13
G
PREMASGARD
®
111x ⁄ 112x ⁄ 112x - SD
Rev. 2018 - V13 GB
DIP switch 6
is not assigned!
DIP switch 6
is not assigned!
Connection
*
:
2-wire connection for devices with ⁄ without display (not illuminated)
3-wire connection for devices with illuminated display
DIP switches for
pressure range setting, output attenuation and zero compensation:
Conversion table for pressure values:
Unit =
bar
mbar
Pa
kPa
mH
2
O
1 Pa
0.00001 bar
0.01 mbar
1 Pa
0.001 kPa
0.000101971 mH
2
O
1 kPa
0.01 bar
10 mbar
1000 Pa
1 kPa
0.101971 mH
2
O
1 bar
1 bar
1000 mbar
100000 Pa
100 kPa
10.1971 mH
2
O
1 mbar
0.001 bar
1 mbar
100 Pa
0.1 kPa
0.0101971 mH
2
O
1 mH
2
O
0.0980665 bar
98.0665 mbar
9806.65 Pa
9.80665 kPa
1 mH
2
O
Pressure range
(selectable, max. measuring range is depending to the type of device)
DIP switch 6
is not assigned!
0...1000 Pa
0...5000 Pa
0...10000 Pa
–1000...+1000 Pa
–5000...+5000 Pa –10000...+10000 Pa
DIP 1 DIP 2
0...100 Pa
0...1000 Pa
0...4000 Pa
–100...+100 Pa
–1000...+1000 Pa
–4000...+4000 Pa
OFF
OFF
0...300 Pa
0...2000 Pa
0...6000 Pa
–300...+300 Pa
–2000...+2000 Pa
–6000...+6000 Pa
O N
OFF
0...500 Pa
0...3000 Pa
0...8000 Pa
–500...+500 Pa
–3000...+3000 Pa
–8000...+8000 Pa
OFF
O N
0...1000 Pa
0...5000 Pa
0...10000 Pa
–1000...+1000 Pa
–5000...+5000 Pa
–10000...+10000 Pa
O N
O N
Measuring range mode
(Mode selectable)
DIP 3
Output characteristic line
(Mode selectable)
DIP 4
Measurement signal filtering
(Time interval selectable)
DIP 5
Unidirectional ( 0 ...+MR )
OFF
Linear
OFF
Long (10 s)
OFF
Bidirectional (–MR ...+MR )
O N
Square root extracting
O N
Small (1 s)
O N
Schematic diagram
*
Output:
4...20 mA
PREMASGARD
®
111x - I
PREMASGARD
®
112x - I
PREMASGARD
®
112x - SD - I
Schematic diagram
Output:
0 -10 V
PREMASGARD
®
111x - U
PREMASGARD
®
112x - U
PREMASGARD
®
112x - SD - U
1 2 3
123456
ON
Pushbutton
Offset
Plug for display
contact is
on the right side
Zero point setting
(auto zero)
Offset correction
see graph
ca.± 10% of
final value
Plug for
display
Offset
auto
zero
LED
DIP
switches
min. max.
Output pr
es
sur
e
0-
10
V in P
a
–UB GND
+UB 24V A
C/DC
1 2 3
123456
ON
Pushbutton
Offset
Plug for display
contact is
on the right side
Zero point setting
(auto zero)
Offset correction
see graph
ca.± 10% of
final value
Plug for
display
Offset
auto
zero
LED
DIP
switches
min. max.
+UB 24V DC
Output pr
es
sur
e P
a 4...2
0mA GND
(optional f
or L
CD
backlighting)