The selection for D6 is „
Manual Regulator
“. The chart chapter 7.3 is valid!
(Chart 7.3 shows the variety of all parameter settings.
The choice below is exactly the same in the display
after confirmation „Manu-
al Regulator“
by ENTER). Rosenberg point out the described applications.
05
“
Manual 4 stages
”
The manual intervention at the display of the MTC MultiControl selects 1 out of 4
definable stages air volume flow. The 4 steps MultiControl 0-10Vdc signal output
are selectable parameters in the program. These parameters can be individual set
to the need values. The appropriate values should be in relation to the character-
istic curves of the single or multiple parallel EC fans in use (plant pressure to plant
air volume flow).
Example see Rosenberg´s German application description. “Kitchen waste
air handling”
06
“
2 stages PIR
”
The external intervention of a switch (PIR, hygrostat, thermostat) at an input of
the MTC MultiControl selects between 2 definable stages for demand of air vol-
ume flow. The Options are switch-off the fan or to provide a minimum speed (air
volume flow)
Example see Rosenberg´s German application description. “Operation for
used room”
*Definition of terms: PIR is used in this document as a name for motion detectors or ex-
ternal switches, or hygrostat, thermostat.
8
Parameter and Settings
Individual displays of the MTC- MultiControl controller are only displayed if the
respective default settings have been selected.
The commissioning should be carried out again after connecting a new accesso-
ry. It may also be necessary to deactivate the corresponding control function
before disconnecting accessories.
8.1
Parameter List
These parameters in the service menu E and display menu D are protected by password 5550.
Description
Default
Min
Max
Unit
Menu C = User
C1 Controller 1, day setpoint (NORM),
depending on parameter E1
Pressure:
200
Air flow:
---
Temp: 22.0
Pressure:
0
Air flow:
0
Temp. -20.0
Pressure:
9999
Air flow:
9999
Temp. +65.0
Pressure: Pa
Air flow: m
3
/h
Temp.: °C
C2 Calendar Switching ON/OFF (enable)
OFF
OFF
ON
OFF/ON
C3 Controller 1, alternative setpoint (ALT),
depending on parameter E1
Pressure:
200
Air flow:
---
Temp: 22.0
Pressure:
0
Air flow:
0
Temp. -20.0
Pressure:
9999
Air flow:
9999
Temp. +65.0
Pressure: Pa
Air flow: m
3
/h
Temp.: °C
C4 User rights 0= Level D and E have
password protection (do not modify, to
contact Rosenberg)
0
0
3