34
Code
Condition
Description
Color LCD
65
State
In converter mode.
Blue
71
Warning
EPO active.
Blue
72
Warning
On maintain Bypass (only models
of 4.. 10 kVA).
Blue
81
Fault
Heatsink over temperature.
Red
82
Warning
Ambient over temperature.
Blue
83
Warning
Ambient NTC abnormal (only models
of 0.7.. 3 kVA).
Blue
84
Warning
Fan failure.
Blue
86
Warning
Heatsink over temperature pre-alarm
(only models of 0.7.. 3 kVA).
Blue
87
Warning
Heatsink NTC abnormal (only models
of 0.7.. 3 kVA).
Blue
94
Warning
Byp relay sticked (only models
of 4.. 10 kVA).
Blue
A3
Warning
Fatal EEPROM fault (only models
of 4.. 10 kVA).
Blue
Tabla 9.
UPS status and color LCD display, as condition.
6.1.3. Main
screen.
Ŗ
UPS control panel provides useful information about the
status of the load, events, measures, identification and setting
through the screen of the front panel.
Ŗ
Immediately after the start up, the LCD panel shows the
SALICRU logo for few seconds and next the main screen
by default is displayed, where the status of the equipment is
represented (figure 21).
Ŗ
When the same menu is displayed for 15 minutes in the LCD,
and there has not been any manipulation over the buttons, it will
return back to main screen automatically.
Ŗ
The main screen shows the following information by default
Summary of the status, including the operating mode and
load.
Status of the alarm, if there is any one active.
The alarm includes the fault and warning informa-
tions.
Battery and status of the charge, including the battery
voltage, charge level and charger status.
Continuous information includes the UPS in parallel and
running time.
UPS output
information
Information of
connected UPS
load leve
l
Equipment
operating mode
Information of the
batteries
UPS power supply
information
Fig. 21.
Main screen of the equipment.
Ŗ
All the screens shown in the figures of this chapter corre-
spond to a 1kVA equipment, as an example. For more details
of LCD screen shoots from control panel, see the next sec-
tion 6.2.
6.2. Operating modes of the
equipment.
Ŗ
The different graphical symbols displayed in the LCD of the
control panel, correspond to the following operating modes
or status:
Normal mode:
The UPS is running on normal mode with power supply
present.
Fig. 22.
Normal mode screen.
Battery mode:
When the UPS is running on battery mode, the alarm
beeps every 4 seconds.
Fig. 23.
Battery mode screen.
USER MANUAL