Initial start-up
FA ROTEX RoCon mb • 09/2017
33
4.3
Commissioning ROTEX HPSU monobloc
compact
The prerequisite for initial commissioning is the completion of all
preparatory installation work as per the installation and mainte-
nance instructions for the.ROTEXHPSU monobloc compact
●
Switch on the power supply to the ROTEX HPSU monobloc
compact.
After the start phase, the operating language selection is
displayed.
●
Use the rotary button to select the desired language.
●
Confirm the selection with a brief push of the rotary button.
The "Use Standard Config?" message is displayed.
●
Confirm the default "Yes" by briefly pressing on the rotary
button (see also chap. 4.2).
The Basic Configuration of the RoCon device is loaded.
The "Starting Up" message is displayed.
The "Initialization" message is displayed.
The standard display for the current rotary switch setting
is shown.
●
Adjust settings related to the configuration of the heating
system on the RoCon device (see chap. 3.6).
4.3.1 Assigning the terminal ID on the RoCon B1
control panel of the ROTEX HPSU monobloc
compact
●
Enter the technician code (see chap. 3.6.1).
After entering, the
"Setup"
level is displayed.
●
Use the rotary button to select the [Terminaladress]
parameter.
●
Confirm the selection with a brief push of the rotary button.
●
Within the display, use the rotary button to set the unique
terminal address.
For reasons of clarity, this control unit must be assigned the
value = 0.
●
Confirm the selection with a brief push of the rotary button.
Change has been accepted. Jump back to previous dis-
play.
Detailed explanations and possible setting values for this rotary switch setting can
be found in chap. 6.2.1.
4.4
Putting optional RoCon system components
into operation
4.4.1
Mixer module RoCon M1
The
RoCon M1
mixer module (
15 70 68
) has no separate
control unit. For configuration and operation, it must be con-
nected via a CAN bus line to a RoCon controller installed in the
heat generator or a RoCon U1 room station(
15 70 34).
After selection and confirming an external device, the terminal
function for this device is activated and the associated standard
display for this device is shown in the display.
The operating component is then in terminal operation.
In the rotary switch position
, the local control panel acts as
a remote control for the external device. In this case, all the con-
trol functions are performed and saved 1:1 as on the external
device.
For reasons of clarity, this control unit must be assigned the value
= 0.
A unique device ID (
≥
1) must be set on the address switch (see
fig. 4-2) for the heating circuit to be controlled by this mixer mod-
ule, which must be synchronised with the [HC Assignment]
parameter of the mixer module (see tab. 4-1]).
All settings and operating steps for this heating circuit are per-
formed in the same way as those for the direct heating circuit.
The overview of the available parameters and their settings can
be found in chap. 6.13.
The current operating status can be determined directly on the
RoCon M1 mixer module (see fig. 4-3).
The operating language can be changed again at
any time.
If several control units are connected in the RoCon
system via the data bus, it is important to note that the
[Terminaladress] parameter = 0 must be set for a heat
generator.
Make sure not to assign a duplicate value as the setting of the
[Terminaladress] in the RoCon system.
In conjunction with a room station, the mixer module
can also be operated as a free-standing heating circuit
controller.
To operate the mixer module directly via the RoCon B1 control
panel of the ROTEX HPSU monobloc compact, it must be
assigned with a terminal ID, and the terminal function must be
activated (see chap. 3.4.9).
If, in the rotary switch position
, the message
"n.A." is displayed, no valid terminal ID has been
assigned to this RoCon B1 control panel yet.
If the "n.A." message is still displayed, it may be necessary to
update the device software in order to use the terminal function.
Contact the ROTEX Service Team for this.
Fig. 4-2
Setting the device ID for the RoCon M1 mixer module