BA 417 BB 05 21 A2
35
E7 Control character of control loop 1
0=PID (linear, dynamic)
1=XP (linear, continuous without time
portion, proportional)
PID
PID
XP
E8 Control loop 1 proportional range /
gain if E7 = XP
Temp: 2.0
Pressure: 50
Humidity: 10
CO
2
: 200
Temp: 0.5
Pressure: 2
Humidity: 5
CO
2
: 50
Temp: 25.0
Pressure: 1000
Humidity: 40
CO
2
: 500
°C, m/s, Pa, %,
ppm
E9 Basic value of control loop 1, output
signal at setpoint
5.0
0,1
10,0
Volt
E10 proportional value P Control loop 1
if E7 = PID
Temp: 20
Pressure: 40
Humidity: 40
CO
2
: 40
1
100
E11 Dynamic integration time I Control
circuit 1 if E7 = PID
Temp: 100
Pressure: 20
Humidity: 20
CO
2
: 20
0
5000
E12 Sampling Time PID control circuit 1
3
1
10
x100 mSek
E13 Min. sensor voltage control circuit 1
0,0
0,0
10,0
Volt
E14 Max. sensor voltage control circuit 1
10,0
0,0
10,0
Volt
E15 Sensor value at min. sensor voltage
in Volt at input control loop 1
Temp: 0.0
Pressure: 0
Humidity: 0
CO
2
: 0
Temp: -40.0
Pressure: 0
Humidity: 0
CO
2
: 0
Temp: 60.0
Pressure: 5000
Humidity: 100
CO
2
: 5000
°C, m/s, Pa, %,
ppm
E16 Sensor value at max. sensor voltage
in Volt at input control loop 1
Temp: 50.0
Pressure: 500
Humidity: 100
CO
2
: 2000
Temp: -40.0
Pressure: 0
Humidity: 0
CO
2
: 0
Temp: 60.0
Pressure: 5000
Humidity: 100
CO
2
: 5000
°C, m/s, Pa, %,
ppm
E17 Min. Voltage output control loop 1
0,0
0,0
5,0
Volt
E18 Max. Voltage output control loop 1
10,0
5,0
10,0
Volt
E19 Pulse periods Time when PWM is
selected (D6= 2, 3, 4)
30
10
250
sec
E20 Outdoor temperature OFF/ON
(NTC2)
OFF
OFF
ON
OFF/ON
E21 Outdoor temperature reduction
(D6 = pressure control)
Pressure:
0
Pressure:
-500
Pressure:
500
Pressure: Pa
E22 Range min. outside temp. reduction
-10 °C
0,0 °C
-25 °C
°C
E23 Range max. Outside temp. reduc-
tion
10,5 °C
-10 °C
15 °C
°C
E25 Min. sensor voltage control loop 2
0,0
0,0
10,0
Volt
E26 max. sensor voltage control loop 2
10,0
0,0
10,0
Volt
E27 Sensor value at min. sensor voltage
in Volt at input control loop 2
Temp: 0.0
Pressure: 0
CO
2
: 0
Temp: -40.0
Pressure: 0
CO
2
: 0
Temp: 60.0
Pressure: 5000
CO
2
: 5000
°C, Pa, ppm
E28 Sensor value at max. sensor voltage
in Volt at input control loop 2
Temp: 50.0
Pressure: 500
CO
2
: 2000
Temp: -40.0
Pressure: 0
CO
2
: 0
Temp: 60.0
Pressure: 9999
CO
2
: 5000
°C, Pa, ppm
E29 Control loop 2 ON = maximum
selection OFF = control circuit 2 at con-
trol output 2
OFF
OFF
ON
OFF/ON
E30 Control character control loop 2
PID
PID
XP