48
FA ROTEX RoCon mb • 09/2017
6
x
Parameter settings
6.4
Rotary switch setting: Operating Mode
6.5
Rotary switch setting: Set Temp Day
6.6
Rotary switch setting: Set Temp Night
6.7
Rotary switch setting: DHW Set Temp
Parameters
Name
Access
Setting range
Min / Max
Factory
setting
Incre-
ment
BE
HF
Standby
In this operating mode all internal functions are switched off. Frost protection remains active
and a blocking protection for the pump is guaranteed.
All controllers integrated in the RoCon system via the CAN data bus are also primarily switched
to this operating mode on selection of this setting.
Outputs are not always completely free of voltage.
E
E
-
Reducing
The internal heating circuit is continuously controlled (24 h per day) to the set setback temper-
ature. Hot water generation is carried out according to [DHW Program 1].
E
E
-
Heating
The internal heating circuit is continuously (24 h per day) regulated to the set day target room
temperature (heating). Hot water generation is carried out according to [DHW Program 1].
E
E
-
Cooling
The internal heating circuit is continuously (24 h per day) regulated to the set day target room
temperature (cooling). Hot water generation is carried out according to [DHW Program 1].
Frost protection remains active and a blocking protection for the pump is guaranteed.
E
E
-
Summer
The internal heating circuit is switched off. Frost protection remains active and a blocking pro-
tection for the pump is guaranteed. Hot water generation is carried out according to [DHW Pro-
gram 1].
All controllers integrated in the RoCon system via the CAN data bus are also primarily switched
to this operating mode on selection of this setting.
E
E
-
Automatic 1
The internal heating circuits regulate according to the set time program [HC Program 1] with
the respective target room temperature. Hot water generation is carried out according to [DHW
Program 1].
E
E
-
Automatic 2
The internal heating circuits regulate according to the set time program [HC Program 2] with
the respective target room temperature. Hot water generation is carried out according to [DHW
Program 2].
E
E
-
Tab. 6-6 Parameters in the "Operating Mode" rotary switch setting
Parameters
Name
Access
Setting range
Min / Max
Factory
setting
Incre-
ment
BE
HF
T-Room 1 Setpoint
Target room temperature for the 1st switching time cycle of the time programs [Automatic 1]
and [Automatic 2].
E
E
5 - 40 °C
20 °C
0.5 °C
T-Room 2 Setpoint
Target room temperature for the 2nd switching time cycle of the time programs [Automatic 1]
and [Automatic 2].
E
E
5 - 40 °C
20 °C
0.5 °C
T-Room 3 Setpoint
Target room temperature for the 3rd switching time cycle of the time programs [Automatic 1]
and [Automatic 2].
E
E
5 - 40 °C
20 °C
0.5 °C
Tab. 6-7 Parameters in the "Set Temp Day" rotary switch setting
Parameters
Name
Access
Setting range
Min / Max
Factory
setting
Incre-
ment
BE
HF
T-Reduced
Target room temperature valid for the reduction times of the permanent time programs [Auto-
matic 1] and [Automatic 2].
E
E
5 - 40 °C
15 °C
0.5 °C
T-Absence
Target room temperature for the reduction times of the temporary time programs [Away] + [Va-
cation].
E
E
5 - 40 °C
15 °C
0.5 °C
Tab. 6-8 Parameters in the "Set Temp Night" rotary switch setting
Parameters
Name
Access
Setting range
Min / Max
Factory
setting
Incre-
ment
BE
HF
T-DHW Setpoint 1
Target hot water temperature for the 1st switching time cycle of the time programs [Automatic
1] and [Automatic 2].
E
E
35 - 70 °C
48 °C
1 °C
T-DHW Setpoint 2
Target hot water temperature for the 2nd switching time cycle of the time programs [Automatic
1] and [Automatic 2].
E
E
35 - 70 °C
48 °C
1 °C
T-DHW Setpoint 3
Target hot water temperature for the 3rd switching time cycle of the time programs [Automatic
1] and [Automatic 2].
E
E
35 - 70 °C
48 °C
1 °C
Tab. 6-9 Parameters in the "DHW Set Temp" rotary switch setting