6
x
Parameter settings
FA ROTEX RoCon mb • 09/2017
41
Glycol
Adding glycol to the water circuit is recommended to guarantee frost protection in the
event of a power failure. If glycol has been added to the system, the RoCon controller
setting must be adapted accordingly.
0: no glycol added
1: glycol added
S
E
0 - 1
0
-
HP Version
Version of the HPSU internal unit
5: version 5
N
E
5
5
-
Function Heating
Rod
Setting regarding whether an additional heat generator (WEZ) for hot water preparation
and heating support is available (see chap. 3.6.7).
0: no additional WEZ
1: optional backup heater
2: alternative WEZ undertakes hot water preparation and heating support
3: alternative WEZ 1 undertakes hot water preparation and alternative WEZ 2 under-
takes heating support
N
E
0 - 3
1
1
Emergency BUH
If the heat pump fails, the backup heater can be used as emergency heating, and can
undertake all heating requirements either automatically or non-automatically.
0: no automatic emergency operation
1: automatic emergency operation
E
E
0 - 1
0
-
HZU
Heating support from hot water storage tank if minimum temperature is exceeded (see
chap. 3.6.8 and parameter [TDiff-DHW CH Support]).
Off: no heating support
On: heating support function active
N
E
Off
On
On
-
Equilibrium Func.
The bi-valence function is only relevant to operation of the optional heater booster due
to a backup requirement (room heating mode).
Off: operation of the backup heater is always possible.
On: backup heater is only released if the temperature set in the parameter [Equilibrium
Temp] is undershot.
N
E
Off
On
On
-
SMART GRID
Evaluation of the SG signal (see chap. 3.4.12).
0: Smart Grid function not active, SG signal is not evaluated.
1: depending on utility company signal, the heat pump is shut off (no frost protection func-
tion - see chap. 3.6.5) or operated at higher temperatures.
N
E
0 - 1
0
-
Mode SG
Only if [SMART GRID] parameter = 1:
Used for a possible increase in the target temperature in the case of a Smart Grid switch-
on command.
0: comfort (target hot water temperature increase by 5 K)
1: standard (target feed temperature increase by 2 K and target hot water temperature
increase by 5 K)
2: eco (target feed temperature increase by 5 K and target hot water temperature in-
crease by 7 K)
N
E
0 - 2
1
1
HT/NT Function
Setting regarding which heat sources are switched off if the peak signal output by the util-
ity company (EVU) is received in the case of an off-peak mains connection.
0: deactivated (no effect)
1: refrigerant compressor is switched off
2: refrigerant compressor and backup heater are switched off
3: everything is switched off (no frost protection function - see chap. 3.6.5)
N
E
0 - 3
0
1
HT/NT Contact
Definition of whether the HT/NT input is evaluated as a normally closed contact or a nor-
mally open contact.
0: normally open contact (switching contact closed = peak)
1: normally closed contact (switching contact closed = off-peak)
N
E
0 - 1
0
-
Room thermostat
Configuration of a room thermostat with potential-free contacts connected to ROTEX
HPSU monobloc compact connection J16.
–
Off: Deactivated
–
On: (only if parameter [Interlink fct] = Off)
Evaluation of the heating
and cooling
switching contacts at plug connection
J16 on the RoCon BM1 printed circuit board (only if none of the "Standby", "Reduc-
ing", "Summer", "Vacation", "Holiday" or "Screed" operating modes are active):
a)
Closed heating
switching contact: operating mode is switched to "Heating".
Priority if both switching contacts are closed.
b)
Closed cooling
switching contact: operating mode is switched to "Cooling".
c)
Open contacts: only frost protection active.
N
E
Off
On
Off
-
Su
b-
le
ve
l
Parameters
Description
Access
Setting range
Min / Max
Factory
setting
Incre-
ment
BE
HF