Advanced Controller Programming (Cont.)

Auxiliary Relay Mode

The Auxiliary Relay in the SL -1000 R is not used to release the
magnetic  brake  inside  the  operator  as  in  the  other  RGS
operators.  The auxiliary relay has normally open and normally
closed  contacts.    The  factory  setting  disables  the  Auxiliary
Relay.   The relay can  be set for:

Maglock:

The relay will energize during any pending of

actual  gate  motion  (open  only),  to  deactivate  a
magnetic or solenoid gate lock.

Ticket  Dispenser:

  The  relay  will  energize while  the

gate  is  moving  in  the  open  direction  and  at  the  full
open limit, or in an entrapment condition.

Strobe:

  the  relay  will  energize  during  any  pending  or

actual gate motion (either open or close), to activate a
warning strobe light.

Alarm:

The  relay  will  energize  if  the  gate  is  manually

forced open from the full closed position.

Reverse Delay Time

The  factory  default  sets  the  Reverse  Delay  to  1  second.  The
operator  will  wait  the  length  of  the  delay  before  reversing
direction.  This feature will not change the reversal time when
the operator is responding to an entrapment condition from an
obstruction input or inherent entrapment protection sensor. The
Reverse  Delay  can be set  from  1  to  9 seconds.  Heaver  gates
require a longer delay to allow time for the gate to stop.

Low Power Mode

The  factory  default disables  the  Low  Power  Mode. When  Low
Power Mode is enabled, and AC power fails, the controller will
assume  Low  Power  Mode  after  10  seconds  of  gate  inactivity.
Low Power Mode turns off all accessory power and indicators.
Only  inputs  from  the  radio  receiver,  reverse  loop  or  opening
device will activate gate.

Power Failure Mode

The factory default is set for

Open Immediate

; alternately the

controller  can  be  set  for  Fail  Secure,  Open  Immediate,  or
Close Immediate.

Fail Safe:

 If the AC power fails and the battery voltage drops

below  17  volts,  5  seconds  later  the  operator  will  cycle
open  if  not  already  open  and  cease  operation. When  AC
power  is  restored,  the  operator  will  resume  normal
operation and auto-close if programmed to do so.

Fail  Secure:

  If  the  AC  power  fails  and  the  battery  voltage

drops  below  17  volts,  5  seconds  later  the  operator  will
cycle  closed  if  not  already  closed.  When  AC  power  is
restored,  or  the  battery  gets charged by  solar panels,  the
operator will resume n ormal operation.

Open  Immediate:

    If  the  AC  power  fails,  the  operator  will

cycle  open  if  not  already  open  and  cease  operation.
When  AC  power  is  restored,  the  operator  will  resume
normal operation and auto -close if programmed to do so.

Close  Immediate:

If the  AC  power  fails,  the  operator  will

cycle  closed  if  not  already  closed  and  cease  operation.
When  AC  power  is  restored,  the  operator  will  resume
normal operation.

FUNCTION

“AR”

AUXILIARY RELAY DISABLED

AUZILIARY RELAY USED FOR MAGLOCK
CONTROL

AUXILIARY RELAY USED FOR TICKET
DISPANSER CONTROL

AUXILIARY RELAY USED FOR WARNING
STROBE LIGHT

AUXILIARY RELAY USED FOR CONNECTION
TO ALARM DEVICE

PRESS UP OR DOWN
TO CYCLE THROUGH

OPTIONS

PRESS ENTER TO

SELECT AN OPTION

AUXILIARY

RELAY MODE

OPTIONS

“RD”

SET TIMER VALUE
1 TO 9 SECONDS

FUNCTION

OPTIONS

PRESS UP OR

DOWN TO CYCLE

THROUGH OPTIONS

PRESS ENTER TO

SELECT AN OPTION

REVERSE

DELAY TIME

“FS”

FUNCTION

SET TO FAIL SAFE MODE

SET TO FAIL SECURE MODE

SET TO OPEN IMMEDIATE MODE

SET TO CLOSE IMMEDIATE
MODE

PRESS UP OR DOWN
TO CYCLE THROUGH

OPTIONS

PRESS ENTER TO

SELECT AN OPTION

POWER

FAILURE MODE

LOW POWER MODE
DISBLED

“LP”

FUNCTIONS

OPTIONS

PRESS UP OR DOWN
TO CYCLE THROUGH

OPTIONS

PRESS ENTER TO

SELECT AN OPTION

LOW POWER

MODE

Summary of Contents for SL-1000 R

Page 1: ...1 SL 1000 R RESIDENTIAL LIGHT COMMERCIAL SLIDE GATE OPERATOR MADE IN U S A ROTARY GATE SYSTEMS INC ALL RIGHTS RESERVED 2008 REV 1 1 1 877 331 4RGS 4747...

Page 2: ...t reversing Sensor Easy troubleshooting with easy to interpret LED display 200 cycles per day when used on properly installed gates Input for non contact secondary entrapment protection device In addi...

Page 3: ...t setup Stagger mode Stagger delay time Auxiliary relay mode Reverse delay time Low power mode Power failure mode Soft start stop duration Reset cycle count Maintenance alert trigger Mid travel stop p...

Page 4: ...ecurity personnel Approved Obstruction Detection Devices The following contact or non contact obstruction detection devices have been approved for use with this slide gate operator as part of a UL325...

Page 5: ...or installation A good earth ground is necessary to allow the controller s built in surge and lightning protection circuitry to work effectively All ROTARY GATE SYSTEMS gate operators are supplied wit...

Page 6: ...ety devices have been included in the layout of the system o A separate pedestrian gate has been included in the gate layout in a location safe from contact with the vehicular gate when it is in the f...

Page 7: ...7 Access Control Devices The SL 1000 R is compatible with any type of access control device which provides a dry contact relay for activation Installation Figure 2 Gate and Post Layout...

Page 8: ...8 Figure 3...

Page 9: ...st 7 Using a 5 16 drill drill a hole into the post through each of the four holes in the mounting plate Tap the holes using a 3 8 16 tap This step may be eliminated if welding the mounting plate to th...

Page 10: ...ontrol panel Secure the operator motor wire so as to ensure that it will stay c lear of the pinion gear rack gear and gate panel when in motion If necessary the motor wires from the operator can be ad...

Page 11: ...UT TERMINALS SINGLE INPUT TERMINALS PRIMARY SECONDARY COMM LINK TERMINALS FIRE DEPT INPUT TERMINALS ACCESSORY POWER TERMINALS DISPLAY PROGRAMMING BUTTONS INPUT POWER TERMINALS PLUG IN LOOP DETECTOR CO...

Page 12: ...OR CURRENT HAS EXCEEDED THE OPEN CURRENT SETTING WHILE OPENING SET MAXIMUM OPEN CURRENT OPEN OBSTR MGT 2 SET OPEN OBSTRUCTION TERMINAL CONNECTED TO COMMON BY BEAM OR SAFETY EDGE OR SIGNAL FROM MGT OBS...

Page 13: ...HEN STOP AGAIN AT THIS TIME THE AUTO CLOSE TIMER IS DISABLED AND A RENEWED INPUT WILL BE REQUIRED TO START THE GATE AGAIN SHOULD THE GATE BE RESTARTED AND THE OBSTACLE SIGNAL OCCUR AGAIN PRIOR TO REAC...

Page 14: ...CH PHOTOEYE FOR CLOSE OBSTRUCTION FIRE ACCESS SWITCH SOLENOID LOCK EXTERNAl POWER PHOTOEYE FOR OPEN OBSTRUCTION SINGLE CHANNEL RADIO RECEIVER MAGLOCK GATE EDGE SENSOR FOR REVERSE TWO CHANNEL RADIO REC...

Page 15: ...T 110 VAC 110 VAC WIRES ARE UNDER TRANSFORMER MOTOR Connect motor wires from SL 1000 R gate operator LIMIT SWITCHES Connect to the wires from the limit switches Black wires go to COMMON RED to OPEN or...

Page 16: ...f the gate For left hand installations program the controller for left hand operation WHEN CHANGING TO LEFT HAND OPERATION YOU MUST ALSO REVERSE THE MOTOR LEADS IN ADDITION Dual Gate Enable The factor...

Page 17: ...If the close current load exceeds the programmed maximum load number the operator will stop reverse a short distance then stop again If after restart the overload or a close obstacle happens again be...

Page 18: ...o ne operator for delayed opening and the other operator for delayed closing The Stagger Delay Time programming function see below sets the length of the delay NOTE This function will only be displaye...

Page 19: ...is set for Open Immediate alternately the controller can be set for Fail Secure Open Immediate or Close Immediate Fail Safe If the AC power fails and the battery voltage drops below 17 volts 5 second...

Page 20: ...med to open for 1 to 99 seconds the stop before reaching the open limit When a Mid travel stop position time has been programmed the gate will still fully open if the Fire Department input is triggere...

Page 21: ...s function will not erase radio transmitters Transmitters must be deleted with the two functions above DO NOT RESET CONTROLLER WITHOUT CONSULTING TECHNICAL SUPPORT AT 877 331 4747 FUNCTION CL ENTER WH...

Page 22: ...osing at any time Single Input Opens the gate if it s closed and closes th e gate if it s open open close programming option Activating the input while the gate is moving will reverse the gate Can be...

Page 23: ...run alarm will beep twice as fast and continue for five minutes after the gate stops The sounder will chirp every five seconds when the gate is idle Correct the trouble close case replace battery or...

Page 24: ...ndicated by EN 04 on the APeX display To clear this error press the RESET button on the out side of the control box and give the system an OPEN or CLOSE signal Model SL 1000 R Maintenance Battery Main...

Page 25: ...in your area THIS WARRANTY APPLIES ONLY TO THIS PRODUCT WHEN INSTALLED BY A QUALIFIED DEALER AND NOT TO ANY ACCESSORIES THE GATE PANEL ITSELF OR ANY GATE SUPPORT HARDWARE THIS WAR RANTY ONLY COVERS TH...

Reviews: