SAMLEX AMERICA INC. | 59
LEGEND FOR FIG 3.13
NOTES:
For sizing of wiring and fuses, refer to the following:
a) DC side wiring: Table 3.1
b) AC side wiring: Table 3.2 for AC input and Table 3.3 for AC output
c) For details regarding 120 VAC Single Phase Input, see Section 3.6.1.2
AC Panel 1.
Main Grid Electrical Panel / Service Entrance Panel : 120 / 240 VAC Split Phase
AC Panel 2.
Sub Panel for distributing AC output from EVO
™
: 120 / 240 VAC with 30A Breaker
Breaker 1.
Breaker for Main Panel / Service Entrance Panel, "Panel-1"
Breaker 2.
30A Breaker for Sub-Panel, "Panel-2"
CB-1
2-Pole Circuit Breaker feeding 120/240 VAC to EVO-4248SP
T-1.
Bi-directional AC input / output transformer
G-B.
Grounded Bus Bar
GE.
Grounding Electrode. Also called "Ground Rod" of the premises
GEC
Grounding Electrode Conductor
SBJ.
System Bonding Jumper for creating N-G bond in the Main Panel/Service Entrance - "AC Panel 1"
RY-1,RY-2,RY-5. Transfer Relays
(Fig 4.1 & Section 4.5.2)
EVO-BCTS.
Battery Charger Temperature Sensor EVO-BCTS
[Fig 2.5(a)]
1.
Battery Positive Input Connector
(1, Figs 2.1 / 3.8)
2.
Battery Negative Input Connector
(2, Figs 2.1 / 3.8)
3.
Positive Input Connector for External Charge Controller
(3, Figs 2.1 / 3.8)
4.
Negative Input Connector for External Charge Controller
(4, Figs 2.1 / 3.8)
5.
DC Side Grounding Terminal on EVO™
(5, Figs 2.1/ 3.8)
6.
RJ-45 Jack for Temperature Sensor
(6, Fig 2.1)
7.
AC input/output Terminals
(i) Refer to AC Input / Output Connections at Fig 3.9
(ii) Refer to Section 3.6.1.2 regarding connection details for 120 VAC Single Phase input
8.
Quick Disconnect to disconnect Neutral to Ground bond (Fig 3.9)
Circuit breaker
Fuse
L1.
Line 1
L2.
Line 2
N Neutral
N-B.
Neutral Bus Bar
WARNING!
In case a Generator is used to feed AC input, please ensure that the Neutral conductor of the Generator is
bonded to the chassis / frame of the Generator and the chassis / frame of the Generator is firmly grounded
to the Earth Ground through Ground Rod. Please refer to Section 3.14.1 for details.
MISE EN GARDE!
En cas d'un générateur est utilisé pour envoyer de l'entrée CA, veuillez vous assurer que le conducteur
neutre de la génératrice est collé sur le châssis / cadre de la génératrice et que le châssis / cadre du
générateur est fermement mis à la terre à la terre via la tige de terre. Veuillez vous reporter à la section
3.14.1 pour plus de détails.
SECTION 3 |
Installation
(i) Voltage between Lines"L1"&"L2" is 240 VAC
(ii) Voltage between Line"L1"& Neutral is 120 VAC
"
Waveform:
(iii) Voltage between Line"L2" and Neutral"N" is
also 120 VAC but its phase is 180o apart
"
Waveform: