background image

6

This is applicable when the two lines are supplied from dif-
ferent mains, i.e.:

 

ˆ

Two different electrical companies.

 

ˆ

An electrical company and genset, ...

Ŗ

All the equipments have an auxiliary terminal strip to install 
an external emergency power off button (EPO), and it will be-
long to the user property.
Type of circuit is selectable through the LCD panel of the 
equipment. The contact is preset from factory as normally 
open, so the button must be switched to close the circuit and 
the voltage to the loads is broken. To establish the power 
supply to the loads again, the EPO button must be deacti-
vated.
EPO doesn't affect to the power supply of the equipment, it 
only breaks the power supply to the loads as a safety measure.

Ŗ

When supplying input voltage to a UPS with fitted in or 
separate static bypass, although the inverter is still 

turned «Off» (deactivated) it doesn't mean that at the output 
there will not be voltage.
So, to do it, the input and static bypass switches will have to 
be turned «Off».
Put warnings of danger and/or emergency switches if the safety 
Standards require it in your particular installation.

Ŗ

It is possible that the UPS supplies output voltage 
through the manual bypass to those equipments that 

incorporate it either standard or optional, so it will have to be 
considered as regards to safety. If it were necessary to break 
the output supply of the equipment in this situation, deactivate 
the outgoing distribution protection or in case of lack of it the 
general protection of the distribution panel that feeds the UPS. 

Ŗ

All power supply electrical cables have to be fixed to the 
equipments and loads, interfaces, etc..., to unmovable parts 
and in the way to avoid treads, trips on them or fortuitous 
pulls.

Ŗ

Phase equipments in the foreseen terminal for that purpose.

Ŗ

CHASSIS or RACK mounted equipments are destined to be in-
stalled in a predetermined set to be done by professionals.

 

ˆ

The installation has to be designed and executed by qual-
ified personnel, who will be the responsible to apply the 
safety and EMC regulations and standards that controls 
the particular installations where the product is destined.

 

ˆ

The equipments assembled in CHASSIS do not have 
enclosure protection, even the power blocks are unpro-
tected.

 

ˆ

Some RACK mounted equipments do not have the power 
blocks protected.

Ŗ

Never manipulate the equipment with wet hands.

1.2.3.2.  To keep in mind.

Ŗ

Do not try to dismantle or change any part of the 
equipment, if this action is not contemplated in this 

document. Manipulation inside the UPS due to any modifica-
tion, reparation or any other cause, can make an electrical 
discharge of high voltage and it is restricted to 

qualified

 staff 

only. Do not open the equipment.
A part from the implicit stated risks, any action that make the 
modification, internal or external of the equipment or just only 
the simple intervention inside of itself, which is not stated in 
this document, 

it can expire the warranty

Ŗ

If it is observed that the UPS exhausts smoke or toxic gas, 
shutdown it immediately and disconnect it from the power 
supply. This kind of fault can cause fire or electrical dis-
charge. Contact with our 

(

S.T.S.

)

.

Ŗ

In case of an accidental equipment dropping or if the enclo-
sure is damaged, do not start it up under any concept. This 
kind of fault can cause fire or electrical discharge. Contact 
with our 

(

S.T.S.

)

.

Ŗ

Do not cut, manipulate the electrical cables, do not put heavy 
objects over them too. Any of these actions could cause a 
short-circuit and make a fire or electrical discharge.
Check that the electrical cables of connection, plugs and out-
lets are in good conditions.

Ŗ

When moving an equipment from a cold place to a warm 
environment and vice versa, it can cause condensa-
tion (small water drops) in the external and internal sur-
faces. Before installing a moved equipment from another 
place or even packaged, the equipment will be left for a 
minimum time of two hours in the new location before 
making any action, with the purpose of adapting it to the 
new environmental conditions and avoid the possible 
condensations.
The UPS has to be completely dry before starting any instal-
lation task.

Ŗ

Do not store, install or expose the equipment in corrosive, 
wets, dusty inflammable or explosive environments and 
never outdoors.

Ŗ

Avoid to locate, install or store the equipment in a place 
with direct sunlight or high temperatures. Batteries could 
be damaged.
In the exceptional case and long exposition to intense 
heat, batteries can cause filtrations, overheating or explo-
sions, which can cause fires, burn or other injuries. High 
temperatures can also make deformation in the plastic 
enclosure.

Ŗ

The location will be spacious, airy, away from heat sources 
and easy access.

Ŗ

Do not obstruct the cooling grids by entering objects through 
themselves or other orifices.

Ŗ

 In equipments of low power rate (up to 3kVA), leave as min-
imum space of 25 cm in the equipment peripheral and 50 cm 
for higher power rates equipments.

Ŗ

 Also in the UPS with power blocks, it is recommended to 
leave another additional 50 cm for an eventual intervention 
of the (

S.T.S.

), considering that if it means to move the UPS, 

the connected cables will have the needed clearance.

Ŗ

Do not put materials over the equipment or parts that obstruct 
the correct visualization of the synoptic.

Ŗ

Be careful to not wet it, because it is not waterproof. Do not 
allow entering any kind of liquids in. If accidentally the outside 
of the machine comes into contact with liquids or salt air, dry 
it with a soft and absorbent cloth. 

Ŗ

To clean the equipment, wipe over a damp cloth and then 
dry it. Avoid sprinkling or spillage that could enter through the 
slots or cooling grids, which may cause fire or electric shock.
Do not clean the equipments with products that could have 
alcohol, benzene, solvent or other inflammable substances, 
or they are abrasive, corrosive, liquids or detergent.

Ŗ

When it is needed to remove the protection cover to access 
to the terminals, they will have to be put back before starting 
up the equipment. Otherwise you may incur personal injury 
or equipment damage.

Ŗ

Be careful to not lift heavy loads without help, according to 
the following recommendations:

 

ˆ

d

, < 18 kg.

 

ˆ

dd

, 18 - 32 kg.

USER MANUAL

Summary of Contents for SLC TWIN RT series

Page 1: ...LIGHTING FLOW DIMMER STABILIZERS ILUEST SWITCH MODE POWER SUPPLY STATIC INVERTERS PHOTOVOLTAIC INVERTERS VOLTAGE STABILIZERS AND POWER LINE CONDITIONERS UPS SLC TWIN RT series 0 7 to 10 kVA UNINTERRUP...

Page 2: ......

Page 3: ...3 8 Dry_out terminals dry contact for alarm 0 7 to 3 kVA equipments only 4 3 9 Connection in parallel 4 3 9 1 Introduction to the redundancy 4 3 9 2 Installation and parallel operating 4 to 10 kVA eq...

Page 4: ...respect such instructions can damage the goods Precaution symbol Read the paragraph text and take the stated preventive mediums it contents the basic instructions and features for the equipment safety...

Page 5: ...circuit that supplies the equipment Cross cable section and its features will be same as the power supply cables but with green colour with or without the yellow strip All outlets of the UPS has an ea...

Page 6: ...shutdown it immediately and disconnect it from the power supply This kind of fault can cause fire or electrical dis charge Contact with our S T S In case of an accidental equipment dropping or if the...

Page 7: ...rds to quantity capacity and voltage are stated in this battery label sticked beside the nameplate of the equipment Respect these data battery connection polarity and the supplied circuit diagram stri...

Page 8: ...ive EMC In accordance with the specifications of the harmonized stand ards Standards as reference EN IEC 62040 1 Uninterruptible power supply UPS Part 1 1 General and safety requirements for UPS s use...

Page 9: ...RT models from 4 to 10 kVA Battery module for TWIN RT from 0 7 to 3 kVA Battery module for TWIN RT from 4 to 10 kVA Fixing screws Front plastic trim Fixing screws Front plastic trim Fixing screws Fro...

Page 10: ...r Fan IEC AC outlets LS1 Models of 2 kVA B1 USB COM port RS232 COM port IEC inlet for AC power supply Main earth for battery module Connector for remote ON OFF Auxiliary contact connector Connector fo...

Page 11: ...odule Battery module for equipments from 0 7 to 3 kVA Earth bonding temrinal to be connected to the equipment and with other module Battery module for equipments from4 to 6 kVA The connection of the b...

Page 12: ...the UPS case or cabinet Under request it is possible to supply the acces sories screws and electrical cables needed to install and connect the external batteries B1 Equipment with extra battery charg...

Page 13: ...ssible to increase the standard back up time of the equip ment by connecting additional battery modules In order to optimise the recharging time of the batteries there are equipments that in corporate...

Page 14: ...ce between this option and the manual bypass in tegrated in the own UPS enclosure in models of higher power rate than 3 kVA consists in a better manoeuvring because it allows a complete disconnection...

Page 15: ...ze they will be as minimum to the currents stated in the nameplate of each UPS In the nameplate of the equipment there are only printed the nominal currents as it is stated in the safety standard EN I...

Page 16: ...where the ambient temperature exceeds above 50 C or below 15 C otherwise it may de grade the electrical characteristics of the batteries 4 2 3 Unpacking The packaging of the equipment consists of a c...

Page 17: ...or battery pack Handle for battery pack rack Fig 4 Battery pack s removing 4 2 5 Vertical tower type or rack models All the UPSs from SLC TWIN RT series are designed to as semble the equipment as towe...

Page 18: ...he beautiful front cover proceed as follows see figure 6 Take out the control panel A see section 4 2 5 1 and remove the fixing screw B of the beautiful front door lo cated below the first one and put...

Page 19: ...supports or stabilizers C to hold the equipment and battery module For equipments up to 3 kVA Put the UPS and battery module on vertical position be tween the stabilizers supports C Fix the D metalli...

Page 20: ...of each front cover there are the K trims as hole to go the cables through it with the battery modules Break the needed trims to pass the connection bus Put the beautiful front cover back of the equi...

Page 21: ...lied screws Put a UPS in a rack cabinet it is needed to have the side internal as support mode C In lack of them and under request a universal rails can be supplied as a guide to be installed by the e...

Page 22: ...is recommended to use terminals in all the cable ends which are connected to the power blocks specially in the power ones input output and bypass Check the correct torque in the screws of the power b...

Page 23: ...r and fuse for general purpose of 250V AC 3A type F 3 Two poles contactor of 230V AC with a minimum distance between contact of 1 4 mm and coil of the same voltage with the minimum current stated in t...

Page 24: ...the load connected to the respective outlet has to be checked otherwise the protection will be acti vated and deactivated cyclically and therefore the loads will suffer the consequences For hardwired...

Page 25: ...dule 4 3 5 Connection of main input earth terminal and the earth bonding terminal As this is a device with class I protection against elec tric shocks it is essential to install a protective earth con...

Page 26: ...arate from other lines that have dangerous voltages energy distribution line Parallel connection bus Use the bundle with 25 signal cables with mesh and DB25 connectors in the ends to joint up to 2 equ...

Page 27: ...Output 3 RXD Input 5 GND Input Tabla 5 Pin out of the RS232 in the DB9 connector USB communication port is compatible with the USB 1 1 pro tocol for communication software 4 3 10 2 Smart slot UPSs hav...

Page 28: ...management This software supplies an auto Shutdown for a system based on several PCs in case of an electrical blackout With this soft ware the end users can monitor and manage any UPS in the same IT...

Page 29: ...e ones are required to be connected like laser printers or CRT monitors keep in mind the start inrush currents of these peripherals in order to avoid that the equipment becomes blocked under the worst...

Page 30: ...re than 3 seconds to shutdown the inverter The acoustic alarm will beep for 3 sec The equipment will be established on Bypass mode When finishing the previous action there is still voltage at the UPS...

Page 31: ...ker switch of the distribution panel corresponding to the new integrated equipment The complete parallel system will supply output voltage through the bypass Remove the cover of the manual bypass in e...

Page 32: ...wrong manoeuvring the mechanical lock has to be fit otherwise the equipment and loads are exposed to serious damages even the de struction of both or fire Move the manual bypass switch to position UP...

Page 33: ...lowing parts Four buttons or membrane keys see table 7 A LCD panel with two colours backlight By default the text or graphics messages are shown in white colour over blue background When a critical al...

Page 34: ...in the LCD and there has not been any manipulation over the buttons it will return back to main screen automatically The main screen shows the following information by default Summary of the status in...

Page 35: ...ads so the ECO mode operating has to be consid ered according to this issue Fig 26 ECO mode screen Frequency converter mode Fig 27 Frequency converter mode screen In the frequency converter mode the s...

Page 36: ...about the current conditions of the equipment details of measures event data logger the own identification of the UPS and change the set tings to be adapted to the own needs and optimise the func tion...

Page 37: ...een by default Alarm screen Parallel system screen Screen Press 1 sec Press o 1 sec Structure of the menu UPS status Main menu structure Press 1 sec Fig 34 UPS status screens 6 3 2 UPS status submenu...

Page 38: ...ey The system is cyclic so you can move in both directions The maximum quantity of registers of the data logger is 50 so a new input will delete the oldest register When pressing the key for more than...

Page 39: ...ble by password by the S T S Control submenu for 0 7 to 3 kVA models Press 1 sec Press o 1 sec Control submenu structure Main menu structure Press 1 sec Press 1 sec Press 1 sec Accesible with password...

Page 40: ...ted or deactivated from this menu Any new alarm will activate the own acoustic alarm Battery test It is a control command of the UPS to make a battery test of the equipment It is also possible to do i...

Page 41: ...ms approximately Therefore this function is not suitable for some sensitive loads or areas with unstable power supply 6 4 1 2 To establish the ECO mode function The function can be activated or deacti...

Page 42: ...heating and sparks with fire risk because the size is not enough Do not short the and poles of the batteries there is risk of fire or electrocution Be sure that there is no voltage before touching the...

Page 43: ...ipment is too high Check the UPS cooling and ambient temperature of the room 93 Back Feed s lo en modelos 3 kVA On battery mode bypass has voltage Transfer to manual bypass and consult with the S S T...

Page 44: ...ooting guide Warning indications 7 2 3 Troubleshooting guide Other circumstances Circumstance or condition Possible cause Solution Code Description in the LCD panel 01 Bypass Abnormal Bypass power sup...

Page 45: ...several tests and sets in the systems Measurement and write down input currents and voltages among the phases Measurement and write down output currents and voltages among the phases Measurement and...

Page 46: ...62040 3 non linear load Transient recover time of the output voltage with load step 0 100 0 9 Transient recover time of output voltage with load step 20 100 20 6 Frequency With mains present synchroni...

Page 47: ...s connectors 6 IEC 10A 3 x LS1 3 x LS2 1 IEC 16 A 3 kVA UPS only 4 IEC 10A 2 IEC 16 A 8 IEC 16 A Output terminals 3 Phase neutral and PE Communication ports 2 RS232 DB9 and USB mutually exclusive Moni...

Page 48: ...ms toward others kVA The voltampere is the unit of the apparent power in electrical current In direct current is almost equal to the real power but in alternating current can defer depending on the po...

Page 49: ...49 SALICRU...

Page 50: ...50 USER MANUAL...

Page 51: ...51 SALICRU...

Page 52: ...NCIA VALLADOLID ZARAGOZA BRANCHES AND SERVICES AND TECHNICAL SUPPORT S T S CHINA FRANCIA HUNGR A MARRUECOS M XICO PORTUGAL REINO UNIDO SINGAPUR SUBSIDIARIES ALEMANIA ARABIA SAUD ARGELIA ARGENTINA B LG...

Reviews: