Smart Positioner
YT-3700 / 3750
Product Manual
Ver. 1.03
59
8.9.2
Split Range Mode (SPLIT)
This is used to set the range of the input signal to control the entire stroke of the valve. You can
select one of the four input signals that consists of 4-20 mA, 4-12 mA, 12-20 mA, and user settings
(Custom, CSt). 4-20 mA is the factory setting.
3 seconds
Press <UP> or
<DOWN> button
if the above is not
displayed.
Press <UP> or
<DOWN> button
if the above is not
displayed.
<UP>/<DOWN>
<ESC>
3 times
4~20mA Control
(Initial condition)
4~12mA Control
8.9.3
Custom Split Range Zero (CST ZERO)
It is used to set the current corresponding to the zeropoint when the valve position of 0 to 100% is
controlled by the user-set CUSTOM. For example, if the valve is controlled by 6-20 mA instead of 4-
20 mA, CST ZERO is 6 mA. However, the difference of the current between the origin point and the
endpoint must be greater than 4 mA.
3 seconds
Press <UP> or
<DOWN> button
if the above is not
displayed.
Press <UP> or
<DOWN> button
if the above is not
displayed.
<UP>/<DOWN>
<ESC>
3 times
This function is activated by saving the Split Range Mode (SPLIT) of above Section 8.9.2 as
“CSt”.