No
Yes
No
Yes
No
Yes
No
Yes
Saijo denki International co.,ltd.
81
Is silicon between control board
of compressor and Heatxink
normal?
Refill silicon to control board
Is resistance of
temperature sensor at
heatzink normal?
Replace the sensor
Check the control board
Check code
Check code name
cause
Error 32
Compressor1 Inverter Driver over
temperature
The control board of compressor 1 temperature is
overheated.
Is heatzink cooling fan at
control board of
compressor 1 normal ?
Replace the cooling fan
Is the attach between control
board of compressor 1 and
heatzink normal ?
Tighten the screw