Code
Name
Description 1
Check Posltion
Description 2
SFV-30-A-VTGP1
SFV-36-A-VTGP1
SFV-50-A-VTGP1
SFV-60-A-VTGP1
SFV-80-A-VTGP1
SFV-120-A-VTGP1
01
-
-
-
-
-
-
-
-
-
-
- Check blockage at the drain pipe
-
-
-
-
-
-
-
- Check operating of the water pump
-
-
-
-
-
-
-
- Check operation of the float
-
-
-
-
-
-
-
- Check operation of the control board
Control board
- Check all connector sensor on control
board all position P1
-
-
-
-
-
-
- Check the wire of the sensor
- Check sensor resistance
- Check operation of the control board
Control board
- Check all connector sensor on control
board all position P2
-
-
-
-
-
-
- Check the wire of the sensor
- Check sensor resistance
- Check operation of the control board
Control board
- Check all connector sensor on control
board all position P3
-
-
-
-
-
-
- Check the wire of the sensor
- Check sensor resistance
- Check operation of the control board
Control board
- Check connector motor on control board
-
-
-
-
-
-
- Check operation of motor
Fan motor
- Check operation of the control board
Control board
Fan coil ass'y
Cross flow fan
Cross flow fan
-
-
- Check speed of fan motor
Fan motor
- Check the quantity of working fluid in the
system
-
-
-
-
-
08
-
-
-
-
-
-
-
-
-
09
-
-
-
-
-
-
-
-
-
10
-
-
-
-
-
-
-
-
-
Saijo denki International co.,ltd.
56
ERROR CODE
Indoor unit Inlet Temperature sensor
fail
There is an error in the refrigerant
temperature sensor at the Evaporator
inlet.
Defrost sensor (60 cm.) (Inlet)
Indoor unit Outlet Temperature
sensor fail
There is an error in the refrigerant
temperature sensor at the Evaporator
outlet.
Defrost sensorR (105 cm.) (Outlet)
6SP505AMWB296AS01
6SP431J-00003
6SP431J-00004
6SP511A-00008
6SP511A-0000704
6SP511A-00002
Control Ass'y
6SP505AMWB296AS01
6SP505AMWB296AS01
6SP505AMWB296AS01
02
04
03
Indoor unit Flood Protection
There is an error in the drainage of the
indoor unit
Indoor unit Room Temperature
sensor fail
There is an error in room temperature
seneor at the indoor unit.
6SP551A-00001
6SP551A-00013
6SP551A-00024
Room thermistor
6SP511A-00002
- Check the coil and fan blades
05
06
Indoor unit Motor fail
There is an error in the cooling motor
of the Indoor unit.
Indoor Antifreeze protection
There is freezing at cooling coil.
07
6SP504CSHA031
6SP511A-0000704
6SP511A-00008
6SP301ASFA016V
6SP301ASFA017V
6SP301ASFA010V
6SP505AMWB296AS01