Initial start-up
If several control units are incorporated in the RoCon system of a
heating installation, additional parameter settings are relevant for
this and can be used to set the individual functions and parame-
ters using the appropriate authorisations.
For the RoCon U1 room station
– [RoCon U1 assign] parameter:
– The setting = "Living Room" can be used to influence the
heating circuit defined by the set heating circuit ID.
– The setting = "Mixing Valve" can be used to carry out all
the settings for the mixer circuit defined by the set heating
circuit ID.
– [Master-RoCon] parameter:
If the heating circuit ID is set for the direct heating circuit of a
ROTEX HPSU monobloc compact, the setting = "On" can be
used to activate the master RoCon function. In addition to the
heating circuit functions, the hot water functions of the
ROTEX HPSU monobloc compact can also be operated with
this room station.
Activation of the master RoCon function can also be used for
heating systems that consist only of a ROTEXHPSU mono-
bloc compact (without heating circuit extension) and a room
station, and which are to be operated primarily via the room
station (observe following information).
On heating systems with heating circuit extensions, we rec-
ommend not activating the master RoCon function (setting =
"Off") and instead using the terminal function.
For all RoCon B1 and RoCon U1 control units
– [Terminaladress] parameter:
As soon as a control panel has been assigned with a terminal
ID (all settings except "Off"), the control panel can be used to
activate the terminal function.
After carrying out the [Bus - Scan], all the system components
integrated in the RoCon system can be remotely controlled
using a valid device ID (caretaker authorisation).
If the terminal function is to be used in the heating system, the
terminal ID = 0 must be allocated to a control unit.
4.2
Operating Support during 1st.
Commissioning and during System
Extensions
When a ROTEX HPSU monobloc compact or a RoCon U1 room
station is switched on for the first time, setting the user language
is normally offered first.
Then, on the ROTEX HPSU monobloc compact you will be asked
"Use Standard Config?". This query can normally be answered
with "Yes".
Only in special applications (e.g. several heat generators in the
RoCon system) should the answer be "No". In this case, the
"Basic Configuration"
parameter level will be offered in order to
set the necessary adaptations (see tab. 6-14).
In the case of the RoCon U1 room station, after setting the user
language, the
"Setup Wizard"
installation menu appears.
The items for defining the function, the authorisation and the IDs
of the room station in the RoCon system are requested and
checked for plausibility.
This prevents duplicate device and terminal IDs being set.
Therefore, it is recommended that you use this installation menu
when extending or making changes to the RoCon system of the
heating installation. To do this, a room station already integrated
in the heating installation must first be reset.
1. Enter the technician code (see chap. 3.6.1).
2. Push the Exit button for at least 5 s.
Menu
"Special Level"
is displayed.
3. Use the rotary button to select the
"RoCon B1/U1 Reset"
program.
4. Execute the program by briefly pressing on the rotary button.
The
"Setup Wizard"
installation menu starts.
Device ID
Unique numbering of a heat genera-
tor or mixer module in the RoCon sys-
tem.
Up to 16 device numbers can be allo-
cated.
These device numbers are detected
during a [Bus - Scan] and are dis-
played for identification of a remotely
controlled device.
ROTEX HPSU monobloc
compact
(RoCon BM1)
[BUS ID HS]
Identical to heat generator detection.
The value must not be the same as the
heating circuit ID of a mixer module in the
RoCon system.
RoCon M1 mixer module
[HC Assignment]
Identical to the heating circuit ID.
The value must not be the same as the
heat generator ID of a ROTEX HPSU
monobloc compact in the RoCon system.
The value must be the same as the setting
of the address switch (fig. 4-2).
Tab. 4-1 Functional IDs in the RoCon system
1)
A maximum of 8 heat generators can be connected in the RoCon system via the CAN data bus. Several heat generators integrated in the heating installation must
be regarded as a special application. If necessary contact a ROTEX service technician.
ID / Function
System components
Parameters
Comments
If the master RoCon function is activated, the oper-
ating mode of the heat generator is set via the room
station, and this is shown on the display.
The settings on the room station are transferred to the heat
generator, but not vice versa. The room station has priority.
If the [Summer] operating mode is set, for example, and sub-
sequently, on the ROTEX HPSU monobloc compact control
panel, the [Heating] operating mode is set, no heating circuit
requirement is generated, because the direct heating circuit
assigned to the room station via the heating circuit ID is still
in [Summer] operating mode. The change in operating mode
must therefore be carried out at the room station.
Fig. 4-1
"Setup Wizard" display
Setup Wizard