at Fig 3 12 1 2 3 4 5 6 7 8 5V Internal Schematic of EVOTM Batt Temp...

Page 57: ...al shore based installation Battery is connected to the DC input connections through DC Electrical Panel with an appropriate fuse to protect the DC input cables against short circuit Battery Charger T...

Page 58: ...G 6 AWG 6 DC ELECTRICAL PANEL External Charge Controller RJ 45 6 4 3 2 1 5 Metal Chassis of EVO 4248SP AC INPUT OUTPUT SECTION Grounding Electrode GE Ground Rod embedded in earth EVO BCTS See LEGEND o...

Page 59: ...Figs 2 1 3 8 4 Negative Input Connector for External Charge Controller 4 Figs 2 1 3 8 5 DC Side Grounding Terminal on EVO 5 Figs 2 1 3 8 6 RJ 45 Jack for Temperature Sensor 6 Fig 2 1 7 AC input output...

Page 60: ...ined it cannot work as inverter and charger at the same time 4 2 COMPONENTS OF THE SYSTEM It consists of 3 Sections Inverter Section Battery Charger Section and AC Input Transfer Relay Section The uni...

Page 61: ...meaning less likelihood of causing problematic voltage drops during starting Power Surge Up to 300 The inverter is able to deliver very high surge power current of up to 300 for 1 ms followed by 200...

Page 62: ...g normally and the battery is connected Relays RY 1 and RY 2 will be in ON condition contact 3 and 4 will close These relays will be ON in Charging Mode 120VAC Single Phase input voltage from i Input...

Page 63: ...ads The Output Neutral to Chassis Ground Bond Switching Relay RY 5 in Fig 4 1 will be ON its NC contacts 3 5 will open and will disconnect the bond between the AC output Neutral 5 Fig 4 1 and the meta...

Page 64: ...F Will close when the relay ON o Contacts 3 5 Normally Closed NC Closed when the relay is OFF Will open when the relay is ON Operation See Section 4 5 2 D and 4 5 2 E Will be ON in Charging Mode Will...

Page 65: ...the backup AC power source is always kept synchronized with the voltage of the primary AC power source Synchronization control logic used in a backup AC source is required to be based on the frequency...

Page 66: ...put is stepped down and rectified to the programmed DC battery charging voltage using Pulse Width Modulation PWM Control That is why it is called a Bi directional device Further the charging voltages...

Page 67: ...r the AC load s to the Inverter Section within 16 ms 4 8 MODES OF OPERATION 4 8 1 Charging Mode As long as the external AC input power is available and is within the programmed limits of voltage and f...

Page 68: ...y 0 5 sec No Load Power Draw from the battery will be 8W The programmable range of this parameter is 4 50Watts Default value is 8W Whenever the Inverter Section is switched ON with Power Saving Mode i...

Page 69: ...n Normal Mode However if it sees a load less than the programmed value of Enter Point for around 5 sec it enters Power Saving Mode Transfer from Inverter to AC Input Source As soon as qualified AC inp...

Page 70: ...remains at this threshold or below for a sustained programmed time period set by programmable parameter GS DETECT TIME See Section 4 4 2 16 of EVO RC PLUS Remote Control Manual the EVO will change ove...

Page 71: ...outside the programmed limits of voltage and frequency For details see Section 4 4 2 13 1 of EVO RC PLUS Remote Control Manual 4 9 TEMPERATURE SENSOR FOR BATTERY CHARGING Battery Temperature Sensor Mo...

Page 72: ...TION 4 11 1 Cooling Fans The unit is cooled by convection and by forced air cooling using 2 variable speed cooling fans Temperature is sensed at the Power Transformer and H Bridge Power Mosfets Heat S...

Page 73: ...r Data Logging using SD Card of up to 32 GB FAT16 FAT32 It also has its own Real Time Clock and Super Capacitor Type of Internal Battery The Remote Control will be required for Firmware upgrade throug...

Page 74: ...d frequency and the following actions are initiated AC input power is fed to the Common Converter Section for conversion to DC voltage to charge the batteries AC input power is simultaneously passed t...

Page 75: ...P VOLTAGE FLOATING VOLTAGE EQUALIZE VOLTAGE the PWM Duty Cycle is reduced that leads to lower short circuit current of the Secondary Winding This will reduce the voltage of the induced pulses and cons...

Page 76: ...se Grid input with Grid input supply circuit breaker capacity of 30A Parameter settings are as follows a GRID MAX CURRENT setting say 10A b BULK CURRENT setting say 10ADC Based on Conversion Factor of...

Page 77: ...REDUCTION OF CHARGING CURRENT IN HIGHER AMBIENT TEMPERATURES In order to protect against over temperature shut down when operating in higher ambient temperatures of around 50C to 60C the BULK CURRENT...

Page 78: ...k at C 20 Discharge Rate Check with the battery manufacturer regarding recommended Bulk Charging Current for your battery bank This value of Bulk Charging Current should be programmed as BULK CURRENT...

Page 79: ...creased when electrolyte temperature falls below the reference temperature of 25 C 77 F i INFO Charging voltages of Lithium Ion Battery are not affected by temperature and hence Battery Temperature Se...

Page 80: ...ery Temperature Sensor Pinout of this RJ 45 Jack marked Battery Temp Sensor on the front panel of EVO 6 in Fig 2 1 is shown at Fig 5 0 also shown at Fig 3 12 1 2 3 4 5 6 7 8 5V Internal Schematic of E...

Page 81: ...sed to feed potential free contact closing signal from the BMS to Stop Charging or Stop Inverting Refer to Section 5 11 2 for details ATTENTION Le syst me de gestion de la batterie BMS qui vient avec...

Page 82: ...eset to Bulk Stage under the following conditions i If the AC input is disconnected and is reconnected ii If battery voltage falls to the programmed value of parameter RESET TO BULK Default value is 4...

Page 83: ...procedure refer to Section 4 4 2 2 of EVO RC PLUS Remote Control Manual Remain in Absorption Stage till the current reduces to value the programmed value of parameter ABSORP EXIT AMPS Default value is...

Page 84: ...AGE VAbsorp 0 3V Io Displayed as X Bulk Stage Displayed as X Absorption Stage Displayed as X Float Stage RESETTO BULK 48V Battery LEGEND for Fig 5 1 Voltage V Curve Current I Curve Io Bulk Stage Curre...

Page 85: ...f T1 is 1 Hr and max value is 12 Hrs The T1 Timer is used to determine the time the charging will take place in the next Absorption Stage Section 5 7 2 5 7 1 2 Automatic Adjustments of Internal AC Cha...

Page 86: ...ch the Duty Cycle of the boosted high frequency PWM voltage pulses Section 5 1 2 is adjusted continuously to keep the battery voltage at level the programmed parameter FLOAT VOLTAGE typically about 54...

Page 87: ...esults in maintaining the peak capacity of the battery i INFO Please read Section 1 4 4 regarding more details on necessity of equalizing batteries This 4 Stage Adaptive Charging Profile can be activa...

Page 88: ...ction 3 6 4 3 and ii codes abbreviations at Table 3 2 under Section 3 6 4 4 of Owner s Manual for Remote Control RVO RC PLUS NOTES for Fig 5 2 1 Voltage V and Current I curves show the battery voltage...

Page 89: ...PLUS Remote Control Manual This time is registered as Bulk Stage Time To As part of Adaptive Algorithm the following times are computed based on the Bulk Stage Time To a Absorption Stage Time T1 To x...

Page 90: ...g takes place at constant voltage at value the programmed value of parameter EQUALIZE VOLTAGE Default value is 57 6V for EVO 4248SP Please see programming range at Table 6 2 and programming procedure...

Page 91: ...Control Manual 4 Stage Adaptive Charging Profile for Equalization is required to be activated manually as follows Initiating 4 Stage Adaptive Charging Profile for Equalization using ON OFF Push Butto...

Page 92: ...ead Acid Battery with load battery backup application like in Telecom battery charging Emergency Lighting etc In this application the voltage setting of the 2nd Absorption Stage is lowered to the leve...

Page 93: ...VO RC PLUS Remote Control Refer to i display screen Nos 1 to 5 at Fig 3 3 c under Section 3 6 4 3 and ii codes abbreviations at Table 3 2 under Section 3 6 4 4 of Owner s Manual for Remote Control RVO...

Page 94: ...Remote Control RVO RC PLUS NOTES for Fig 5 4 1 Please see Srl 1 of Table 5 3 for details of charging process 2 Voltage V and Current I curves show the battery voltage and current 3 The Voltage V and...

Page 95: ...nd restart the selected CHARGING PROFILE from the 1st Stage i e from the Bulk Stage Please see Section 5 7 4 ABSORP EXIT AMPS When charging current in Absorption Stage drops to value set by programmin...

Page 96: ...US Remote Control Manual Reset to Bulk Stage under the following conditions i If the AC input is disconnected and is reconnected ii If battery voltage falls to the programmed value of parameter RESET...

Page 97: ...value is 4A For details of programming range procedure refer to Section 4 4 2 20 of EVO RC PLUS Remote Control Manual Reset to Bulk Stage under the following conditions i If the AC input from the Grid...

Page 98: ...and Source of Mosfet Switch Example of this type of relay is IXYS Part No CPC1002N 60V 700mA rating The following 2 types of signals are normally used by the BMS for on off control of charging and inv...

Page 99: ...in EVO RC PLUS Remote Control will show message Refer to Section 3 6 8 3 of EVO RC PLUS Remote Control Manual EVOTM in Inverting Mode Inverting will stop Internally the EVOTM will enter Standby Mode...

Page 100: ...at Section 3 of this manual ATTENTIONS a Veuillez vous assurer que toutes les instructions de s curit de la Section 1 de ce manuel sont lues et comprises avant d utiliser l appareil b Veuillez vous as...

Page 101: ...ected To power ON the unit without use of Remote Control EVO RC PLUS press and hold the ON OFF Button on the front panel 11 Fig 2 1 for around 3 seconds until completion of sequence shown below Blue L...

Page 102: ...in Fault Mode it will be possible to power off the unit with the help of On Off Button on the front panel of the unit or the On Off Key on the optional Remote Control EVO RC PLUS NOTE For Power On Off...

Page 103: ...us 12V control signal will be made available and the EVOTM will turn ON EVOTM will remain On as long 12V control signal is available through the On condition of the external On Off Switch or the close...

Page 104: ...e switched on or off through programming parameter BUZZER Refer to Section 4 8 2 7 of EVO RC PLUS Manual The default setting is 1 On 6 4 OPTIONAL REMOTE CONTROL EVO RC PLUS FOR PROGRAMMING OF MODES OF...

Page 105: ...pensation 3mV to 5mV C Cell 4mV C Cell BATT OVER VOLT Battery Over Voltage Shutdown 56 00V 70 00V 64 00V RESET VOLTAGE Reset voltage for BATT LOW VOLTAGE condition 48 00V 70 00V 56 00V LOW VOLT ALARM...

Page 106: ...FE CHARGING 0 300 min 0 min EXT CHARGER 0 Affect 1 Not affect 0 Affect NOTES 1 BULK CURRENT value may automatically reduce in higher ambient temperatures of around 50 60 C if Power Transformer tempera...

Page 107: ...OFF VOLT 2 60 0 200 0V 175 0V DETECT TIME 2 0 2000 cycle 60 cycle CUT OFF VOLT 3 60 0 200 0V 165 0V DETECT TIME 3 0 2000 cycle 1 cycle TABLE 6 5 PROGRAMMABLE AND DEFAULT PARAMETERS PARAMETER GROUP NO...

Page 108: ...Control is changed to external Remote Switch it will not be possible to switch ON OFF the EVOTM Inverter Charger from the front panel ON OFF Push Button because it will work with Switch Type Logic It...

Page 109: ...his LED will light up steady when the unit registers any of the FAULT MODE situations shown in Table 7 1 of EVO RC PLUS Remote Control Manual Table 7 1 of EVO RC PLUS Remote Control Manual shows detai...

Page 110: ...button on the front panel of EVOTM unless EVO RC PLUS Remote Control has been connected to the EVOTM unit For the Standby Mode to be switched ON the EVO should be in ON condition and should be operati...

Page 111: ...150 VA 120 VAC L N Power Boost for 1 min 140 5 880 VA 240 VAC L L 2 940 VA 120 VAC L N Power Boost for 10 min 120 5 040 VA 240 VAC L L 2 520 VA 120 VAC L N Power Boost for 30 min 110 4 620 VA 240 VAC...

Page 112: ...AC input of 120 VAC Single Phase 0 30 ADC Programmable Charging Voltages Bulk Absorption Stage Float Stage Equalization Stage 48 0 to 64 0V Default 57 6V 48 0 to 60 0V Default 54 0V 56 0 to 66 0V Def...

Page 113: ...M 33ft RJ 45 Data Cable COMPLIANCE Safety Compliance CSA listed Conforms to CAN CSA STD C22 2 No 107 1 16 and UL Std No 1741 2nd Ed EMI EMC Compliance Certified to FCC Part 15 B Class A ENVIRONMENTAL...

Page 114: ...s been altered removed or modified in any way There is no warranty for defects or damages to equipment or parts caused by Installation alternation inspection or removal Normal wear and tear Abuse or m...

Page 115: ...SAMLEX AMERICA INC 115 NOTES...

Page 116: ...Numbers Ph 1 800 561 5885 Fax 1 888 814 5210 Local Numbers Ph 604 525 3836 Fax 604 525 5221 Website www samlexamerica com USA Shipping Warehouses Kent WA Plymouth MI Canadian Shipping Warehouse Delta...

Reviews: