23

Operation Indications

During  normal  operation,  the  controller’s  display  will  indicate
current operating conditions and status.

Power-up Display

When  the  controller  powers  up,  dashes  will  show  on  the
display  for  one  second,  then  the  firmware  version  number  will
be displayed for one second.
Exiting  programming  restarts  the  controller.  The  power -up
display will show upon the restart.

Idle Condition

While  the  controller  is  idling,  waiting  for  a  command,  the
display will show circulation dashes.

Last Gate Position/Condition

When the gate moves or stops, the display will show the status
for up to one minute.

Stop is displayed as

St

Full Close is displayed as

FC

Full Open is displayed as

FO

Entrapment is displayed as

Et

Pre-Start Delay

During  the  pre-start  delay,  the  display  will  countdown  the
number of seconds remaining before the operator starts

Reverse Delay

If  the  gate  travel  direction  is  reversed  from  user  activation  or
reversing  device  and  a  reverse  delay  is  set,  the  display  will
count  down  the  delay  time  in  seconds  before  the  operator
restarts.

Run Timer

While  the  gate  is  opening  or  closing,  the  number  of   seconds
running time is displayed.

Error Indications

During  abnormal  operation,  the  controller’s  displays  and
beeper will indicate the error condition that has occurred.

Entrapment

If  an  entrapment  condition  occurs  detected  by  two  repeated
open  or  close  obstruction  triggers,  the  controller  will  lock  the
operator  out.  The  beeper  will  sound  constantly  and  the  gate
will  not  operate.  To  reset  the  controller  press  the

STOP

buttons.

COMM LINK Connection Failure

In dual installations, if there is a connection failure between the
two  operators,  the

COMM  LINK

  indicator  will  blink  once  a

second. During this condition the gate will not operate, except
if triggered by the

FIRE DEPT

 input, which functions normally.

MGT Obstacle Transmitter Trouble

If  any  MGT  transmitters  are  used  with  the  operator,  their
supervision feature will alert the controller if there is any trouble
with  the  transmitter.  MGT  transmitters  send  hourly  status
reports  and  will  send  low  battery  reports  when  the  transmitter
has  a  low  battery.  The  MGT  transmitters  also  have  a  tamper
detection switch that will trigger when their case is opened.
When the controller detects a low transmitter battery, a tamper
signal,  or  missing  transmitter  status  reports,  the  gate  will  still
operate normally, but the beeper will change as follows:

The Pre-start Alarm will beep twice as fast.

The run alarm will beep twice as fast and continue for five

minutes after the gate stops.

The sounder will “chirp” every five seconds when the gate

is idle.

Correct the  trouble  (close  case,  replace  battery,  or  replace
transmitter) to clear the obstacle transmitter trouble indications.

Maximum run Time Exceeded

If the Maximum Run Time is exceeded, the controller stops the
operator  the  same  as  if  a  double  obstacle  has occurred  in  an
entrapment 

condition. 

The 

entrapment 

alarm 

sounds

constantly,  and  is  cleared  by  pressing  the

STOP

  button.  After

the

STOP

or

RESET

button is pressed, because the Maximum

Run  Time  has  been  exceeded,  the  sounder  will  beep  twice
every five seconds. The next operation of the gate will clear the
indication.

The Stop and/or Reset button must be located in the line-
of-sight of the gate. Activation of the reset control
shall not cause the operator to start.

WARNING

CONTROLLERERROR CAUSES ANDINDICATIONS

ERROR CAUSE

ERROR INDICATION

HOW TO CLEAR

TWO SAFETY REVERSALS
(ON SINGLE GATE OR ON
EITHER DUAL GATE)

En 00, CONTINUOUS
ALARM BEEPER, GATE
DISABED

PRESS STOP BUTTON

MAXIMUM RUN TIMER
EXCEEDED ON OPENING

En 01, AND

MAX RUN

 LED,

CONTINUOUS ALARM
BEEPER, GATE DISABLED

PRESS STOP BUTTON
CLEARS CONTINUOUS
ALARM, THEN DOUBLE BEEP
EVERY 5 SECONDS UNTIL
NEXT OPERATION

MAXIMUM RUN TIMER
EXCEEDED ON CLOSING

En 02, AND

MAX RUN

 LED,

CONTINUOUS ALARM
BEEPER, GATE DISABLED

PRESS STOP BUTTON
CLEARS CONTINUOUS
ALARM, THEN DOUBLE BEEP
EVERY 5 SECONDS UNTIL
NEXT OPERATION

COMM LINK FAILURE

En 03, AND

COMM LINK

LED, CONTINUOUS ALARM
BEEPER FOR 1 MINUTE,
GATE DISABLED (EXCEPT
FOR FIRE DEPT INPUT)

PRESS STOP BUTTON,
CLEARS CONTINUOUS
ALARM

GATE FULL OPEN
RESULTING FROM FIRE
DEPT INPUT

En 04, GATE DISABLED

PRESS STOP OR RESET
BUTTON, GIVE OPEN OR
CLOSE COMMAND

FAIL SAFE OR FAIL
SECURE
BECAUSE OF AC POWER
LOSS

En 05, GATE DISABLED

BATTERY VOLTAGE MUST
RISE ABOVE 24 VDC

OTHER CONTROLLER IN
ENTRAPMENT (DUAL
GATE)

En 06, GATE DISABLED

CLEAR ENTRAPMENT ON
OTHER CONTROLLER
(PRESS STOP)

LOW AC VOLTAGE AT
CONTROLLER

En 07, GATE DISABLED

LOW VOLTAGE AC POWER
MUST RISE ABOVE 20 VAC

INPUT TRIGGERED
DURING ENTRAPMENT
LOCKOUT

En 08, GATE DISBLED

PRESS STOP BUTTON

COMPATIBILIY PROBLEM

En 09, GATE DISABLED

UPDATE FIRMWARE AND
RESET BOTH PAIRED
CONTROLLERS

EEPROM PROBLEM

En 10, GATE DISABLED

TRY RESET, CALL TECH
SUPPORT

DC MOTOR MISMATCH

En 11, GATE DISABLED

REPROGRAM MOTOR TYPE
OR CHANGE DC MOTOR
BOARD, NEXT GATE
MOEMENT WILL RETRY DC
MOTOR CHECK

MOTOR FAILURE

En 12, GATE DISABLED

REPLACE MOTOR

MGT SUPERVISOY
CONDITION (TAMPER,
LOW BATTERY, MISSING
HOURLY STATUS)

FAST BEEPS DURING
RESTART FAST BEEP RUN
ALARM, CHIRP EVERY 5
SECONDS AT IDLE

CLEARS WHEN MGT
CONDITION CLEARS

Summary of Contents for SL-1000 R

Page 1: ...1 SL 1000 R RESIDENTIAL LIGHT COMMERCIAL SLIDE GATE OPERATOR MADE IN U S A ROTARY GATE SYSTEMS INC ALL RIGHTS RESERVED 2008 REV 1 1 1 877 331 4RGS 4747...

Page 2: ...t reversing Sensor Easy troubleshooting with easy to interpret LED display 200 cycles per day when used on properly installed gates Input for non contact secondary entrapment protection device In addi...

Page 3: ...t setup Stagger mode Stagger delay time Auxiliary relay mode Reverse delay time Low power mode Power failure mode Soft start stop duration Reset cycle count Maintenance alert trigger Mid travel stop p...

Page 4: ...ecurity personnel Approved Obstruction Detection Devices The following contact or non contact obstruction detection devices have been approved for use with this slide gate operator as part of a UL325...

Page 5: ...or installation A good earth ground is necessary to allow the controller s built in surge and lightning protection circuitry to work effectively All ROTARY GATE SYSTEMS gate operators are supplied wit...

Page 6: ...ety devices have been included in the layout of the system o A separate pedestrian gate has been included in the gate layout in a location safe from contact with the vehicular gate when it is in the f...

Page 7: ...7 Access Control Devices The SL 1000 R is compatible with any type of access control device which provides a dry contact relay for activation Installation Figure 2 Gate and Post Layout...

Page 8: ...8 Figure 3...

Page 9: ...st 7 Using a 5 16 drill drill a hole into the post through each of the four holes in the mounting plate Tap the holes using a 3 8 16 tap This step may be eliminated if welding the mounting plate to th...

Page 10: ...ontrol panel Secure the operator motor wire so as to ensure that it will stay c lear of the pinion gear rack gear and gate panel when in motion If necessary the motor wires from the operator can be ad...

Page 11: ...UT TERMINALS SINGLE INPUT TERMINALS PRIMARY SECONDARY COMM LINK TERMINALS FIRE DEPT INPUT TERMINALS ACCESSORY POWER TERMINALS DISPLAY PROGRAMMING BUTTONS INPUT POWER TERMINALS PLUG IN LOOP DETECTOR CO...

Page 12: ...OR CURRENT HAS EXCEEDED THE OPEN CURRENT SETTING WHILE OPENING SET MAXIMUM OPEN CURRENT OPEN OBSTR MGT 2 SET OPEN OBSTRUCTION TERMINAL CONNECTED TO COMMON BY BEAM OR SAFETY EDGE OR SIGNAL FROM MGT OBS...

Page 13: ...HEN STOP AGAIN AT THIS TIME THE AUTO CLOSE TIMER IS DISABLED AND A RENEWED INPUT WILL BE REQUIRED TO START THE GATE AGAIN SHOULD THE GATE BE RESTARTED AND THE OBSTACLE SIGNAL OCCUR AGAIN PRIOR TO REAC...

Page 14: ...CH PHOTOEYE FOR CLOSE OBSTRUCTION FIRE ACCESS SWITCH SOLENOID LOCK EXTERNAl POWER PHOTOEYE FOR OPEN OBSTRUCTION SINGLE CHANNEL RADIO RECEIVER MAGLOCK GATE EDGE SENSOR FOR REVERSE TWO CHANNEL RADIO REC...

Page 15: ...T 110 VAC 110 VAC WIRES ARE UNDER TRANSFORMER MOTOR Connect motor wires from SL 1000 R gate operator LIMIT SWITCHES Connect to the wires from the limit switches Black wires go to COMMON RED to OPEN or...

Page 16: ...f the gate For left hand installations program the controller for left hand operation WHEN CHANGING TO LEFT HAND OPERATION YOU MUST ALSO REVERSE THE MOTOR LEADS IN ADDITION Dual Gate Enable The factor...

Page 17: ...If the close current load exceeds the programmed maximum load number the operator will stop reverse a short distance then stop again If after restart the overload or a close obstacle happens again be...

Page 18: ...o ne operator for delayed opening and the other operator for delayed closing The Stagger Delay Time programming function see below sets the length of the delay NOTE This function will only be displaye...

Page 19: ...is set for Open Immediate alternately the controller can be set for Fail Secure Open Immediate or Close Immediate Fail Safe If the AC power fails and the battery voltage drops below 17 volts 5 second...

Page 20: ...med to open for 1 to 99 seconds the stop before reaching the open limit When a Mid travel stop position time has been programmed the gate will still fully open if the Fire Department input is triggere...

Page 21: ...s function will not erase radio transmitters Transmitters must be deleted with the two functions above DO NOT RESET CONTROLLER WITHOUT CONSULTING TECHNICAL SUPPORT AT 877 331 4747 FUNCTION CL ENTER WH...

Page 22: ...osing at any time Single Input Opens the gate if it s closed and closes th e gate if it s open open close programming option Activating the input while the gate is moving will reverse the gate Can be...

Page 23: ...run alarm will beep twice as fast and continue for five minutes after the gate stops The sounder will chirp every five seconds when the gate is idle Correct the trouble close case replace battery or...

Page 24: ...ndicated by EN 04 on the APeX display To clear this error press the RESET button on the out side of the control box and give the system an OPEN or CLOSE signal Model SL 1000 R Maintenance Battery Main...

Page 25: ...in your area THIS WARRANTY APPLIES ONLY TO THIS PRODUCT WHEN INSTALLED BY A QUALIFIED DEALER AND NOT TO ANY ACCESSORIES THE GATE PANEL ITSELF OR ANY GATE SUPPORT HARDWARE THIS WAR RANTY ONLY COVERS TH...

Reviews: