Publication 1771-6.5.132 - June 2000
A-2
1785-ENET Module Channel Configuration
2.
Select the
Channel 3A
tab.
3.
Select
Ethernet
as the
Channel Type
.
4.
Uncheck the
BOOTP Enabled
box to disable BOOTP.
5.
Enter the
IP Address
you want to assign to the PLC-5 processor
(e.g., 130.130.130.2).
6. Download
the configuration to the processor, using a
communications driver that was previously configured, (e.g,
ControlNet or DH+). See chapter 6 for examples of downloading
to the PLC-5 using these drivers.