Yes
No
Yes
No
No
Yes
No
Yes
No
Yes
Saijo denki International co.,ltd.
96
Is the supply voltage to the
outdoor unit control board
normal?
Check power voltage to control board
Is wiring connection from
control board to compressor
correct ?
Correct wiring connection
Is control board
working normal?
Check control board
Check compressor
Check code
Check code name
cause
Error 50
Compressor 2 Inverter Driver
Starting Fail
There is a failure in the start command to operate
compressor 2.
Is there shortage or
high refrigerant in the
system ?
Correct refrigerant amount
Is there cloging in the
refrigerant system ?
Correct refrigerant system