SAMLEX AMERICA INC. | 107
SECTION 6 |
Operation, Protections and Troubleshooting
TABLE 6.4 PROGRAMMABLE AND DEFAULT PARAMETERS: PARAMETER GROUP NO.3 "INPUT LOW LIMIT"
(For detailed information on parameters in this Table, refer to Section 4.6.2 of the Owner's Manual for Remote Control
EVO-RC-PLUS)
Group
Parameter name
Setting range
Default value
INPUT -
LOW LIMIT
RESET VOLTAGE
60.0 – 200.0V
195.0V
CUT OFF VOLT 1
60.0 – 200.0V
185.0V
DETECT TIME 1
0 – 2000 cycle
300 cycle
CUT OFF VOLT 2
60.0 – 200.0V
175.0V
DETECT TIME 2
0 – 2000 cycle
60 cycle
CUT OFF VOLT 3
60.0 – 200.0V
165.0V
DETECT TIME 3
0 – 2000 cycle
1 cycle
TABLE 6.5 PROGRAMMABLE AND DEFAULT PARAMETERS: PARAMETER GROUP NO.4 "INPUT HIGH LIMIT"
(For detailed information on parameters in this Table, refer to Section 4.7.2 of the Owner's Manual for Remote
Control EVO-RC-PLUS)
Group
Parameter name
Setting range
Default value
INPUT -
HIGH LIMIT
RESET VOLTAGE
120.0 – 350.0V
265.0V
CUT OFF VOLT 1
120.0 – 350.0V
270.0V
DETECT TIME 1
0 – 2000 cycle
60 cycle
CUT OFF VOLT 2
120.0 – 350.0V
275.0V
DETECT TIME 2
0 – 2000 cycle
15 cycle
CUT OFF VOLT 3
120.0 – 350.0V
280.0V
DETECT TIME 3
0 – 2000 cycle
1 cycle