SAHP - Installation Manual
|31
V3 June 2021US - SD667052
TROUBLESHOOTING
GUIDE
PROBLEMS
The water is cold and the
compressor is working.
The panel is frosting.
The water does not reach
temperature.
CAUSES
Lower set temperature.
The temperature sensor
is disconnected to the
cylinder.
The pipework between
the panel and the SAHP is
not properly insulated.
Incorrect refrigerant
charge.
Incorrect refrigerant
charge.
Incorrect Installation.
Refrigerant Leak or
charge.
SOLUTION
Check the temperature
set point on screen.
Check the right placement
of the temperature sensor
inside the cylinder.
Check the proper
insulation of the plumbing
circuit and the cylinder.
Check the R134a / 513a
charge (check the sight
glass for the refrigerant).
Check the R134a / 513a
charge (check the sight
glass for the refrigerant).
Ensure panel is installed
and unit installed
correctly.
Check for leaks. If pipe
run over 27 “ extra
refrigerant must be added
(check the sight glass for
the refrigerant).
Frost could appear during the normal operation and it
melts once the LMTB stops.