Alarm
Code
Abbreviation
Status / Alarm name
Description or proposed actions
32
STAK
Stack Overflow
Replace the electronics board by contacting the
manufacturer or manufacturer’s representative.
33
COMM
Communication Error
Count Limit
It is active if the HART related communication errors
exceed the setting. Check the cable connections or make
sure that the environment is susceptible to noise.
34
FCLC
Full Close Count Limit
It is active if the valve exceeds Full Close Count Limit.
35
FOPC
Full Open Count Limit
It is active if the valve exceeds Full Open Count Limit.
36
LPCH
Loop Current Hi Limit
It is active if the input current exceeds 20.5 mA.
37
LPCL
Loop Current Lo Limit
It is active if the input current falls below 3.8 mA.
38
DI0S
Digital Input Status
It is active when the digital input port has changed its
status.
39
DO0S
Digital Output Status
It is active when the digital output port has changed its
status.
40
DIGF
Diagnostics Failure
It indicates that the diagnosis test such as Large Step Test,
Normal Step Test, Small Step Test, Stroke Time Test and
Trace Test has failed.
145
VARA
Device Variable Alert
It is active when one of the internal variables are out of
range.
144
MNTR
Maintenance Required
It is active when more than one of alarms assigned to
“Maintenance Required” have happened. Remove the
cause of the alarm after checking it.
147
FAIL
Failure
It is active when more than one of alarms assigned to
“Failure” have happened. Remove the cause of the alarm
after checking it.
148
OUTS
Out of Specification
It
is active when more than one of alarms assigned to “Out
of Specification” have happened. Remove the cause of the
alarm after checking it.
149
FUNC
Function Check
It is active when more than one of alarms assigned to
“Functional Check” have happened. Remove the cause of
the alarm after checking it.