background image

7

SALICRU

 

ˆ

ddd

, 32 - 55 kg.

 

ˆ

, > 55 kg.

Ŗ

UPSs are electronic equipments, so they will be treated as 
they are:

 

ˆ

Avoid shocks.

 

ˆ

Avoid jolting or bouncing of the UPS, like those produced 
by moving the equipment on a hand truck and move on 
an uneven or wavy surface.

Ŗ

UPS transport will be done packaged inside its original pack-
aging in order to prevent it from shock and impact and by 
means of the suitable type of packaging (carton box, pallet 
packaging, ...) and appropriate to its weight.

Ŗ

Although the physical location of the elements can differ from 
the illustrations in this manual in some cases, the correct la-
belling correct the possible doubts and makes easy its com-
prehension.

1.2.3.3.  Safety warning regarding batteries.

Ŗ

The manipulation and connection of the batteries 
shall be done and supervised by 

personnel with 

battery knowledge only

.

Before doing any action, disconnect the batteries. Check that 
no current is present and there is not dangerous voltage in 
the DC BUS (capacitors) or in the endpoint of the battery set 
terminals.
Battery circuit is not isolated from input voltage. Dangerous 
voltages can be found between the terminals of the battery 
set and the earth. Check that there is not any voltage at the 
input before take any action over them.

Ŗ

When faulty batteries are replaced, the complete battery set 
has to be replaced, less exceptional cases in new equip-
ments,  were  due  to  manufacturing  faults  it  will  only  be  re-
placed the defective ones.
The replacement will be done by another one of the same 
type, voltage, capacity, quantity and brand. All of them has to 
be of the same brand.

Ŗ

Generally, the used batteries are sealed lead acid of 12V and 
maintenance free (VRLA).

Ŗ

Do not reuse the faulty batteries. There could be an explo-
sion or burst any battery with the involved problems and is-
sues that could happen.

Ŗ

Generally supplied batteries are installed in the same cab-
inet, case or rack of the equipment. Depending on the power, 
autonomy or both, they can be supplied separately from the 
equipment in another cabinet, case or rack, with the interlink 
cables among them. Do not modify its length.

Ŗ

In those equipments requested without batteries, their ac-
quisition, installation and connection of themselves will be 
done by the end-user and 

under his responsibility

. Data 

concerning the batteries as regards to quantity, capacity and 
voltage, are stated in this battery label sticked beside the 
nameplate of the equipment. 

Respect these data

, battery 

connection polarity and the supplied circuit diagram 

strictly

.

For an optimum and efficient operating, the battery set has to 
be located as close as possible to the equipment.

Ŗ

The battery voltage can involve the risk of electric 
shock and can produce high short circuit currents. 

Observe the following preventive measures before manipu-
lating any terminal block identified in the labelling as «Bat-
teries»:

 

ˆ

Disconnect the corresponding protection elements.

 

ˆ

When connecting a battery cabinet to the equipment, 

respect the cable’s polarity and colour (red-positive; 
black-negative) indicated in the manual and in the cor-
responding labelling.

 

ˆ

Wear rubber gloves and shoes.

 

ˆ

Use tools with insulated handles.

 

ˆ

Take off watches, rings or other metal objects.

 

ˆ

Do not place metal tools or objects over the batteries.

 

ˆ

Never manipulate with your hands or through conducting 
objects, do not short either the battery terminal block of 
the equipment or the own from the batteries.

Ŗ

In order to avoid a complete discharge of the batteries and 
as a safety measure after a long blackout of the commercial 
mains and when ending the working day, proceed to the load 
shutdown and then to the equipment too, by following the op-
erating described in this «User's manual».

Ŗ

When the equipment and/or battery module has a protec-
tion through a fuse and it were needed to be replaced, it will 
always be done by another one with the same dimension, 
type and size.

Ŗ

For long periods of disconnection, consider that the equip-
ment  has  to  be  connected  once  a  month  for  10  hours  as 
minimum, in order to charge the batteries, so the irreversible 
degradation of itself is avoided. On the other hand, in case of 
storing an equipment, it will be done in a fresh and dry place, 

never outdoors

.

Ŗ

Never short the battery terminals as it involves a high risk. It 
involves the detriment of the equipment and batteries.

Ŗ

Avoid mechanical efforts and impacts.

Ŗ

Do not open or mutilate the battery. Spilled electrolyte is 
harmful and toxic to the skin and eyes.

Ŗ

Do not dispose the batteries in a fire and high temperatures. 
The batteries may explode.

Ŗ

In case of contact of the acid with parts of the body, wash 
immediately with plenty water and call urgently the nearest 
medical service.

Ŗ

Batteries involve a serious risk for the health and for the en-
vironment. Their disposal should be done according to the 
existing laws.

Summary of Contents for SLC TWIN RT series

Page 1: ...LIGHTING FLOW DIMMER STABILIZERS ILUEST SWITCH MODE POWER SUPPLY STATIC INVERTERS PHOTOVOLTAIC INVERTERS VOLTAGE STABILIZERS AND POWER LINE CONDITIONERS UPS SLC TWIN RT series 0 7 to 10 kVA UNINTERRUP...

Page 2: ......

Page 3: ...3 8 Dry_out terminals dry contact for alarm 0 7 to 3 kVA equipments only 4 3 9 Connection in parallel 4 3 9 1 Introduction to the redundancy 4 3 9 2 Installation and parallel operating 4 to 10 kVA eq...

Page 4: ...respect such instructions can damage the goods Precaution symbol Read the paragraph text and take the stated preventive mediums it contents the basic instructions and features for the equipment safety...

Page 5: ...circuit that supplies the equipment Cross cable section and its features will be same as the power supply cables but with green colour with or without the yellow strip All outlets of the UPS has an ea...

Page 6: ...shutdown it immediately and disconnect it from the power supply This kind of fault can cause fire or electrical dis charge Contact with our S T S In case of an accidental equipment dropping or if the...

Page 7: ...rds to quantity capacity and voltage are stated in this battery label sticked beside the nameplate of the equipment Respect these data battery connection polarity and the supplied circuit diagram stri...

Page 8: ...ive EMC In accordance with the specifications of the harmonized stand ards Standards as reference EN IEC 62040 1 Uninterruptible power supply UPS Part 1 1 General and safety requirements for UPS s use...

Page 9: ...RT models from 4 to 10 kVA Battery module for TWIN RT from 0 7 to 3 kVA Battery module for TWIN RT from 4 to 10 kVA Fixing screws Front plastic trim Fixing screws Front plastic trim Fixing screws Fro...

Page 10: ...r Fan IEC AC outlets LS1 Models of 2 kVA B1 USB COM port RS232 COM port IEC inlet for AC power supply Main earth for battery module Connector for remote ON OFF Auxiliary contact connector Connector fo...

Page 11: ...odule Battery module for equipments from 0 7 to 3 kVA Earth bonding temrinal to be connected to the equipment and with other module Battery module for equipments from4 to 6 kVA The connection of the b...

Page 12: ...the UPS case or cabinet Under request it is possible to supply the acces sories screws and electrical cables needed to install and connect the external batteries B1 Equipment with extra battery charg...

Page 13: ...ssible to increase the standard back up time of the equip ment by connecting additional battery modules In order to optimise the recharging time of the batteries there are equipments that in corporate...

Page 14: ...ce between this option and the manual bypass in tegrated in the own UPS enclosure in models of higher power rate than 3 kVA consists in a better manoeuvring because it allows a complete disconnection...

Page 15: ...ze they will be as minimum to the currents stated in the nameplate of each UPS In the nameplate of the equipment there are only printed the nominal currents as it is stated in the safety standard EN I...

Page 16: ...where the ambient temperature exceeds above 50 C or below 15 C otherwise it may de grade the electrical characteristics of the batteries 4 2 3 Unpacking The packaging of the equipment consists of a c...

Page 17: ...or battery pack Handle for battery pack rack Fig 4 Battery pack s removing 4 2 5 Vertical tower type or rack models All the UPSs from SLC TWIN RT series are designed to as semble the equipment as towe...

Page 18: ...he beautiful front cover proceed as follows see figure 6 Take out the control panel A see section 4 2 5 1 and remove the fixing screw B of the beautiful front door lo cated below the first one and put...

Page 19: ...supports or stabilizers C to hold the equipment and battery module For equipments up to 3 kVA Put the UPS and battery module on vertical position be tween the stabilizers supports C Fix the D metalli...

Page 20: ...of each front cover there are the K trims as hole to go the cables through it with the battery modules Break the needed trims to pass the connection bus Put the beautiful front cover back of the equi...

Page 21: ...lied screws Put a UPS in a rack cabinet it is needed to have the side internal as support mode C In lack of them and under request a universal rails can be supplied as a guide to be installed by the e...

Page 22: ...is recommended to use terminals in all the cable ends which are connected to the power blocks specially in the power ones input output and bypass Check the correct torque in the screws of the power b...

Page 23: ...r and fuse for general purpose of 250V AC 3A type F 3 Two poles contactor of 230V AC with a minimum distance between contact of 1 4 mm and coil of the same voltage with the minimum current stated in t...

Page 24: ...the load connected to the respective outlet has to be checked otherwise the protection will be acti vated and deactivated cyclically and therefore the loads will suffer the consequences For hardwired...

Page 25: ...dule 4 3 5 Connection of main input earth terminal and the earth bonding terminal As this is a device with class I protection against elec tric shocks it is essential to install a protective earth con...

Page 26: ...arate from other lines that have dangerous voltages energy distribution line Parallel connection bus Use the bundle with 25 signal cables with mesh and DB25 connectors in the ends to joint up to 2 equ...

Page 27: ...Output 3 RXD Input 5 GND Input Tabla 5 Pin out of the RS232 in the DB9 connector USB communication port is compatible with the USB 1 1 pro tocol for communication software 4 3 10 2 Smart slot UPSs hav...

Page 28: ...management This software supplies an auto Shutdown for a system based on several PCs in case of an electrical blackout With this soft ware the end users can monitor and manage any UPS in the same IT...

Page 29: ...e ones are required to be connected like laser printers or CRT monitors keep in mind the start inrush currents of these peripherals in order to avoid that the equipment becomes blocked under the worst...

Page 30: ...re than 3 seconds to shutdown the inverter The acoustic alarm will beep for 3 sec The equipment will be established on Bypass mode When finishing the previous action there is still voltage at the UPS...

Page 31: ...ker switch of the distribution panel corresponding to the new integrated equipment The complete parallel system will supply output voltage through the bypass Remove the cover of the manual bypass in e...

Page 32: ...wrong manoeuvring the mechanical lock has to be fit otherwise the equipment and loads are exposed to serious damages even the de struction of both or fire Move the manual bypass switch to position UP...

Page 33: ...lowing parts Four buttons or membrane keys see table 7 A LCD panel with two colours backlight By default the text or graphics messages are shown in white colour over blue background When a critical al...

Page 34: ...in the LCD and there has not been any manipulation over the buttons it will return back to main screen automatically The main screen shows the following information by default Summary of the status in...

Page 35: ...ads so the ECO mode operating has to be consid ered according to this issue Fig 26 ECO mode screen Frequency converter mode Fig 27 Frequency converter mode screen In the frequency converter mode the s...

Page 36: ...about the current conditions of the equipment details of measures event data logger the own identification of the UPS and change the set tings to be adapted to the own needs and optimise the func tion...

Page 37: ...een by default Alarm screen Parallel system screen Screen Press 1 sec Press o 1 sec Structure of the menu UPS status Main menu structure Press 1 sec Fig 34 UPS status screens 6 3 2 UPS status submenu...

Page 38: ...ey The system is cyclic so you can move in both directions The maximum quantity of registers of the data logger is 50 so a new input will delete the oldest register When pressing the key for more than...

Page 39: ...ble by password by the S T S Control submenu for 0 7 to 3 kVA models Press 1 sec Press o 1 sec Control submenu structure Main menu structure Press 1 sec Press 1 sec Press 1 sec Accesible with password...

Page 40: ...ted or deactivated from this menu Any new alarm will activate the own acoustic alarm Battery test It is a control command of the UPS to make a battery test of the equipment It is also possible to do i...

Page 41: ...ms approximately Therefore this function is not suitable for some sensitive loads or areas with unstable power supply 6 4 1 2 To establish the ECO mode function The function can be activated or deacti...

Page 42: ...heating and sparks with fire risk because the size is not enough Do not short the and poles of the batteries there is risk of fire or electrocution Be sure that there is no voltage before touching the...

Page 43: ...ipment is too high Check the UPS cooling and ambient temperature of the room 93 Back Feed s lo en modelos 3 kVA On battery mode bypass has voltage Transfer to manual bypass and consult with the S S T...

Page 44: ...ooting guide Warning indications 7 2 3 Troubleshooting guide Other circumstances Circumstance or condition Possible cause Solution Code Description in the LCD panel 01 Bypass Abnormal Bypass power sup...

Page 45: ...several tests and sets in the systems Measurement and write down input currents and voltages among the phases Measurement and write down output currents and voltages among the phases Measurement and...

Page 46: ...62040 3 non linear load Transient recover time of the output voltage with load step 0 100 0 9 Transient recover time of output voltage with load step 20 100 20 6 Frequency With mains present synchroni...

Page 47: ...s connectors 6 IEC 10A 3 x LS1 3 x LS2 1 IEC 16 A 3 kVA UPS only 4 IEC 10A 2 IEC 16 A 8 IEC 16 A Output terminals 3 Phase neutral and PE Communication ports 2 RS232 DB9 and USB mutually exclusive Moni...

Page 48: ...ms toward others kVA The voltampere is the unit of the apparent power in electrical current In direct current is almost equal to the real power but in alternating current can defer depending on the po...

Page 49: ...49 SALICRU...

Page 50: ...50 USER MANUAL...

Page 51: ...51 SALICRU...

Page 52: ...NCIA VALLADOLID ZARAGOZA BRANCHES AND SERVICES AND TECHNICAL SUPPORT S T S CHINA FRANCIA HUNGR A MARRUECOS M XICO PORTUGAL REINO UNIDO SINGAPUR SUBSIDIARIES ALEMANIA ARABIA SAUD ARGELIA ARGENTINA B LG...

Reviews: