background image

THERMOSTAT (option)

If you want constant heat, day and night, you will be sur-
prised  of  what  the  wall  thermostat  option  can  do  for  you.
Once you have your fire burning, just set the manual con-
trol  on  low  (push  the  draft  control  lever  all  the  way  to  the
left) and let the automatic thermostat take over.  Your room
temperature will keep as even as though you were heating
with oil, gas, or electricity - except you will find wood heat
more comfortable  (see Options: Wall Thermostat part FD-
HC4).

NOTE:  This  thermostat  controls  the  combustion  air  rate,
not the internal circulating blower.  

INTERNAL CIRCULATING BLOWER (option)

If  you have the optional internal blower installed, adjust the
speed of the blower to the output you require.  The blower
speed control should have been installed at a convenient
place on the wall.  When a fire is burning, the thermo disc
installed inside the fireplace will turn on at 110° F, allowing
the blower to operate; this will take about 20 minutes from
the time you start the fire. When the Delta cools to 90°F, the
switch deactivates the blower.  The maximum heat output
of  the  fireplace  is  greater  with  the  blower  running    (see
Options: Circulating Blower part FD-HB5-N).

GRAVITY VENT SYSTEM (option)

If there are areas in your home that you would like to heat
either  in  an  upper  level  or  an  adjacent  room,  the  gravity
vent system can provide this heat with or without the use of
a  blower.    It  is  controlled  by  a  gravity  vent  damper.    The
handle is located above the top left louvers of the fireplace.
Simply turn the lever to adjust the air flow through the grav-
ity  vent  ducting.   As  the  hot  air  rises,  it  will  be  distributed
through  the  insulated  ducting  to  the  outlet  (see  Options:
The Gravity Vent System part FD-VD, page 24).

CENTRAL HEAT SYSTEM (option)

You  have  the  option  to  heat  remote  rooms  in  your  home
from the heat generated by your fireplace.  If this option is
installed,  there  may  be  a  thermostat  installed  in  the  main
room you want to heat, away from the room that contains
the  fireplace.  Or  a  thermostat  installed  that  removes  heat
from  the  fireplace  when  the  main  room  you  are  trying  to
heat  reaches  the  desired  temperature.  This  thermostat
controls the blower, which brings air to the other rooms in
your  home,  keeping  them  at  the  temperature  you  desire.
When the blower is running, it takes air from the room the
Delta is in, draws it around the fireplace and distributes it
(see  Options:  Central  Heating  System  parts  FD-HC6/FD-
HB6).

NOTE: The blower (part FD-HB6) can push warm air either
up or down, and can also be zone controlled (see Options:
Zone Heating and diagrams).

HINT:  If  some  evening  you  would  like  to  enjoy  the  ambi-
ence of the wood flame, but you are a little too warm, turn
up the central heating thermostat and open a window in the
room the ducting goes to.  This will keep your room in front
of the fire from getting too warm.

OPERATION

THE FIRST FIRE

Before  the  first  fire,  be  absolutely  sure  to  wipe  off  all  fin-
gerprints and debris from the gold plating, if you have cho-
sen this option.  The plating undergoes a sealing process
during this first fire, and the acid from your finger prints will
permanently  etch  the  gold  plating.   You  will  experience  a
slow start-up during the first fire.  The refractory bricks still
contain moisture and take a good hot fire to get rid of the
moisture.  While there is moisture in the bricks, the bricks
will  be  black  with  smoke  deposits.    When  the  moisture  is
gone,  the  bricks  will  turn  white.    You  will  experience  an
odour during the first few fires.  This odour results from the
curing paint and the burn-off of oil from the heat exchang-
er. Ventilate room to expel odours.

LIGHTING

Slide the draft control that is located above the lower right
side louvers all the way to the right.  Light a fire in the fire-
place, starting with paper and kindling only.  Then add 2-3"
diameter  wood.    After  the  fire  is  established,  close  the
doors to prevent overheating of the fireplace face. The unit
is  designed  to  accept  combustion  air  through  the  outside
air duct only.  (See the Combustion Control System, page
5)  Never use any flammable liquids.  Once a coal bed is
established, add standard cord wood.  Leave the draft con-
trol  open  until  the  fire  is  well  lit,  then  adjust  it  to  the  level
you desire.

Warning:  

Do not use a grate or elevate the fire.

REFUELLING

Fuel  wood  can  be  of  any  species.    However,  ensure  that
the wood is well seasoned and kept under cover. 

NOTE:  The  central  heat  and  internal  blowers,  if  installed,
should be shut off during refuelling to prevent smoke from
spilling out of the fireplace.

The  door  should  be  opened  slowly  to  keep  smoke  from
spilling  into  your  room.  If  you  do  have  smoke  spillage,
check to see that all kitchen and bathroom fans have been
shut  off.  They  can  cause  a  vacuum  in  the  house,  which
pulls smoke out of the fireplace.

Page 4

DELTA

Summary of Contents for DELTA

Page 1: ...Keep these instructions for future use Owner s Manual Residential Factory Built Fireplace Operation Maintenance Installation Delta 01 03 The DELTA ...

Page 2: ...it 19 Remote Venting 19 The Gravity Vent System 21 The Central Heat System 24 Zone Heating WIRING DIAGRAMS 26 Zone Heat System 27 Thermostat 27 Circulating Blower 27 Central Heat System 27 All Systems Combined REPLACEMENT PARTS LIST 28 Replacement Parts List LABEL 29 Label WARRANTY 30 Warranty Page 2 Dear Customer The Delta incorporates technology with elegance to give you a beautiful view of the ...

Page 3: ... fire The chimney must be inspected periodically during the heating season to see if a creosote buildup has occurred If a significant layer of creosote has accumulated 1 4 or more it should be removed to reduce the risk of chimney fire Warning burn seasoned wood only Do not burn driftwood treated wood coal garbage plastic Do not use construction scraps e g 2x4 or plywood scraps as your only supply...

Page 4: ...it takes air from the room the Delta is in draws it around the fireplace and distributes it see Options Central Heating System parts FD HC6 FD HB6 NOTE The blower part FD HB6 can push warm air either up or down and can also be zone controlled see Options Zone Heating and diagrams HINT If some evening you would like to enjoy the ambi ence of the wood flame but you are a little too warm turn up the ...

Page 5: ...ver the pins can be turned so that the doors seal well and fit with each other After adjustment tighten the Allen screws holding the hinge pins in place with the screwdriver and replace the door If the left side door fits correctly and the front door does not pass the paper test then the angle bracket needs to be adjusted Loosen the four screws that are attached to the centre door and slightly adj...

Page 6: ...pipe This can be done by removing the cotter pin from the top right side of the secondary air pipe and sliding the pipe as far as it goes to the left Then when the right side drops out of its hole slide it to the right until the other side drops To remove the baffle push up and slide it off the brackets Replace both as you removed them and be sure the holes on the secondary air pipe are facing tow...

Page 7: ...onents for gravity system central heat blower framing guide standoff gravity vent damper handle Hearth extension radiation shield ceiling clearance 39 min 84 from base to the ceilling fresh air hood at floor level For other installation options see figure 7 electrical knockouts Figure 2 General assembly ...

Page 8: ...between the two forks before using STANDOFF INSTALLATION Before installing your Delta the side nailing strips need to be assembled as follows 1 Remove the nailing strips from the top of the unit 2 Remove the four 4 metal screws on each side of the Delta facing 3 Attach the nailing strip to the side of the Delta using the metal screws that you removed in Step 2 Figure 4 NOTE When using the optional...

Page 9: ...lexible pipe must be used 1 Use the side or back outside air outlet 2 Find a convenient location for the combustion air duct and intake air hood The location of the intake air hood may be above or below floor level see Figure 7 Under no circumstances should the combustion air inlet be placed in attic spaces 3 Make a 4 1 4 5 1 4 if using a 5 diameter duct hole in the outside wall of the house Mount...

Page 10: ...r above the radiation shield as shown in Figure 8 3 Place the first chimney length on the fireplace Secure the chimney length to the fireplace with the three screws provided The chimney must extend at least 3 ft above its point of contact with the roof and at least 2 ft higher than any wall roof or building within 10 ft of it Refer to the Excel instruc tion installation flue height requirements fo...

Page 11: ...heat loss If the climate in your area is mild insulate the chase at least to the first firestop If the climate in your area is very cold insulate the chase to the top to keep the flue warmer to increase the draft and reduce creosote buildup If required by local codes make certain that the walls have been properly insulated vapour sealed and sheathed with a fire rated gypsum board see Figure 9 10 R...

Page 12: ...must NOT go closer to the fireplace than the stand offs top back and sides You may also completely cover the top of the Delta as long as you main tain top standoff clearances and the 2 clearances around the chased chimney The 2 clearance around the chimney must be open to the fireplace up to the first fire stop 39 min SPARK GUARD Install a 5 piece of sheet metal centred under the joint between the...

Page 13: ...rk guard 16 min 8 min 44 Figure 16 Clearance to combustibles mantle is 50 1 2 mini mum from the base of the fireplace 10 1 2 min no limit to side surround as long as 11 side clearance is observed MANTEL A masonry or other non combustible mantle may be placed directly above the top louvers If a wood or other com bustible mantle is desired then it must be at least 10 1 2 inches above the top louver ...

Page 14: ...17 Installation of mantles and crown moulding backing 2x4 corner moulding hides mounting screws bolts screw bolt attaches crown moulding to backing 2x4 counter sink and fill crown moulding 11 6 12 25 4 12 24 47 12 12 8 6 16 2 5 5 35 3 29 19 44 2 framing guide 5 Figure 18 Unit dimensions 47 ...

Page 15: ...re will be some increase in warm air movement to the room serviced by the gravity vent If you desire even heat throughout your home strictly from your fireplace or if you want to move heat to a remote area of your home it is recommended that you incorpo rate the central heat option parts FD HC6 and FD HB6 A thermostatically controlled blower takes heat from the fireplace and distributes the warm a...

Page 16: ... blower with the outlet facing up from the back Fit the blower through the louver opening 3 Slide the blower into the two blower mounts being sure that it is pushed all the way down 4 Mount the thermo disc as shown in Figure 21 The front face of the fireplace is bent into a flange just above the lower opening The thermo disc mounts just above the centre louvers Push the clips on to the flange as f...

Page 17: ... it is recommended that you purchase the rock retainer kit part FD KD 1 to help keep the facing in place It is NOT recommended for brick or other self supporting materials Follow these steps NOTE Remove the fireplace doors and louvers and store them in a safe place until the masonry work is finished Acid from the cleaning operation will permanently damage the gold plating Ensure that the cover rem...

Page 18: ... must be removed for this option optional soldiering brick over louver openings Figure 25 Facing with soldiering brick Note when using a thicker facing be sure to leave enough room for the door to swing wide top framing guide use only the pre drilled holes in the rock retainer kit for screwing to the face spread plaster over more than a workable area so that the mortar will not set before the faci...

Page 19: ...rts is allowed These genuine RSF Woodburning Fireplaces parts have the correct clearances These clearances must be maintained for your safety exept that B vent components can be replace by ICC double wall black pipe ULTRABlack UBF use only UBF black pipe The FD VD system incorporates standard 8 B vent com ponents for installation Single wall pipe is not allowed due to the high temperature of the a...

Page 20: ...ur hand up inside and underneath bend up at least two of the four tabs at the base of the starter section to hold it in place 6 Install the shut off damper in the B vent starter sec tion through the left side louvers The shut off damper enables the manual control of hot air flowing through the gravity vent pipe With the top left louver removed and the angular portion of the rod in hand insert the ...

Page 21: ...be run at a 0 clear ance to combustibles Warning If you are ducting out of the top of the fireplace and the backdraft damper is not installed the central heat ducting will become too hot for the surrounding com bustible materials Any substitute for any RSF kit will void all liability and warranty coverage by RSF Woodburning Fireplaces Installation 1 Remove the cover to the left on the top of the D...

Page 22: ... ducting rigid or flex Any other size will not work properly Use only metal ducting between the fireplace and the blower You may use plastic ducting after the blower provided the temperature rating of the ducting is at least 250 F Do not use plastic ducting in a chase 7 To install the blower for the FD HB6 blower only attach the noise reduction collars to either side of the blower using 1 2 self t...

Page 23: ...is is the most pop ular use of the central heat blower Do not install it in the room where the fireplace is installed We recommend an electrician wire the following There are yellow black and red wires coming out of the relay as shown in the wiring diagram Connect the wire from 4 of the terminal block to the yellow relay wire and the black transformer wire with a wire marrette Connect the black re...

Page 24: ...ading if it is tested with a meter 2 If the blower still fails to operate consult your local RSF Woodburning Fireplaces authorized dealer for repair or replacement instructions ZONE HEATING FD HCZ 1 AND FD HCZ 2 For more regional heat control the Delta is ideally suited for zone heating Figure 38 shows an example of a three zone system The thermostat simultaneously opens the desired valve and star...

Page 25: ...heat plenum for circulation throughout all rooms example 2 tie in to part of the duct system Figure 36 examples of air circulation when tying in to existing ducting zone dampers zone thermostats Figure 37 Zone heating example of 3 zones ...

Page 26: ...ft damper motor internal blower thermal switch terminal block draft damper thermostat internal blower speed control black white black bare 110V relay yellow white black external blower control external central heat blower 24V 18ga LVT white Figure 38 Wiring for all systems with zone heat system zone thermostats heat only transformer ...

Page 27: ...iring for the central system 110V draft damper motor draft damper thermostat internal bower speed control blower control thermostat variable speed switch external central heat blower 110V black black black white yellow 1 2 internal blower thermal switch bare white white 18 ga LVT transformer Figure 42 Wiring for all systems combined For a warming thermostat 1 should be the red wire and 2 should be...

Page 28: ...31B 14 14 7 Thermostat RSF T822D2501 14 14 9 Controller 00100201 14 14 10 Control Centre 001 00204 14 14 11 Electric Blower Speed Control 5 14 14 13 Electric Blower c w Thermal Switch 11 1 D Refractory Back Right 11 2 D Refractory Back Left 11 3 D Refractory Side Right 11 4 D Refractory Side Left 11 5 D Refractory Bottom Right 11 6 D Refractory Bottom Left 11 7 D Refractory Front Right 11 8 D Refr...

Page 29: ... OPERATE ONLY WITH VIEWING DOOR CLOSED AND LATCHED OPEN TO FEED FIRE ONLY FOR USE WITH SOLID WOOD FUELS ONLY OPERATE ONLY WITH FIREBRICK IN PLACE WARNOCK HERSEY 00000 UN PLANCHER COMBUSTIBLE DOIT ÊTRE PROTÉGÉ PAR UN MATÉRIAU NON COMBUSTIBLE S ÉTENDANT AU MOINS 16 405 MM AU DEVANT ET 8 205MM SUR LES CÔTÉS DE L OUVERTURE DE LA PORTE DU FOYER PIÈCES REQUISES POUR L INSTALLATION TUYAU FLEXIBLE DE 4 ou...

Page 30: ... components Repairs or replacements necessitated by vandalism neglect abuse over firing improper fuel or fuel loads or failure to ade quately service the unit as stated in the owner s manual Repairs or replacements particularly charges for travel and labor not authorized by RSF Woodburning Fireplaces in advance LIMITATIONS All items found to be defective will be replaced or repaired upon return of...

Reviews: