23
Operation Indications
During normal operation, the controller’s display will indicate
current operating conditions and status.
Power-up Display
When the controller powers up, dashes will show on the
display for one second, then the firmware version number will
be displayed for one second.
Exiting programming restarts the controller. The power -up
display will show upon the restart.
Idle Condition
While the controller is idling, waiting for a command, the
display will show circulation dashes.
Last Gate Position/Condition
When the gate moves or stops, the display will show the status
for up to one minute.
Stop is displayed as
St
Full Close is displayed as
FC
Full Open is displayed as
FO
Entrapment is displayed as
Et
Pre-Start Delay
During the pre-start delay, the display will countdown the
number of seconds remaining before the operator starts
Reverse Delay
If the gate travel direction is reversed from user activation or
reversing device and a reverse delay is set, the display will
count down the delay time in seconds before the operator
restarts.
Run Timer
While the gate is opening or closing, the number of seconds
running time is displayed.
Error Indications
During abnormal operation, the controller’s displays and
beeper will indicate the error condition that has occurred.
Entrapment
If an entrapment condition occurs detected by two repeated
open or close obstruction triggers, the controller will lock the
operator out. The beeper will sound constantly and the gate
will not operate. To reset the controller press the
STOP
buttons.
COMM LINK Connection Failure
In dual installations, if there is a connection failure between the
two operators, the
COMM LINK
indicator will blink once a
second. During this condition the gate will not operate, except
if triggered by the
FIRE DEPT
input, which functions normally.
MGT Obstacle Transmitter Trouble
If any MGT transmitters are used with the operator, their
supervision feature will alert the controller if there is any trouble
with the transmitter. MGT transmitters send hourly status
reports and will send low battery reports when the transmitter
has a low battery. The MGT transmitters also have a tamper
detection switch that will trigger when their case is opened.
When the controller detects a low transmitter battery, a tamper
signal, or missing transmitter status reports, the gate will still
operate normally, but the beeper will change as follows:
The Pre-start Alarm will beep twice as fast.
The run alarm will beep twice as fast and continue for five
minutes after the gate stops.
The sounder will “chirp” every five seconds when the gate
is idle.
Correct the trouble (close case, replace battery, or replace
transmitter) to clear the obstacle transmitter trouble indications.
Maximum run Time Exceeded
If the Maximum Run Time is exceeded, the controller stops the
operator the same as if a double obstacle has occurred in an
entrapment
condition.
The
entrapment
alarm
sounds
constantly, and is cleared by pressing the
STOP
button. After
the
STOP
or
RESET
button is pressed, because the Maximum
Run Time has been exceeded, the sounder will beep twice
every five seconds. The next operation of the gate will clear the
indication.
The Stop and/or Reset button must be located in the line-
of-sight of the gate. Activation of the reset control
shall not cause the operator to start.
WARNING
CONTROLLERERROR CAUSES ANDINDICATIONS
ERROR CAUSE
ERROR INDICATION
HOW TO CLEAR
TWO SAFETY REVERSALS
(ON SINGLE GATE OR ON
EITHER DUAL GATE)
En 00, CONTINUOUS
ALARM BEEPER, GATE
DISABED
PRESS STOP BUTTON
MAXIMUM RUN TIMER
EXCEEDED ON OPENING
En 01, AND
MAX RUN
LED,
CONTINUOUS ALARM
BEEPER, GATE DISABLED
PRESS STOP BUTTON
CLEARS CONTINUOUS
ALARM, THEN DOUBLE BEEP
EVERY 5 SECONDS UNTIL
NEXT OPERATION
MAXIMUM RUN TIMER
EXCEEDED ON CLOSING
En 02, AND
MAX RUN
LED,
CONTINUOUS ALARM
BEEPER, GATE DISABLED
PRESS STOP BUTTON
CLEARS CONTINUOUS
ALARM, THEN DOUBLE BEEP
EVERY 5 SECONDS UNTIL
NEXT OPERATION
COMM LINK FAILURE
En 03, AND
COMM LINK
LED, CONTINUOUS ALARM
BEEPER FOR 1 MINUTE,
GATE DISABLED (EXCEPT
FOR FIRE DEPT INPUT)
PRESS STOP BUTTON,
CLEARS CONTINUOUS
ALARM
GATE FULL OPEN
RESULTING FROM FIRE
DEPT INPUT
En 04, GATE DISABLED
PRESS STOP OR RESET
BUTTON, GIVE OPEN OR
CLOSE COMMAND
FAIL SAFE OR FAIL
SECURE
BECAUSE OF AC POWER
LOSS
En 05, GATE DISABLED
BATTERY VOLTAGE MUST
RISE ABOVE 24 VDC
OTHER CONTROLLER IN
ENTRAPMENT (DUAL
GATE)
En 06, GATE DISABLED
CLEAR ENTRAPMENT ON
OTHER CONTROLLER
(PRESS STOP)
LOW AC VOLTAGE AT
CONTROLLER
En 07, GATE DISABLED
LOW VOLTAGE AC POWER
MUST RISE ABOVE 20 VAC
INPUT TRIGGERED
DURING ENTRAPMENT
LOCKOUT
En 08, GATE DISBLED
PRESS STOP BUTTON
COMPATIBILIY PROBLEM
En 09, GATE DISABLED
UPDATE FIRMWARE AND
RESET BOTH PAIRED
CONTROLLERS
EEPROM PROBLEM
En 10, GATE DISABLED
TRY RESET, CALL TECH
SUPPORT
DC MOTOR MISMATCH
En 11, GATE DISABLED
REPROGRAM MOTOR TYPE
OR CHANGE DC MOTOR
BOARD, NEXT GATE
MOEMENT WILL RETRY DC
MOTOR CHECK
MOTOR FAILURE
En 12, GATE DISABLED
REPLACE MOTOR
MGT SUPERVISOY
CONDITION (TAMPER,
LOW BATTERY, MISSING
HOURLY STATUS)
FAST BEEPS DURING
RESTART FAST BEEP RUN
ALARM, CHIRP EVERY 5
SECONDS AT IDLE
CLEARS WHEN MGT
CONDITION CLEARS