Valve Actions
From the lower tool bar menu select
Valve Actions
.
The following settings are available:
Open/Close Torque
Maximum allowed output torque can be varied between
40% to 100% of rated in both Open and Close directions.
The torque is displayed in lb.in or Nm.
MOV Tag
Modify as required.
Shaft Action
Clock or Anticlock to close (Clock is Default).
Close / Open Stop
Set the end of travel stop function for Torque or Limit to suit
the characteristics of the valve.
Torque
The actuator can be set to apply its selected output ‘Torque’
to the valve at the end of travel where tight shut off is
required.
Limit
Alternatively it can be set to the ‘Limit’ function to disengage
motor drive, where the valve does not require the seating
force to be applied.
Send Settings
Send modified settings to the actuator.
Fig. 39.2
Fig. 39.1