30
BA ROTEX HPSU compact 4 - 09/2013
6
x
Parameter settings
6.2.2 Level "System Configuration"
Parameter
Description
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
Equilibrium Temp
Outdoor temperature from which the optional ancillary heating is activated for supporting the
room heating. The bivalent temperature is relevant for operation of the optional ancillary heater
based on a backup demand (room heating operation). We use the integrated temperature sen-
sor on the external unit of the heat pump (different from the one shown in the display).
E
E
-15 - 35°C
0 °C
1 °C
Quite Mode
Mode for low-noise operation: Two modes are available. In certain cases, whisper mode can
become apparent through reduced performance.
Off: Deactivated
On: Activated
Interval: Operated in whisper mode only at night between 22:00 and 5:00 hours.
E
E
Off,
On,
Interval
Off
-
Sensor Test
In this context menu we can manually call up measured values of the individual sensors. These
can deviate from the displayed values in the other menu levels since here we show the current
unfiltered measured values. In the individual menu levels, on the other hand, we show the fil-
tered measured values relevant for the Controller.
Sensor 1: EVU contact,
mixer circuit flow temperature sensor
Sensor 2: Outside temperature sensor
Sensor 3: SMART GRID-input
Sensor 4: Storage tank temperature sensor
Sensor 5: Temperature sensor for the flow sensor
Sensor 6: Pressure sensor
S
S
Sensor 1
-
Sensor 6
-
-
Tab. 6-2
Parameter in rotary switch setting "Configuration", level "System Configuration"
Depending on the version of the device software certain
information parameters for the device, not described in
tab. 6-2, can be displayed at this level. For this see
tab. 6-12.
6.2.3 Level "HC Configuration"
Sub-
leve
l
Parameter
Description
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
Operating Mode
Setting the operating mode of the internal heating circuit.
If the rotary switch for the Control is set to "- - - -" it applies to the control of this heating
circuit.
When the operating modes "Readiness" and "Summer time" are set at the rotary switch
on the controller of the Control (control element RoCon B1 or room temperature control-
ler RoCon U1 with activated terminal function), this has a reducing effect on all heating
circuits and consumer circuits in the entire system.
E
E
- - - -
Standby
Reducing
heating
Cooling
Summer
Automatic 1
Automatic 2
- - - -
1
T-Frost Protect
Off: No frost protection of the heating circuit
Otherwise: If the outside temperature falls below the programmed value, the system
switches into the frost protection mode (switches the pumps on). The function ceases
once the outside temperature has risen to the set value +1 K.
E
E
Off,
-15 - 0°C
0 °C
1 °C
Insulation
Setting the insulation standard of the building. This affects the way the heating curve and
the heating times automatically adapt to the outside temperature.
E
E
Off
Low
Normal
Good
Very Good
Normal
-