eng eng
● Only allow trained persons to use the electrical device. Apprentices may
only operate the electrical device when they are older than 16, when this is
necessary for their training and under the supervision of a trained operative.
● Check the power cable of the electrical device and the extension leads
regularly for damage.
Have these renewed by qualifi ed experts or an authorised
ROLLER customer service workshop in case of damage.
● Only use approved and appropriately marked extension leads with a suffi -
cient cable cross-section. Use extension leads up to a length of 10 m with
cable cross-section 1.5 mm², from 10 – 30 m with cable cross-section 2.5 mm².
Explanation of symbols
WARNING
Danger with a medium degree of risk which could result in
death or severe injury (irreversible) if not heeded.
CAUTION
CAUTION
Danger with a low degree of risk which could result in minor
injury (reversible) if not heeded.
NOTICE
Material damage, no safety note! No danger of injury.
Read the operating manual before starting
Use hand protection
Power tool complies with protection class I
Environmentally friendly disposal
CE conformity mark
Not suitable for using outdoors
1. Technical Data
Use for the intended purpose
WARNING
The ROLLER’S Scirocco 50 and ROLLER’S Scirocco 80 electric air dehumidifi ers/
building driers are intended for drying and dehumidifying rooms, e.g. after mains
water damage, fl ooding, dehumidifi cation of damp cellar rooms etc. and for fast
drying of concrete, masonry, plaster and screed for example. The operating hours
counter and electricity meter is intended for recording the operating hours and
electricity consumption when drying and dehumidifying with ROLLER’S Scirocco 50.
For commercial use in trade and industry. All other uses are not for the intended
purpose and are therefore prohibited.
1.1. Scope of Supply
ROLLER’S Scirocco 50, 7.7 l condensation tank, condensation draining hose,
operating instructions.
ROLLER’S Scirocco 80, operating instructions.
1.2. Article numbers
ROLLER’S Scirocco 50 Set
132011
ROLLER’S Scirocco 80 Set
132010
11.5 l condensation tank Scirocco 80 132100
Connecting fl ange
Scirocco 80 132101
Exhaust air hose Ø 200 mm, 10 m long, Scirocco 80 132102
Exhaust air set Scirocco 80
(connecting fl ange,
exhaust air hose Ø 200 mm)
132104
Condensation tank with pump Scirocco 50
132129
Condensation tank with pump Scirocco 80
132121
Operating hours counter and electricity meter
132132
ROLLER’S Control W, dielectric humidity meter
132115
Machine cleaner
140119
1.3. Applications
Scirocco 50
Scirocco 80
Dehumidifi cation rate
≤ 50 l/24 h
≤ 80 l / 24 h
Air volume
≤ 265 m
3
/h
≤ 850 m
3
/h
33
Adjustment range of
the relative humidity
30 – 90 %
30 – 90 %
Compressor
Rotation piston compressor Rotation piston compressor
Ambient temperature
+5 °C – +32 °C
+5 °C – +32 °C
+5 °C – +32 °C
+5 °C – +32 °C
(41 °F – 89 °F)
(41 °F – 89 °F)
Storage temperature
+5° C – +45 °C
+5° C – +45 °C
+5° C – +45 °C
+5° C – +45 °C
(41 °F – 113 °F)
(41 °F – 113 °F)
1.4. Electrical data
Air dehumidifi er/
220 – 240 V~; 50 Hz 220
240 V~; 50 Hz
240 V~; 50 Hz
– 240 V~; 50 Hz
building drier
900 W; 4.1 A
1200 W; 5.3 A
Protection class I
Protection class I
Condensation tank
100 – 240 V~; 50 – 60 Hz 100 – 240 V~; 50 – 60 Hz
with pump
12 V –
---
12 V –
---
Scirocco 50
Scirocco 80
Operating hours counter
230 V~; 50 Hz
and electricity meter
≤ 3680 W
Protection class I
Protection class IP20
4,5 V –
---
1.5. Coolant data
Coolant
R-410A R-407C
GWP
2088
1774
CO
2
comp.
0,6682 t
1,455 t
Filling quantity
0.320 kg
0.820 kg
0.320 kg
0.320 kg
Operating pressure low pressure side
≤ 18 bar
≤ 10 bar
≤ 18 bar
≤ 18 bar
Operating pressure high pressure side
≤ 36 bar
≤ 25 bar
≤ 36 bar
≤ 36 bar
1.6. Dimensions L × W × H
385 × 320 × 595 mm
540 × 530 × 1 040 mm
(15,2" × 12,6" × 23,4")
(21,3" × 20,9" × 40,9")
1.7. Weight
21 kg (46 lbs)
54 kg (119 lbs)
1.8. Noise information
Work place-related
Emission value
L
pA
= 57 dB (A) L
pA
= 63 dB (A)
K = 3 dB (A)
K = 3 dB (A)
2. Start-up
CAUTION
CAUTION
Transport weights above 35 kg must be carried by at least 2 persons.
NOTICE
Only transport/store the ROLLER’S Scirocco 50, ROLLER’S Scirocco 80 in an
upright position. Do not lie it on its side! Leave the ROLLER’S Scirocco 50,
ROLLER’S Scirocco 80 to stand for at least one hour before putting into oper-
ation.
2.1. Electrical connection
WARNING
Caution: Mains voltage present! Before connecting the device or the conden-
sation tank with pump or the operating hours counter and electricity meter, check
whether the voltage given on the rating plate corresponds to the mains voltage.
Only connect devices of protection class I to a socket/extension lead with a
functioning protective contact. On building sites, in a wet environment, indoors
and outdoors or under similar installation conditions, permanently connected
to a permanently installed pipe, only operate the device or the condensation
tank with pump with a fault current protection switch (RCD) which interrupts
the power supply as soon as the leakage current to earth exceeds 30 mA for
200 ms.
2.2. Fitting the handle to the tubular steel frame of the ROLLER’S Scirocco 80
See Fig. 1.
2.3. Installation of the device with draining of the condensation into an external
tank or into a drain pipe
2.3.1.
Place the ROLLER’S Scirocco 50 in the centre of the room to be dehumidifi ed
on a level base. The minimum distance from the wall must be 200 mm. Close
all doors and windows to the outside. Unscrew the union nut (Fig. 6 (19).
Remove the plug (20). Push the condensation draining hose (4) through the
hole of the union nut until the hose fl ange is touching. Screw on and tighten
the union nut. Feed the condensation draining hose (4) into a suitable tank or
lengthen the hose which feeds directly into a drain pipe.
Operating hours counter (Fig. 9 (7)) and electricity meter (Fig. 9 (8)) (accessory
Art No. 132132).
2.3.2. Place the ROLLER’S Scirocco 80 in the centre of the room to be dehumidifi ed
on a level base. The minimum distance from the wall must be 200 mm. Close
all doors and windows to the outside. Remove the detachable power cable
from the tray (1) and connect it. The back
light of the display (2) comes on briefl y.
from the tray (1) and connect it. The back
from the tray (1) and connect it. The back
Press down the fl ap on top of the condensation tank (3) to open it. Push the
hose for draining the condensation (4) through the hole in the housing from the
inside to the outside. Feed the condensation draining hose (4) into a suitable
tank or lengthen the hose which feeds directly into a drain pipe. Set the conden-
sation tank switch (5) in the direction of the symbol showing the crossed out
tank. Close the fl ap of the condensation tank (3).
ROLLER’S Scirocco 80 is equipped with an operating hours counter (7) and
an electricity meter (8).
2.4. Install the device with condensation draining into the condensation tank
(9) or into the condensation tank with pump (Fig. 7, 8)
2.4.1. Place the ROLLER’S Scirocco 50 in the centre of the room to be dehumidifi ed
on a level base. The minimum distance from the wall must be 200 mm. Close
all doors and windows to the outside. Check whether the union nut (Fig. 6 (19))
11