6
x
Parameter settings
BA ROTEX HPSU compact 4 - 09/2013
31
heating
T-Outside lim day
Only if parameter [Pump Mode] = 1:
Setting the automatic summer shutdown of the heating system. If the outside tempera-
ture measured and averaged out by the controller exceeds the set value by 1 K, the heat-
ing circuit is switched off. The heating is released again if the outdoor temperature falls
below the set heat curve.
E
E
Off, 10 - 40 °C
19 °C
0.5 K
T-Outside lim night
Only if parameter [Pump Mode] = 1:
Parameter for setting the heating limit for "Switch-off" of the heating circuit during setback
time (functionality as for parameter [T-Outside lim day]).
E
E
Off, 10 - 40 °C
10 °C
0.5 K
Heat-Slope
Only if parameter [HC Function] = 0:
Setting the heating curve. The heating curve reflects the dependence of the set inflow
temperature of the heating circuit on the outside temperature (see chapter 3.6.2).
E
E
0.0 - 3.0
0.7
0.1
Room Influence
Only if the room temperature controller
is connected and assigned to the heating
circuit:
Setting of the impact the deviation of the room temperature measured by the RoCon U1
from the actual set value (see chapters 3.4.3 and 3.4.4) has on the flow temperature.
Off : Purely weather-controlled flow temperature regulation, but internal heat recircula-
tion pump continues to run until the next heating cycle following a heat demand during
the setback time.
1-20: Causes a correction of the set flow temperature (parallel shift of the heat curve) by
the set factor. If the measured temperature is 2 K below the set value, the set flow
temperature is raised 2-times the set value.
E
E
Off, 1 - 20 K
Off
1 K
T-Room Adj
Only if the room temperature controller
is connected and assigned to the heating
circuit:
Individual adaptation of the room temperature relevant for control.
Should a systematic deviation of the room temperature, measured by the RoCon U1,
from the actual temperature in the living area of this room be detected, the measured
value can be corrected by the set value.
E
E
-5 - 5 K
0.0 K
1 K
Heat Up Opt
Heating up optimisation is a function for automatic bringing forward of the start of heating.
Off : Deactivated
1: Weather-controlled bringing forward
2: Room-temperature-controlled bringing forward (only if the room temperature controller
is connected and assigned to the heating circuit.)
E
E
Off, 1, 2
Off
1
Max Operation Time When heating-up optimisation is activated the start of heating is brought forward by a
maximum of the time set for this parameter (format hh:mm).
E
E
00:15 - 03:00
02:00
15 min
Opt Reduced
Function for preventing the HPSU compact starting up shortly before the end of the
parameterised heating time (format hh:mm).
E
E
00:00 - 02 :00
00:00
15 min
T-Flow Day
Only if parameter [HC Function] = 1
Setting the inflow target temperature for the heating circuit during the heating time when
in operating mode: "Automatic 1", "Automatic 2", "heating". "Cooling"
E
E
20 - 110°C
40 °C
1 °C
T-Flow Night
Only if parameter [HC Function] = 1
Setting the inflow target temperature for the heating circuit during the setback time when
in operating mode: "Automatic 1", "Automatic 2", "Reducing".
E
E
10 - 110°C
10 °C
1 °C
Cooling
Start T-Out Cooling This parameter is used to determine from which outdoor temperature the cooling mode
starts (Setting condition: Operating mode cooling).
E
E
20 - 45°C
24 °C
1 K
Max T-Out Cooling
This parameter is used to determine from which outdoor temperature the lowest cooling
flow temperature [T-Flow cooling start] or the highest set room value
[T-Room max cooling] is stipulated (Setting condition: Operating mode cooling).
E
E
20 - 45°C
35 °C
1 K
T-Flow cooling start This parameter is used to determine which flow temperature is stipulated at the start of
the cooling (outside temperature = parameter [Start T-Out Cooling])
(Setting condition: Parameter [Cooling] = ON).
E
E
5 - 25°C
18 °C
1 K
T-Flow cooling max This parameter is used to determine which flow temperature is stipulated at maximum
cooling (outside temperature = parameter [T-Flow cooling max])
(Setting condition: Operating mode cooling).
E
E
5 - 25°C
8 °C
1 K
T-Flow Cooling
Value of set flow temperature in cooling mode when regulating according to a fixed flow
temperature.
E
E
8 - 30°C
18 °C
1 K
T-Room start cool-
ing
This parameter is used to determine to which set room temperature the cooling regulates
at outdoor temperature = [Start T-Out Cooling].
E
E
15 - 40°C
24 °C
0.5 K
T-Room max cool-
ing
This parameter is used to determine to which set room temperature the cooling regulates
at outdoor temperature = Parameter [Max T-Out Cooling].
E
E
15 - 40°C
28 °C
0.5 K
Cooling Setpoint Adj This parameter can be used for a parallel displacement of the set cooling characteristic
line (Condition: Operating mode cooling).
E
E
-5 - 5°C
0 °C
1 K
Room Factor Cool-
ing
This parameter can be used to adapt the room sensor in cooling mode
(Condition: Operating mode cooling).
E
E
-5 - 5°C
0 °C
1 K
Tab. 6-3
Parameter in rotary switch setting "Configuration", level "HC Configuration"
Sub-
le
vel
Parameter
Description
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
Summary of Contents for HPSU compact 304
Page 52: ...52 BA ROTEX HPSU compact 4 09 2013 10 x Notes 10 2 Other notes...
Page 53: ...10 x Notes BA ROTEX HPSU compact 4 09 2013 53...
Page 54: ...54 BA ROTEX HPSU compact 4 09 2013 10 x Notes...
Page 56: ...ROTEX BA ROTEX HPSU compact 4 Subject to change and correction 008 1414644_01 09 2013...