Publication 1771-6.5.132 - June 2000
3-4
Hardware Setup
To go online to the PLC-5 processor via Data Highway Plus:
1.
Define the DH+ station address of channel 1A by setting switch
assembly SW-1 on the back of the processor. For the example
application we used address 1. (Set switch 4 in the up position, and
switches 1, 2, 3, 5, and 6 in the down position.)
2.
Set the baud rate to 57.6 Kbaud by placing switch 7 in the up
position.
See Appendix C for information on installing and configuring the Data
Highway Plus driver.
TIP
See the information on the side of the processor if
you want to use another address.
back view of processor
up
down
side view
Switch 7 in the “up” position.