No
Yes
No
Yes
No
Yes
Saijo denki International co.,ltd.
75
Is the wire of the sensor
normal ?
Change the sensor
Is sensor resistance
normal ?
Change the sensor
Check the control board
Check code
Check code name
cause
Error 17
Compressor 1 Discharge pipe
temperature sensor fail
Threr is an error in the refrigerant temperature
sensor at compressor 1 outlet.
Is sensor connect on
control board ?
Correct connector connection