12
Installation & Setup Guide
Commissioning
The Rotork CVA Range of actuators provide simple, safe
and rapid non-intrusive commissioning using a Bluetooth
enabled PDA. Actuator limit setting can be achieved using the
Automatic setup feature.
Tools & Equipment Required
Bluetooth enabled hand held computer (PDA) or Smartphone
(screen resolution 240 x 320 minimum) running Windows
Mobile operating system.
Note: Local operation is only possible with a PDA or
Smartphone. Alternatively if the HART option card is
fitted a Hart communicator can be used.
Software
The Rotork Enlight CVA software must be installed
on the PDA or Smartphone before carrying out any
commissioning procedures.
The software is free and is available for download from
the Rotork website at www.rotork.com.
CAUTION
It is essential that the setup procedure is carried
out when the valve is not under working process
conditions, as full valve movement will occur.
If actuators are fitted with a failsafe capacitor pack
the unit may operate the valve on removal of the
power supply.
To prevent this occurrence, it will be necessary to
reconfigure the failsafe action, see page 39.
Alternatively ‘STOP’ can be selected to
prevent unwanted movement.
IMPORTANT
It is essential that the actuator is mounted correctly to
the valve.
The Installation & Setup will include the following procedures:
1. Prepare the Drive Bush.
2. Ensure Valve position is noted and safe (Offline).
3. Mount and align actuator to valve.
4. Adjust Mechanical stops.
5. Use of PDA to set limits of travel.
6. Use of PDA to configure control and
indication parameters.