E1 Model selection (ON/OFF, Continu-
ous %, 4 steps)
Depending on
settings
E2 Lowest voltage control loop 1
0
0
5.0
Volt
E3 Highest voltage value control loop 1
10.0
5.0
10.0
Volt
E4 Start value at output (1= Min., 2=
Max., 3= Last)
3
1
3
E5 Invert voltage value
OFF
OFF
ON
E6 Relay limit value/ threshold value
0.1
0.0
10.0
Volt
E25 Minimum voltage setpoint genera-
tor input Vin2 (C6 = external)
0.0
0.0
10.0
Volt
E26 Maximum voltage of setpoint gen-
erator input Vin2 (C6 = external)
10.0
0.0
10.0
Volt
E27 Scaling the minimum voltage from
the setpoint generator in % Input Vin2
(C6 = external)
0
0
100
%
E40 Use control output 2 Vout2:
0=10V constant,
1= not used,
2 = Off- Set to control output 1,
3 = 10V constant when switched on
4 = 10V if E17 exceeded
0
0
4
E42 Select temperature sensor or signal
source control loop 2 Extern: NTC =
terminals 20-21 Volt = Sensor 0-10V at
terminals 7-8; Alarm 1: Alarm, at termi-
nals 20-21 (= open), switch/ PIR1 *: Mo-
tion detector, terminals 20-21 (Normal
setpoint or alternative setpoint at con-
tact open), NTC10K: NTC at terminals
20-21, switch/ PIR2 *: Motion detector
terminals 20-21 (normal setpoint or OFF
at contact open)
Alarm 2: Indicate alarm, at terminals 20-
21 = open Relay does not release
Extern
0
8
E44 User/ system text max. 12 charac-
ters, enabled by C9
System name
E45 Operating hours text max. 12 char-
acters 6 lines, enabled by C10
E46 Lower limit alarm, only for tachome-
ter signal
10
0
50
E47 Alarm upper limit value, only for
tacho signal
60
50
100
E48 Time delay PIR motion detector *
600
1
3600
Sek.
E49 Off-Set Vout2 to Vout1
Formula Vout2=Vout1 x (E49/100).
100%
0
200
%
E52 Control time delay
if E6 >0: relay is used for
Damper drive function used
0
0
240
Secund
E55 Level step 1, fan step 1
25
0
100
%
E56 Level step 2, fan step 2
50
0
100
%
E57 Level step 3, fan step 3
75
0
100
%
E58 Level step 4, fan step 4
100
0
100
%