34
BA ROTEX HPSU compact 4 - 09/2013
6
x
Parameter settings
6.8 Rotary switch setting: Time Program
Parameter
Designation
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
Party
With this operating mode we can set a one-off time for the temporary heating time extension
of the internal heating circuit.
E
E
00:00 - 06:00
00:00
1 h
Away
With this operating mode we can set a one-off time for the temporary regulation to the param-
eterised absence temperature.
E
E
00:00 - 06:00
00:00
1 h
Vacation
The internal heating circuit provides continuous (24 h per day) regulation to the parameterised
absence temperature (parameter T-Reduced).
A calendar function can be used to enter a time period for the absence.
E
E
Date on first
day
-
Date on last
day
-
1 Day
Holiday
A calendar function can be used to enter a time period for presence.
E
E
Date on first
day
-
Date on last
day
-
1 Day
HC Program 1
In this menu we can parameterise the 1st timer programme for the internal heating circuit.
3 switching cycles with a resolution of 15 minutes can be set. A separate entry for each week-
day is possible. Format: (on) hh:mm - hh:mm (off)
Also, the cycles can be parameterised from Monday to Friday, Saturday to Sunday and Mon-
day to Sunday.
E
E
See
chapter 3.4.7
See
15 min
HC Program 2
In this menu we can parameterise the 2nd timer programme for the internal heating circuit.
3 switching cycles with a resolution of 15 minutes can be set. A separate entry for each week-
day is possible. Format: (on) hh:mm - hh:mm (off)
Also, the cycles can be parameterised from Monday to Friday, Saturday to Sunday and Mon-
day to Sunday.
E
E
See
chapter 3.4.7
See
15 min
DHW Program 1
In this menu we can parameterise the 1st timer programme for hot water generation. 3 switch-
ing cycles with a resolution of 15 minutes can be set. A separate entry for each weekday is
possible. Format: (on) hh:mm - hh:mm (off)
Also, the cycles can be parameterised from Monday to Friday, Saturday to Sunday and Mon-
day to Sunday.
E
E
See
chapter 3.4.7
See
15 min
DHW Program 2
In this menu we can parameterise the 2nd timer programme for hot water generation. 3 switch-
ing cycles with a resolution of 15 minutes can be set. A separate entry for each weekday is
possible. Format: (on) hh:mm - hh:mm (off)
Also, the cycles can be parameterised from Monday to Friday, Saturday to Sunday and Mon-
day to Sunday.
E
E
See
chapter 3.4.7
See
15 min
Circulation Time
In this menu we can parameterise a timer programme for the circulation pump. 3 switching cy-
cles with a resolution of 15 minutes can be set. A separate entry for each weekday is possible.
Format: (on) hh:mm - hh:mm (off)
Also, the cycles can be parameterised from Monday to Friday, Saturday to Sunday and Mon-
day to Sunday.
E
E
See
chapter 3.4.7
See
15 min
Tab. 6-10
Parameter in rotary switch setting "Time Program"
6.9 Rotary switch setting: Remote Param
Parameter
Description
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
Bus - Scan
Off: No function
On: Control checks which RoCon devices are connected to the system using the CAN bus
lines. Devices that are detected are displayed with their type and data bus ID
(For example: MM#8 = Mixer module with bus ID 8).
The selection and activation of a device with the rotary switch switches the function of the
control unit to that of the selected device (see chapter 3.4.9).
E
E
Off
On
Off
-
No selection
Activation switches to the local device.
E
E
-
Contr BM1/BE1 #X
Activation switches to the HPSU compact with the bus ID X.
E
E
-
Mix Valve #X
Activation switches to the mixer module with the bus ID X (see section 6.12.1, parameter
[HC Assignment]).
E
E
-
Tab. 6-11
Parameter in rotary switch setting "Remote Param"
Summary of Contents for HPSU compact 304
Page 52: ...52 BA ROTEX HPSU compact 4 09 2013 10 x Notes 10 2 Other notes...
Page 53: ...10 x Notes BA ROTEX HPSU compact 4 09 2013 53...
Page 54: ...54 BA ROTEX HPSU compact 4 09 2013 10 x Notes...
Page 56: ...ROTEX BA ROTEX HPSU compact 4 Subject to change and correction 008 1414644_01 09 2013...