Publication 2711P-UM001D-EN-P - September 2005
Installation
2-3
Application Information
Per the National Electrical Code, the circuit parameters of associated
field wired apparatus for use in hazardous locations shall be
coordinated with the host product such that their combination
remains nonincendive. The PanelView Plus terminal and the USB
peripheral device shall be treated in this manner.
The circuit parameters of the PanelView Plus USB ports are given in
Table 2.1. The USB peripheral device and its associated cabling shall
have circuit parameters with the limits given in Table 2.2 for them to
remain nonincendive when used with the PanelView Plus USB port. If
cable compliance and inductance are not known, use the following
values from UL 913:
C
cable
= 60 pF/ft
L
cable
= 0.20 µH/ft
Environmental
Considerations
The terminals are suitable for use in an industrial environment when
installed in accordance with these instructions. Specifically, this
equipment is intended for use in clean, dry environments (Pollution
Degree 2)
(1)
and with circuits not exceeding Over Voltage Category
II
(2)
(IEC 60664-1).
(3)
(1) Pollution Degree 2 is an environment where, normally only non-conductive pollution occurs except that
occasionally a temporary conductivity caused by condensation shall be expected.
(2) Over Voltage Category II is the load level section of the electrical distribution system. At this level transient
voltages are controlled and do not exceed the impulse voltage capability of the product’s insulation.
(3) Pollution Degree 2 and Over Voltage Category II are International Electrotechnical Commissions (IEC)
designations.
Enclosures
The terminals must be mounted in a panel or enclosure to protect the
internal circuitry. The terminals meet IP54, IP65 and NEMA Type
12/13 and 4X (indoor) ratings only when mounted in a panel or
enclosure with the equivalent rating. When the terminal is not
mounted in a panel, it is not secure or safe for operation. You must
comply with NEMA Type 4X (indoor) requirements for environmental
specifications.
For more enclosure and certification information on the Outdoor
High-Bright display module, refer to publication 2711P-IN026.
Summary of Contents for Allen-Bradley PanelView Plus 400
Page 1: ...PanelView Plus Terminals 2711P 400 600 700 1000 1250 1500 User Manual...
Page 6: ...Publication 2711P UM001D EN P September 2005 Table of Contents iv...
Page 44: ...Publication 2711P UM001D EN P September 2005 2 16 Installation...
Page 56: ...Publication 2711P UM001D EN P September 2005 3 12 Connect Power...
Page 160: ...Publication 2711P UM001D EN P September 2005 7 12 Transfer files and Upgrade Firmware...
Page 176: ...Publication 2711P UM001D EN P September 2005 8 16 Troubleshooting...
Page 182: ...Publication 2711P UM001D EN P September 2005 B 2 Compatible USB Devices...
Page 191: ...Publication 2711P UM001D EN P September 2005 Index 5...
Page 192: ......