23
SALICRU
5. Operating.
5.1. Start up.
5.1.1. Controls before commissioning.
•
Make sure that all the connections have been made prop-
erly, respecting the labelling of the equipment and the in-
structions of chapter 4.
•
Check that the UPS is turned Off (shutdown).
•
Be sure that all the loads are turned «Off».
Turn off the connected loads before starting up the
UPS , and start up the loads one by one, when the
UPS is started up only. Before shutdown the UPS, check all
the loads are out of service (Off).
•
It is very important to proceed in the established order.
•
For UPS view, see figures 1 to 3.
5.2. UPS start up and shutdown.
5.2.1. Initial UPS start up.
•
Check that the power supply connection is correct.
•
Connect the power cord from UPS input to mains power
supply. The LCD panel lights and shows the UPS status,
"STBY" (Wait mode).
•
Press over the start up key for more than 3 seconds. The
UPS will shift to "NORM" mode (Line mode).
•
Check that there are not any alarm or warning activated in the
UPS screen and in case of them fix them before proceeding
(consult the troubleshooting guide).
•
In case of having battery modules connected to the equip-
ment, it is needed to set the complete system (UPS - quantity
of battery modules), see section 6.1.6.4.
•
To change or modify other factory preset values, consult sec-
tion 6 of this document.
•
In the initial start up, the UPS auto-senses the input fre-
quency and established it as the standard one.
In extreme cases can happen, although is almost not pos-
sible, that the mains frequency is very high or low from the
nominal and takes as a default value the wrong one. Check
the frequency in the control panel and repeat the procedure if
this circumstance would occur.
5.2.2. UPS start up, with mains present.
•
For the daily start up of the equipment, press over the start up
key for more than 3 seconds, the acoustic alarm will beep
for 1 sec. and the UPS will start up.
•
Fan will be started up and the LCD from control panel will
show the status of the equipment.
•
After several seconds, the UPS is established on "NORM"
(Line mode). If the mains voltage is wrong, the UPS will shift
to battery mode "BATT", with no break in the power supply to
the outlets.
•
Start up the load/s, without overloading the equipment.
5.2.3. Start up of the UPS, with no mains
present.
•
Press over the start up key for more than 3 seconds, the
acoustic alarm will beep for 1 sec. and the UPS will start up.
Fan will be started up and the LCD from control panel will
show the status of the equipment.
•
After several seconds, the UPS is established on battery
mode "BATT". If mains is restored, the UPS will shift to line
mode "NORM", with no break in the power supply to the out-
lets.
•
Start up the load/s, without overloading the equipment.
5.2.4. UPS shutdown, with mains
present.
•
Shutdown the load/s.
•
Press over the start up key for more than 3 seconds to
shutdown the inverter. Several seconds after, the LCD panel
is shutdown and the complete equipment will be out of ser-
vice.
•
Outlets will be with no voltage.
5.2.5. UPS shutdown, with no mains
present.
•
Shutdown the load/s.
•
Press over the start up key for more than 3 seconds to
shutdown the UPS. Several seconds after, the LCD panel is
shutdown and the complete equipment will be out of service.
•
Outlets will be with no voltage.