Smart Positioner
YT-3700 / 3750
Product Manual
Ver. 1.03
48
The Table below identifies the range and initial factory settings of each parameter for Menu Level 2
and Menu Level 3 where the menu hierarchy has been lowered by one level.
Level 2
Level 3
Range
Initial factory setting
View Monitoring
Counts [VI CNTS]
Cycle Count [CYCL CNT]
0 ~ 4,200,000,000
Accumulated Travel
[TVL ACUM]
0 ~ 168,000,000 [%]
Operating Count [OPER CNT]
0 ~ 4,200,000,000
Full Open Count [FOP CNT]
0 ~ 4,200,000,000
Full Close Count [FCL CNT]
0 ~ 4,200,000,000
LIMT CFG
Travel Hi Limit [TVL HI]
0 ~ 120 [%]
100 %
Travel Lo Limit [TVL LO]
-10 ~ 50 [%]
0 %
Temperature Hi Limit
[TEMP HI]
-57 ~ 85 [
℃
]
Sellecting
by
temp.
option
Temperature Lo Limit
[TEMP LO]
-57 ~ 85 [
℃
]
Sellecting
by
temp.
option
Deviation Time [dV TIME]
0 ~ 300 [sec]
60 sec
Deviation Deadband [dV db]
0 ~ 10 [%]
5 %
Travel Hi Limit Alarm Enable
[AL TVLH]
oFF, on
oFF
Travel Lo Limit Alarm Enable
[AL TVLL]
oFF, on
oFF
Temperature Hi Limit Alarm
Enable [AL TMPH]
oFF, on
oFF
Temperature Lo Limit Alarm
Enable [AL TMPL]
oFF, on
oFF
Deviation Time Out Alarm
Enable [AL dVTO]
oFF, on
oFF
PST CFG
PST Interval [INTERVAL]
1 ~ 365 [days]
365
PST Starting Position
[START PO]
0 ~ 100 [%]
100 %
PST Tolerance [TOL]
0.1 ~ 10 [%]
5 %
PST Target Position [TARGET]
0 ~ 100 [%]
90 %
PST Hold Time [HOLD TM]
1 ~ 300 [sec]
5 sec
PST Limit Time [LIMT TM]
1 ~ 200 [sec]
10 sec
PST Ramp Up Rate
[PRAMP UP]
oFF, 1 ~ 100 [%/sec]
oFF
PST Ramp Down Rate
[PRAMP dN]
oFF, 1 ~ 100 [%/sec]
oFF
PST Time Remaining
[NEXT PST]
oFF,
1 ~ 365[days],
0 ~ 24[hour]
oFF