RVR Energy Technology VICTRIX 24kW X Instruction Booklet Download Page 14

Page 14 

 

 

Victrix 24kW X Instructions 

The boiler has two sets of flow/return connections.  One set is used for connection to the central system 
while the other set is connected to the coil of the domestic hot water heating tank.  The boiler incorporates 
a diverter valve which diverts all flow to heat the DHW tank when the temperature of the hot water tank is 
below the temperature set on the boiler.  The optional 3 way valve kit ACB515 and the sensor must be fit-
ted to the tank in order for this feature to work. 

Alternatively, if  hot water priority operation is not required, the boiler may be plumbed as shown below.  In 
this type of installation, the DHW flow and return connections should be capped or connected to each other.  
If a hot water heating tank is connected as shown below, then it will not be possible to use the boiler’s 
weather compensation feature as the boiler flow temperature may not be sufficient to heat the hot water 
tank adequately. The hot water only position on the boiler is not in use for this configuration. 

Filling the central heating system 

The system design pressure (cold) should be set to 1.0 bar. This pressure is equivalent to a static head of 
10.2 metres of water.  Provision should be made to replace water lost from the system. This can be by 
manual or automatic means.   
 
Filling of the system must be carried out in a manner approved by the local authority. Where allowed, the 
system may be filled via a temporary connection as shown below or by using the integrated filling valve in 
the boiler.  After filling, always disconnect the flexible hose of the filling loop if used and close the filling 
valve in the boiler. 
 
All fittings used in the system must be able to withstand pressures up to 3 bar. Drain taps (to BS 2879) 
must be used to allow the system to be completely drained. The heating system should be thoroughly 
flushed before the boiler is connected and again after the first heating. If it is necessary to add inhibitor to 
the central heating system, contact RVR Ltd. for guidance. 

 

24 kW X 

 

24 kW X 

Summary of Contents for VICTRIX 24kW X

Page 1: ...ority For Technical assistance spare parts or service call RVR Energy Technology Limited Kenmare Co Kerry Tel 064 41344 Fax 064 89520 Doc Ref ALT107 181207 Read these instructions completely before us...

Page 2: ...I S 820 Non Domestic Gas Installations All relevant Building Regulations Local Water Bye Laws IEE Wiring Regulations Health Safety legislation This appliance meets the requirements of IPX4D ie degree...

Page 3: ...Immergas 80 litre T 30 C in accordance with EN 625 1 min 20 2 Specific range D UB Immergas 105 litre T 30 C in accordance with EN 625 1 min 22 0 Specific range D UB Immergas 120 litre T 30 C in accord...

Page 4: ...uctions Dimensions Victrix 24kW X Key V Electrical connection G Gas supply RU Cylinder return optional MU Cylinder flow optional RR System filling SC Condensate drain min internal diameter 13mm R Syst...

Page 5: ...ectrode 21 Safety thermostat 4 Gas valve 13 Air intake pipe 22 Air valve 5 Voltage transformer 14 Negative signal pressure point 23 Boiler circulating pump 6 Fan 15 Positive signal pressure point 24 S...

Page 6: ...heating tank and connected to terminals 36 and 37 If this cable is routed in close proximity to cables carry ing mains voltages then screened cable should be used The resistor connected to terminals...

Page 7: ...with the round protrusions facing downwards in con tact with boiler flange and tighten using the screws supplied with the kit Fit the male end smooth of the adapter 3 in the female end of the concent...

Page 8: ...he fe male end of the flanges 3 4 Fit the male end of the intake terminal 6 up to the stop on the female end of the bend 5 making sure that the relevant internal and external sealing rings are fitted...

Page 9: ...g tables The resistance factor varies depending on whether the component in question conveys fresh inlet air or hot combustion gases All boilers have a maximum resistance factor of 100 The sum of all...

Page 10: ...nces Component Resistance Quantity Total 80mm Intake pipe 0 87 9 7 83 90 air intake bend 1 9 3 5 7 80mm Flue pipe 1 2 6 7 2 90 Flue bend 2 6 2 5 2 25 93 Total Flue Resistance In this case the total re...

Page 11: ...terminal is fitted within 850 mm of a plastic or painted gutter or 450 mm of painted eaves or 300 mm of a plastic car port roof an aluminium shield at least 1 m long should be fitted to the underside...

Page 12: ...iler may be installed in any room or internal space although particular attention is drawn to the re quirements of the current IEE Wiring Regulations Where a room sealed boiler is installed in a room...

Page 13: ...orporated into the boiler is pre charged to 1 0 bar and is suitable for a sealed heating system with a maximum water content of 80 litres 18 gal Above 80 litres consideration should be given to fittin...

Page 14: ...to heat the hot water tank adequately The hot water only position on the boiler is not in use for this configuration Filling the central heating system The system design pressure cold should be set to...

Page 15: ...appliance with wet hands or other parts of the body and never touch when barefoot never pull electrical cables or leave the appliance exposed to atmospheric agents rain sunlight etc the appliance pow...

Page 16: ...cleaning function symbol Malfunction symbol combined with error code Flame present symbol Burner output scale symbol Fault and anomaly signalling The Victrix 24 kW boiler indicates any malfunctions us...

Page 17: ...valve No pressure variation must occur in the next five minutes on the gauge Ensure activation of the device for protection against the ionisation flame control gas activation time must be less than...

Page 18: ...Page 18 Victrix 24kW X Instructions Variable Heat Output Victrix 24kW X...

Page 19: ...Page 19 Victrix 24kW X Instructions Victrix 24kW X Wiring Diagram...

Reviews: