Publication 1771-6.5.132 - June 2000
5-12
Communicating with DeviceNet from Another Network
Configuring the DeviceNet Pass-Through Driver
Before you can communicate with the 1771-SDN module via the
Ethernet network, you must configure the DeviceNet pass-through
driver (1771-SDNPT). RSLinx, version 2.10 or higher, is required.
Connect your 1785-ENET module to your Ethernet network. Then
perform the following steps.
1.
Start
RSLinx
.
2.
From the
Communications
menu, select
Configure Drivers
.
3.
From the list of
Available Driver Types
select
DeviceNet Drivers
and click on
Add/New
.
Summary of Contents for DEVICENET 1771-SDN
Page 1: ...PLC 5 DeviceNet Scanner Module 1771 SDN User Manual...
Page 4: ......
Page 12: ...Publication 1771 6 5 132 June 2000 P 8 About This User Manual...
Page 16: ...Publication 1771 6 5 132 June 2000 Table of Contents iv...
Page 28: ...Publication 1771 6 5 132 June 2000 1 12 Before You Begin...
Page 52: ...Publication 1771 6 5 132 June 2000 3 14 Hardware Setup...
Page 70: ...Publication 1771 6 5 132 June 2000 4 18 Configuring the DeviceNet Network...
Page 94: ...Publication 1771 6 5 132 June 2000 5 24 Communicating with DeviceNet from Another Network...
Page 122: ...Publication 1771 6 5 132 June 2000 C 4 Installing and Configuring the DH Communications Driver...
Page 132: ...Publication 1771 6 5 132 June 2000 D 10 Data Map Example...
Page 137: ......