Smart Positioner
YT-3700 / 3750
Product Manual
Ver. 1.03
62
8.9.7
User Set Characterization 21 Points (U21)
A total of 21 target points can be set every 0.8 mA intervals. When shipped from the factory, the initial
P0 (4mA, 0%), P1 (4.8 mA, 5%), P2 (5.6 mA 10%), - - -, P19 (19.2 mA, 95%), and P20 (20 mA,
100%). For example, a characteristic curve below can be made through the settings of P1 to P20.
User can change all 21 points or only change partially and exit the menu by pressing <ESC> button.
3 seconds
Press <UP> or
<DOWN> button
if the above is not
displayed.
Press <UP> or
<DOWN> button
if the above is not
displayed.
<UP>/<DOWN>
or
<UP>/<DOWN>
or
To repeat with
identical way.
<UP>/<DOWN>
or
<UP>/<DOWN>
or
To automatically
move after
several seconds.
<ESC>
2 times
This function is activated by saving the Flow Rate Characteristics Setting Mode (CHAR) of above
Section 8.9
.5 as “U21”.