Publication 1771-6.5.132 - June 2000
3-8
Hardware Setup
Setting the Channel 1 Data Rate and Node Address Switches
1.
Locate the switchbank labeled “Channel 1” on the left side of the
module.
2.
Set the DeviceNet Data Rate for Channel 1 to 500K baud for the
example application by setting switch 1 to an ON (“1”) position
and switch 2 to an OFF (“0”) position.
3.
Set the DeviceNet node address for Channel 1 to node 0 for the
example application by setting switches 3 through 8 to the OFF
(“0”) position.
Setting the I/O Chassis Addressing Node Switches
Set the I/O chassis addressing mode to 1-slot for the example
application.
1.
Locate the switchbank labeled “Configuration” on the left side of
the module.
2.
Set switch 7 to an OFF (“0”) position and switch 8 to an ON (“1”)
position.
TIP
Refer to the table on the left side of the module to
set the channel to a different node address. The
address range is 0 to 63.
IMPORTANT
The node address setting must not conflict with the
node address of any other device on the network.
Note that channel 2 is not used for the example
application.
IMPORTANT
Make sure switches 1 through 6 in the Configuration
switchbank always remain in the OFF (“0”) position.
IMPORTANT
The chassis addressing mode setting for the 1771 I/O
chassis (page 3-2) must match the I/O chassis
address setting of the scanner. If the switches do not
match, data will be lost in the data transfer between
the PLC-5 processor and the scanner module.
Channel 1
= ON = 1
= OFF = 0
1
2
3
4
5
6
7
8
O N
= ON = 1
= OFF = 0
Configuration
1
2
3
4
5
6
7
8
O N
Summary of Contents for DEVICENET 1771-SDN
Page 1: ...PLC 5 DeviceNet Scanner Module 1771 SDN User Manual...
Page 4: ......
Page 12: ...Publication 1771 6 5 132 June 2000 P 8 About This User Manual...
Page 16: ...Publication 1771 6 5 132 June 2000 Table of Contents iv...
Page 28: ...Publication 1771 6 5 132 June 2000 1 12 Before You Begin...
Page 52: ...Publication 1771 6 5 132 June 2000 3 14 Hardware Setup...
Page 70: ...Publication 1771 6 5 132 June 2000 4 18 Configuring the DeviceNet Network...
Page 94: ...Publication 1771 6 5 132 June 2000 5 24 Communicating with DeviceNet from Another Network...
Page 122: ...Publication 1771 6 5 132 June 2000 C 4 Installing and Configuring the DH Communications Driver...
Page 132: ...Publication 1771 6 5 132 June 2000 D 10 Data Map Example...
Page 137: ......