Parameter settings
FA ROTEX RoCon mb • 09/2017
43
Terminaladress
Setting of the terminal ID of the control unit for system access. The set value must be
unique throughout the entire system. Confirmation of this parameter with the rotary but-
ton effects new initialisation of the control unit.
All settings except for "Off" authorise the user of the control unit to activate the terminal
function and thus to operate all RoCon system components with a valid device ID (see
chap. 3.4.9 and 4.1).
N
E
Off, 0 - 9
Off
1
System Config
System configuration of the device, consisting of sensor configuration and data bus con-
figuration. If the prompt regarding use of the standard configuration is answered "Yes"
when the device is first started, the basic configuration appropriate to the installed heat
generator is automatically activated.
Confirmation of this parameter with the rotary button when "Inactive" or "Delete" is set
leads to re-initialisation of the controller. An error message follows. The rotary switch
must then be set to
"Info"
. Use the rotary button to operate the displayed menu guidance.
N
E
Inactive
Active
Delete
Active
-
HC Assignment
Display only on connected
room station:
Setting of the heating circuit ID for the room station (see chap. 4.1). This parameter de-
termines which heating circuit should be operated with this value.
The direct heating circuit of the ROTEX HPSU monobloc compact is set to heating circuit
ID "0" as standard (see chap. 6.12, parameter [Unmixed Circ Config]).
N
E
Off, 0 - 15
Off
1
Tab. 6-1 Parameters in the "Configuration" rotary switch setting, "Setup" level
Su
b-
le
ve
l
Parameters
Description
Access
Setting range
Min / Max
Factory
setting
Incre-
ment
BE
HF