RVR Energy Technology VICTRIX 24kW X Instruction Booklet Download Page 6

Page 6 

 

 

Victrix 24kW X Instructions 

General Installation Information 

Gas Supply 

The meter and supply pipes must be sized to deliver the gas rate and pressure given on page 3.    The 
boiler requires at least a 22 mm (3/4”) gas supply pipe.  The complete installation, including the meter, must 
be tested for gas soundness and purged as described in IS 813:2002.

 

The boiler requires a 220/240 V ~ 50 Hz mains supply, fused at 3 A.  

The boiler must be earthed.  The polarity 

of the supply must be correct as otherwise the boiler will not operate. 
 

There must only be one common isolator, providing complete electrical isolation, for the boiler and any external 
controls.  Using PVC  insulated cable not less than 0.75 mm² (24 x 0.2 mm) to BS 6500 Table 16, the boiler should 
be connected to a fused three pin plug and unswitched shuttered socket outlet (both complying with BS 1363), or a 
fused double pole  switch with a contact separation of at least 3 mm in both poles. Wiring external to the boiler 
must be in accordance with the current IEE Wiring Regulations. 

 

Note: 

External controls connected to the boiler must be of the volt free type and are connected to terminals 40 and 41 as 

shown above.   

DHW Sensor 

If the boiler’s hot water priority feature is to be used, then the optional DHW sensor must be mounted on the hot 
water heating tank and connected to terminals 36 and 37.  If this cable is routed in close proximity to cables carry-
ing mains voltages, then screened cable should be used. The resistor connected to terminals 36 and 37 to be re-
moved in this case. 

Weather Compensation: 

A temperature sensor for outdoors is available as an optional accessory for the boiler.  This should be fitted in an 
outdoor location which is not exposed to direct sunlight.  A north facing wall is a good location.  If the optional 
weather compensation sensor is used, it should be connected to terminals 38 and 39 as shown above using a two 
core cable.  If this cable is routed in close proximity to cables carrying mains voltages, then screened cable should 
be used.  Contact RVR for more information. 
When the sensor is connected, the boiler adapts it’s flow temperature to suit the prevailing weather conditions.  
This results in lower energy usage and enhanced comfort. 

 

Warning! - Connection of a voltage to any boiler terminals other than the mains lead will result in destruc-
tion of the boiler control panel.  The product warranty does not cover this type of damage. 

 

Clearances and Air Supply 

The boiler does not require any air vents for cooling in the room in which it is installed or when installed in a cup-
board or compartment. The minimum clearances for servicing must always be maintained.  Please see table on 
page 3.  

Note: 

A  cupboard or compartment used to enclose the boiler must be designed and constructed specifi-

cally for the purpose. 

 

 

 

Summary of Contents for VICTRIX 24kW X

Page 1: ...ority For Technical assistance spare parts or service call RVR Energy Technology Limited Kenmare Co Kerry Tel 064 41344 Fax 064 89520 Doc Ref ALT107 181207 Read these instructions completely before us...

Page 2: ...I S 820 Non Domestic Gas Installations All relevant Building Regulations Local Water Bye Laws IEE Wiring Regulations Health Safety legislation This appliance meets the requirements of IPX4D ie degree...

Page 3: ...Immergas 80 litre T 30 C in accordance with EN 625 1 min 20 2 Specific range D UB Immergas 105 litre T 30 C in accordance with EN 625 1 min 22 0 Specific range D UB Immergas 120 litre T 30 C in accord...

Page 4: ...uctions Dimensions Victrix 24kW X Key V Electrical connection G Gas supply RU Cylinder return optional MU Cylinder flow optional RR System filling SC Condensate drain min internal diameter 13mm R Syst...

Page 5: ...ectrode 21 Safety thermostat 4 Gas valve 13 Air intake pipe 22 Air valve 5 Voltage transformer 14 Negative signal pressure point 23 Boiler circulating pump 6 Fan 15 Positive signal pressure point 24 S...

Page 6: ...heating tank and connected to terminals 36 and 37 If this cable is routed in close proximity to cables carry ing mains voltages then screened cable should be used The resistor connected to terminals...

Page 7: ...with the round protrusions facing downwards in con tact with boiler flange and tighten using the screws supplied with the kit Fit the male end smooth of the adapter 3 in the female end of the concent...

Page 8: ...he fe male end of the flanges 3 4 Fit the male end of the intake terminal 6 up to the stop on the female end of the bend 5 making sure that the relevant internal and external sealing rings are fitted...

Page 9: ...g tables The resistance factor varies depending on whether the component in question conveys fresh inlet air or hot combustion gases All boilers have a maximum resistance factor of 100 The sum of all...

Page 10: ...nces Component Resistance Quantity Total 80mm Intake pipe 0 87 9 7 83 90 air intake bend 1 9 3 5 7 80mm Flue pipe 1 2 6 7 2 90 Flue bend 2 6 2 5 2 25 93 Total Flue Resistance In this case the total re...

Page 11: ...terminal is fitted within 850 mm of a plastic or painted gutter or 450 mm of painted eaves or 300 mm of a plastic car port roof an aluminium shield at least 1 m long should be fitted to the underside...

Page 12: ...iler may be installed in any room or internal space although particular attention is drawn to the re quirements of the current IEE Wiring Regulations Where a room sealed boiler is installed in a room...

Page 13: ...orporated into the boiler is pre charged to 1 0 bar and is suitable for a sealed heating system with a maximum water content of 80 litres 18 gal Above 80 litres consideration should be given to fittin...

Page 14: ...to heat the hot water tank adequately The hot water only position on the boiler is not in use for this configuration Filling the central heating system The system design pressure cold should be set to...

Page 15: ...appliance with wet hands or other parts of the body and never touch when barefoot never pull electrical cables or leave the appliance exposed to atmospheric agents rain sunlight etc the appliance pow...

Page 16: ...cleaning function symbol Malfunction symbol combined with error code Flame present symbol Burner output scale symbol Fault and anomaly signalling The Victrix 24 kW boiler indicates any malfunctions us...

Page 17: ...valve No pressure variation must occur in the next five minutes on the gauge Ensure activation of the device for protection against the ionisation flame control gas activation time must be less than...

Page 18: ...Page 18 Victrix 24kW X Instructions Variable Heat Output Victrix 24kW X...

Page 19: ...Page 19 Victrix 24kW X Instructions Victrix 24kW X Wiring Diagram...

Reviews: