No
Yes
No
Yes
No
Yes
Saijo denki International co.,ltd.
71
Check the control board
Error 13
Outdoor unit Ambient Temperature
sensor fail
There is an error in the temper sensor at air inlet
of outdoor unit
Is sensor connect on
control board ?
Correct connector connection
Is the wire of the sensor
normal ?
Change the sensor
Is sensor resistance
normal ?
Change the sensor
Check code
Check code name
cause
Summary of Contents for CVIA-80-CPF3
Page 3: ...Saijo denki International co ltd 2 ...
Page 41: ......
Page 46: ......
Page 47: ......
Page 49: ...Z Service valve Check joint Temperature Saijo denki International co ltd 41 Symbol ...