16
BA ROTEX HPSU compact 4 - 09/2013
3
x
Operation
3.4.2 Setting the operating mode
The selection of the operating mode with which the ROTEX
HPSU compact is to operate is undertaken on the rotary switch in
the setting
"Operating Mode"
..
The selected operating mode is activated by briefly pushing the
rotary switch.
Operating Mode
Standby
Reducing
Operating Mode
heating
Cooling
Summer
Operating Mode
Summer
Automatic 1
Automatic 2
Operating Mode
Summer
Automatic 1
Automatic 2
Fig. 3-7
Changing over the operating mode
(e.g.: From "Standby" to "Automatic 1")
●
Place the rotary switch in the
"Operating Mode"
position.
An overview is displayed.
●
Select the desired operating mode with the rotary switch.
●
Confirm the changes with a brief push of the rotary switch.
ROTEX HPSU compact operates in accordance with the
set operating mode.
The current operating mode is indicated by an appropriate
symbol in the standard display.
Operating mode Standby (Stand-by)
CAUTION!
A heating system that is not frost-protected can freeze
in cold weather and be damaged.
●
Drain the water out of the heating system if there is
a danger of frost.
●
If the heating system is not drained, the power
supply must be ensured and the main switch must
remain switched on if there is a danger of frost.
In this mode, the ROTEX HPSU compact is shifted to the stand-
by mode. The frost-protection function remains in place. In order
to maintain this function, the system must not be disconnected
from the mains!
If the outdoor temperature is below the parameter value [T-Frost
Protect] the integrated heating circulation pump is switched on in
order to prevent the heating system from freezing.
All controllers integrated into the RoCon-system via the CAN bus
are also switched at a higher level to the operating mode
"Standby".
Fig. 3-8
Standard display in operating mode [Standby]
(above the frost protection limit)
In the operating mode [Standby] the heat pump and any
optionally connected internal electric heater are iso-
lated from the power supply (energy efficiency) when
the following conditions are met:
– The outdoor temperature sensor (RoCon OT1,
15 60 70) is connected and correctly parame-
terised in the system configuration,
– the outdoor temperature is over 8 °C,
– there is no heating command,
– the frost protection function is not active in any of
the connected heating circuits, and
– ROTEX HPSU compact has been switched on for at
least 5 mins.
Operating mode Reducing
Reduced heating mode (lower set room temperature) in
accordance with the set back temperature set in the parameter
[T-Reduced] (see section 3.4.4).
Hot water generation according to the set temperatures and
switching cycles in the hot water time programme
[DHW Program 1] (see section 3.4.5).
Operating modes heating, Cooling
Heating or cooling operation in accordance with the room
temperature set in the parameter [T-Room 1 Setpoint]
(see section 3.4.3). A connected outdoor temperature sensor
(weather-controlled flow temperature regulation) or a connected
room station will also influence the set flow temperature regu-
lation.
Hot water generation according to the set temperatures and
switching cycles in the hot water time programme
[DHW Program 1] (see section 3.4.5).
Operating mode Summer
Hot water generation according to the set temperatures and
switching cycles in the hot water time programme
[DHW Program 1] (see section 3.4.5).
All controllers integrated into the RoCon-system via the CAN bus
are also switched at a higher level to the operating mode
"Summer".
Operating mode Automatic 1 (Timer programme)
Automatic heating and economy mode in accordance with the
permanent timer programmes (see section 3.4.7):
– [HC Program 1]
– [DHW Program 1]