12
G
PREMASGARD
®
111x ⁄ 112x ⁄ 112x - SD
Rev. 2018 - V13 GB
Mounting diagram
Mounting diagram
Connecting diagram
Output:
4...20 mA
PREMASGARD
®
111x - I
PREMASGARD
®
112x - I
PREMASGARD
®
112x - SD - I
-
+
+
-
1 2 3
230V AC
PLC
Working
resistance
24V DC
+UB 24V DC
Output pr
es
sur
e P
a 4-20mA
GND
(optional f
or L
CD
backlighting)
-
+
+
-
1 2 3
230V AC
24V AC/DC
PLC
PC
+UB 2
4V AC/DC
-UB AC/DC GND
Output pr
es
sur
e P
a 0–10V
110 Pa
110 Pa
110 Pa
(A)
(B)
(C)
110 Pa
110 Pa
110 Pa
(A)
(B)
(C)
TYPES OF MONITORING:
(A) Below-atmospheric pressure:
P1 (
+
) is not connected
but open against atmosphere
P2 (
–
) connected to inside of duct
(B) Filter:
P1 (
+
) connected upstream of filter
P2 (
–
) connected downstream of filter
(C) Ventilator:
P1 (
+
) connected downstream of ventilator
P2 (
–
) connected upstream of ventilator
Pressure connections at the pressure switch
are marked with
P1 (
+
) for higher pressure and
P2 (
–
) for lower pressure.
Connecting diagram
Output:
0 -10 V
PREMASGARD
®
111x - U
PREMASGARD
®
112x - U
PREMASGARD
®
112x - SD - U
PREMASGARD
®
111x
PREMASGARD
®
112x
PREMASGARD
®
112x - SD
PREMASGARD
®
111x
PREMASGARD
®
112x
PREMASGARD
®
112x - SD
Load resistance diagram
4...20 mA
800
700
600
500
400
300
250
50
200
10
15
20
25
30 35 36 40
Load resistance diagram
W
orking r
esis
tanc
e (Ohm)
Operating voltage (V DC)
Admissible
range
800
700
600
500
400
300
250
50
200
10
15
20
25
30 35 36 40
Load resistance diagram
W
orking r
esis
tanc
e (Ohm)
Operating voltage (V DC)
Admissible
range