Before powering up the door
WARNING
It is recommended that this pretest be done by a certified electrician.
1
Make sure
the power to the door is correct.
▪
Open
the System 4 control box and check the power supply
listed on the label inside.
▪
Test
the voltages at the disconnect. Test leg to leg and leg to ground.
▪
If power is correct,
power up
the door and start the set limits sequence.
How to sync the SmartSurround™ system to the controller, set
limits, and test the door
CAUTION
Make sure
that people and vehicles do not pass through the open doorway
until the automatic calibration is complete. The door can open or close
unexpectedly, resulting in injury.
NOTE: The System 4 display uses hexadecimal numbers to
number parameters and for some values.
The display uses the ten numeric characters (0-9), plus six
letters (A-F), which represent the values from 11 through 16.
In some cases it will be necessary to press the UP arrow
sixteen times to change a value from 0000 to 0010.
Icon
key
Sample
electrical
specs
shown
■
While the control box is open,
locate
the 120Ω resistor for
CAN bus testing taped to the
bottom of the box
#2
Multimeter
001=
1979 Cyc
P:Password
O
Access level
O
= Operator level
S
= Service level
Accesses more parameters
R
= Rytec level
Accesses all parameters
Requires password from technical support
Blinking cursor
On left side of display:
press arrows to change parameter number
On right side of display:
press arrows to change paramter value
Parameter name
The Controller Display
The Controller Controls
Parameter
number
All three digits are
hexadecimal
Parameter value
?
= value being changed
?
= change saved
RESET Button
▪
Press
to toggle the flashing cursor
between parameters and values
▪
Press and hold
to save changes
to a value
UP Arrow
▪
Press
to increase a value or
parameter number
▪
Press and hold
to increase values
or parameter numbers quickly
DOWN Arrow
▪
Press
to decrease a value or
parameter number
▪
Press and hold
to decrease values
or parameter numbers quickly
OPEN
OPEN
CLOSE
CLOSE
RES
ET
RESET
Press UP or DOWN
arrow, as needed
Press and
hold
Press
Make sure
the protective film
has been removed from the
Advanced
3
light curtains in
both door tracks before
turning on power
to the door.
First: set the controller to Parameter mode and access Service level parameters
Do This
Result
1
The door starts in run mode.
2
You are in Parameter mode. Go to parameter 999.
3
The Password parameter P:999 screen displays.
Do This
Result
4
You can now change the value of parameter P:999.
5
Set the value to 10 (Service level password).
6
The Service level password is saved.
7
The controller automatically moves to
parameter L:201.
0 Cycles
Spiral
Turn on power
to controller
001=
[xxx] Cyc
P:Password
O
until the parameter screen displays
RY-UI-000050
PDN-UI-000051
999=
0000
0
#
00
P:Password
O
2x
to reach parameter P:999
PDN-UI-000052
1x
to move cursor to the right (edit value)
0000
0
#
00
999=
P:Password
O
PDN-UI-000059
999=
0010?#
00
P:Password
O
16x
to set value to hexadecimal 10
PDN-UI-000060
until question mark changes to
checkmark (value saved)
999=
0010
0
#
00
P:Password
S
201=
-
#
L:SAI Slot2