Offset adjustment is done at a potentiometer on the circuit board within  
an adjustment range of ± 10 % of the device’s pressure range. 

Ex-factory this potentiometer is in center position and is lacquer sealed. 

All settings and adjustments that are made before must be done in this 
configuration. 

Offset adjustment is carried out using a tool called “screwdriver 2.5”  
(blade with in mm). 

Automatic offset setting

1.  Before setting the zero point, the device must be in operation for  

at least 60 minutes.  

2.  Connect pressure inputs P (+) and P (–) by means of a hose  

(pressure difference between both inputs = 0 Pa). 

3.  For zero point setting press button uninterruptedly for 5 seconds.   

A LED signalises prompting the calibration by short flashing,  
and after a short countdown the measured (current) offset value is  
added to the measurand and zero voltage safe stored. 

Correct calibration is confirmed by steady light of the LED for  
3 seconds respectively indicated in the display (optional) by switching  
from “AUTO 0” to “PROG 0”. 

Note: By releasing the button during the countdown (counter > 0),  
zero point setting is immediately terminated! 

Manual offset adjustment

At the potentiometer OFFSET ∆P can be balanced.  
The adjustment range is ca. ± 10  % of the pressure range.  
Here another reference point different from zero point can be used. 

Readout in the display
In the 1st line of the display, the ACTUAL pressure up to the measuring range  
limit is displayed. 
Switching between the units Pa and hPa (100 Pa = 1 hP) happens automatically.   
Pa  =  Pascal 
hP  =  Hektopascal

The following configurations can be preset via 
DIP switches. 

The DIP switch sliding blocks can be moved 
without using tools. DIP switch 6 is not assigned. 

Pressure ranges 

In each case four different pressure ranges 
depending on the type of device can be preset 
via DIP switches DIP 1 and DIP 2.

Measuring range mode

The measuring range is configured via DIP 
switch DIP 3, either into the unidirectional range 
or into the bidirectional range. 

Therefore altogether eight pressure measuring 
ranges are configurable.

Characteristic line – analog output

The output characteristic line can be defined via 
DIP switch DIP 4. Here is distinguished between 
a linear and a square root extracting output 
characteristic line. When square root extracting 
output characteristic line is selected, the 
measuring range setting at DIP switches DIP 1 
and DIP 2 is without function. 

In that case the maximum pressure range is 
used for computation.  

Measurement signal filtering

In order to stabilize the pressure measurement 
signal and the  output voltage, the measurement 
signal is filtered. 

The time interval for such averaging can be 
preset via DIP switch DIP 5 to 1 or 10 seconds. 

By a longer filtering interval, the settling time of 
the sensor is automatically extended. 

G  

PREMASGARD

®

  111x  112x  112x - SD

  |  Configuration and zero point calibration

Summary of Contents for PREMASGARD 111x

Page 1: ...Operating Instructions Mounting Installation Pressure and differential pressure measuring transducers including connection set compact form adjustable calibratable with multi range switching and activ...

Page 2: ...12 37 8 14 8 14 8 43 3 12 39 49 4 3 15 6 4 15 64 M16x1 5 M16x1 5 PREMASGARD 111x PREMASGARD 112x Ma zeichnung Dimensional drawing Plan cot Ma zeichnung Dimensional drawing Plan cot ohne Display withou...

Page 3: ...20 mA elektrischer Anschluss 2 oder 3 Leiteranschluss Medientemperatur 20 50 C Druckanschluss 4 6 x 11 mm Schl uche 4 6 mm Druckanschluss Stutzen aus Metall Druckart Differenzdruck Medium saubere Luft...

Page 4: ...000 Pa 0 8000 Pa 8000 8000 Pa 0 10000 Pa 10000 10000 Pa PREMASGARD 1116 U 0 10 V 1301 1111 0060 000 PREMASGARD 1116 U DISPLAY 0 10 V 1301 1111 2060 000 PREMASGARD 1116 I 4 20 mA 1301 1112 0060 000 PRE...

Page 5: ...diagramm B rde Ohm Betriebsspannung DC V zul ssiger Bereich BERWACHUNGSARTEN A Unterdruck P1 wird nicht angeschlossen ist luftseitig offen gegen Atmosph re P2 Anschluss im Kanal B Filter P1 Anschluss...

Page 6: ...hnungstabelle f r Druckwerte Einheit bar mbar Pa kPa mWs 1 Pa 0 00001 bar 0 01 mbar 1 Pa 0 001 kPa 0 000101971 mWs 1 kPa 0 01 bar 10 mbar 1000 Pa 1 kPa 0 101971 mWs 1 bar 1 bar 1000 mbar 100000 Pa 100...

Page 7: ...entiometer kann der OFFSET P abgeglichen werden Der Einstellbereich betr gt ca 10 vom Druckbereich Hierbei kann ein anderer Referenzpunkt als der Nullpunkt verwendet werden Anzeige im Display Im Displ...

Page 8: ...etr gt die Ausgangsspannung bei Mittelstellung des Offsetreglers 5V bei OPa Druckdifferenz Ausgangsspannung 0 10V f r Druckdifferenz P P I Variante MB 0 xxPa Nach erfolgreicher Nullpunktkalibrierung b...

Page 9: ...technischen Daten und Anschlussbedingungen der zum Ger t gelieferten Montage und Bedienungs anleitung Abweichungen zur Katalogdarstellung sind nicht zus tzlich aufgef hrt und im Sinne des technischen...

Page 10: ...r 3 wire connection Media temperature 20 50 C Pressure connection 4 6 x 11 mm hoses 4 6 mm metal pressure connection nozzles Type of pressure differential pressure Medium clean air and other non aggre...

Page 11: ...000 Pa 8000 8000 Pa 0 10000 Pa 10000 10000 Pa PREMASGARD 1116 U 0 10 V 1301 1111 0060 000 PREMASGARD 1116 U DISPLAY 0 10 V 1301 1111 2060 000 PREMASGARD 1116 I 4 20 mA 1301 1112 0060 000 PREMASGARD 11...

Page 12: ...ected upstream of filter P2 connected downstream of filter C Ventilator P1 connected downstream of ventilator P2 connected upstream of ventilator Pressure connections at the pressure switch are marked...

Page 13: ...2000 Pa 6000 6000 Pa O N OFF 0 500 Pa 0 3000 Pa 0 8000 Pa 500 500 Pa 3000 3000 Pa 8000 8000 Pa OFF O N 0 1000 Pa 0 5000 Pa 0 10000 Pa 1000 1000 Pa 5000 5000 Pa 10000 10000 Pa O N O N Measuring range m...

Page 14: ...display In the 1st line of the display the ACTUAL pressure up to the measuring range limit is displayed Switching between the units Pa and hPa 100 Pa 1 hP happens automatically Pa Pascal hP Hektopasca...

Page 15: ...ral position Output voltage 0 10 V for pressure difference P P I variant Range 0 xxPa After successful zero point calibration the output current is 4 mA at 0 Pa pressure difference with the offset kno...

Page 16: ...g conditions of the mounting and operating instructions delivered together with the device are exclusively valid Deviations from the catalogue representation are not explicitly mentioned and are possi...

Page 17: ...e sortie 0 10 V ou 4 20 mA Raccordement lectrique 2 ou 3 fils Temp rature du fluide 20 50 C Prise de pression 4 6 x 11 mm flexibles 4 6 mm raccords de pression en m tal Type de pression pression diff...

Page 18: ...8000 8000 Pa 0 10000 Pa 10000 10000 Pa PREMASGARD 1116 U 0 10 V 1301 1111 0060 000 PREMASGARD 1116 U DISPLAY 0 10 V 1301 1111 2060 000 PREMASGARD 1116 I 4 20 mA 1301 1112 0060 000 PREMASGARD 1116 I D...

Page 19: ...de raccordement Sortie 0 10 V PREMASGARD 111x U PREMASGARD 112x U PREMASGARD 112x SD U PREMASGARD 111x PREMASGARD 112x PREMASGARD 112x SD PREMASGARD 111x PREMASGARD 112x PREMASGARD 112x SD Diagramme d...

Page 20: ...2000 2000 Pa 6000 6000 Pa O N OFF 0 500 Pa 0 3000 Pa 0 8000 Pa 500 500 Pa 3000 3000 Pa 8000 8000 Pa OFF O N 0 1000 Pa 0 5000 Pa 0 10000 Pa 1000 1000 Pa 5000 5000 Pa 10000 10000 Pa O N O N Mode Plage d...

Page 21: ...r f rence diff rent du point z ro Affichage sur l cran Sur la 1 re ligne de l cran s affiche la pression effective jusqu la limite de la plage de pression La commutation entre les unit s Pa et hPa 10...

Page 22: ...de 0 Pa Tension de sortie 0 10V pour diff rence de pression P P variante I plage de mesure 0 xxPa Une fois le calibrage du point z ro effectu le courant de sortie si le bouton offset est en position m...

Page 23: ...ctu e uniquement par un sp cialiste qualifi Seules les donn es techniques et les conditions de raccordement indiqu es sur la notice d instruction accompagnant l appareil sont applicables des diff renc...

Page 24: ...4 6 x 11 4 6 1111 1121 1121 SD 1000 10 1115 1125 1125 SD 5000 50 1116 1126 1126 SD 10000 50 10 5 x 1 1c 10c 0 3 0 1 C 20 1 30 RAL 9016 111x 112x 112x SD 72 x 64 x 37 8 Tyr 1 Tyr 01 72 x 64 x 43 3 Tyr...

Page 25: ...1112 0050 000 PREMASGARD 1115 I DISPLAY 4 20 A 1301 1112 2050 000 10000 10000 PREMASGARD 1116 IP 65 0 4000 4000 4000 0 6000 6000 6000 0 8000 8000 8000 0 10000 10000 10000 PREMASGARD 1116 U 0 10 1301 1...

Page 26: ...tance diagram Working resistance Ohm Operating voltage V DC Admissible range A P1 P2 B P1 P2 C P1 P2 P1 P2 0 10 PREMASGARD 111x U PREMASGARD 112x U PREMASGARD 112x SD U PREMASGARD 111x PREMASGARD 112x...

Page 27: ...ches min max UB 24V DC Output pressure Pa 4 20mA GND optional for LCD backlighting DIP 1 0 00001 0 01 1 0 001 0 000101971 1 0 01 10 1000 1 0 101971 1 1 1000 100000 100 10 1971 1 0 001 1 100 0 1 0 0101...

Page 28: ...28 10 2 5 1 60 2 P P 0 3 5 3 AUTO 0 PROG 0 0 OFFSET P 10 100 1 DIP DIP6 DIP1 DIP2 DIP3 DIP4 DIP1 DIP2 DIP5 1 10 r PREMASGARD 111x 112x 112x SD...

Page 29: ...29 U 0 xx 0 0 0 10 0 U xx xx 5 0 0 10 I 0 xx 4 0 4 20 0 I xx xx 12 0 4 20 r PREMASGARD 111x 112x 112x SD...

Page 30: ...30 r P P 10 90 ZVEI VDE EMV 0 10 0 UB 15 36 UB GND 24 Circuitry Circuitry 0 10V 0V GND 0 10V 0V GND Power supply AC 24V 0V DC 15 36V GND Circuitry 0 10V 0V GND V Power supply AC 24V 0V DC 15 36V GND...

Page 31: ...on PREMASGARD 112x SD Ma zeichnung Dimensional drawing Plan cot mit Schnappdeckel with snap on lid avec couvercle embo t 37 8 14 8 7 39 49 4 3 15 30 6 4 107 72 64 M16x1 5 Copyright by S S Regeltechnik...

Page 32: ...ction set Kit de raccordement Ma zeichnung ASD 06 Dimensional drawing Plan cot ASD 07 Anschlussnippel Connection nipple Embouts de raccordement DAL 01 Druckauslass Pressure outlet Sortie pression Ma z...

Reviews: