2) Installation Requirements
2.1)
Both the Bank A and Bank B Supply lines MUST be protected with individual 40 Amp fuses,
preferably at (or near to) the battery terminal.
2.2)
If the splitter charge primary sense input is used, the input MUST be protected by a 1 Amp fuse,
preferably at (or near) to the primary battery terminal.
2.3)
DO NOT obstruct fan vents along the top, side or under surfaces of the CVS012. Do not install
any equipment on top or underneath the CVS012.
The above installation requirement must be followed for safe operating and extended product
lifetime